CONTRACTOR'S MATERIAL&TEST CERTIFICATE FOR ABOVEGROUND PIPING
PROCEDURE
Upon conwletlon of work,Inspection end tests shall be made by the contractor's representative and witnessed by an owner's representative. All
defects shall be corrected and system left In service before contractor's personnel finally leave the job.
A certlfl ate shall be filled out and signed by both representatives. Copies shell be prepared for approving authorities,owners and eontrector,
It Is understood the owner's representative's signature in no way prejudices any claim against contractor for faulty material,poor workmanship,
or failure to comply with approving authority's requirements or load ordinances.
PROPERTr-tiAME GATE
11 ' Ail
chi CD 1/V CPROPE TV ADDRESS - f� / ) 1( • V o,1 '_ f $ ¶cv -
ACCEPTED SY APPROVING AUTHORITY1 NAMES
(--r 'l
11
ADDRESS
PLANS
INSTALLATION CONFORMS TO ACCEPTED PLANSr S 0 NO
EQUIPMENT USED 15 APPROVED JjS 0NO
IF NO,EXPLAIN DEVIATIONS
HAS PERSON IN CHARGE OF FIRE EQUIPMENT SEEN INSTRUCTED AS TO LOCATION 12i'EE ONO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT
IF NO,EXPLAIN
INSTRUCTIONS COPIESo uu
AND NOF AP ROPR OA S tNSTPREMIRV TIONS AND CARE AND MAINTENANCE CHARTS [IVES 0 NO
IF NO,EXPLAIN
LOCATION SUPPLIESSLOGS.
OF SYSTEM k ./1 ( ii!� fy ,y'r.' 0' I N FrnasQ,/_� 1?" bli- A/7'
/-f MVAKE V_*'r I MODEL ,YEEAR O wrORIIFI`CE QUANTITY TEMPERATURE f
MANUFACTURE ZE RATING
6LtG klet-,4' Fe{v 1 1_o '- L `' ( !3"tj r'
SPRINKLERS 'K=ZL lel /31.�? E( ;Yr� Q ,k, 'UM V'7 f I 1 i f.,--g'
PIPE CONFORMS TO iv/pot , . STANDARD OYES D NO
PIPE AND FITTINGS CONFORM TO N /P Jy _ STANDARD OYES ONO
FITTINGS IF NO,EXPLAIN
ALARM DEVICE MAXIMUM TIME TO OPERATE THROUGH TEST PIPE
ALARM -
VALVE TYPE ; MAKE `� MODEL MIN. SEC.
OR FLOW J S�"� /E-( fGD _
INDICATOR W!Tr(�1L Z _ .5t-g----
DRY VALVE 00.0.
MAKE. MODEL SERIAL NO. MAKE MODEL SERIAL NO.
TIME TO TRIP WATER AIR I TRIP POINT TI E WATER ALARM
THRU TEST PIPE" PRESSURE PRESSURE AIR PRESSURE REACHED OPERATED
TEST OUTLET' PROPERLY
DRY PIPE MIN. SEC. PSI PSI PSI MIN. SEC. YES NO
OPERATING
TEST Without
O.O.O.
O.O.DWltn
.
IF NO.EXPLAIN
•MEASURED FROM TIM!INSPECTOR'S TEST PIPE IS OPENED.
SSA pew PRINTED IN USA (OVER)
Contractor's Material&Tat Certificate for Aboveground Piping
13-10 SPRINKLER SYSTEMS
nnmes
OPERATION
❑PNEUMATIC 0 ELECTRIC ❑HYDRAULIC
PIPING SUPERVISED OYES ONO 'DETECTING MEDIA SUPERVISED DYES ONO
DOES VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE CONTROL STATIONS DYES NO
DELUGE 8 IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT FOR TESTING IF NO,EXPLAIN
/REACTION ❑YES ❑NO
VA V(ES DOES EACH CIRCUIT OPERATE DOES EACH CIRCUIT
MAKE MODEL SUPERVISION LOSS ALARM OPERATE VALVE RELEASE MAXIMUM TIME TO
OPERATE RELEASE
YES NO YES NO MIN. SEC.
HYDROISTATIC: Hydrostatic tests shall be made at not less than 200 psi(13.6 bars)for two hours or 50 psi(3.4 bars)above static
pressure in excess of 150 psi(10.2 bars)for two hours. Differential drypipe valve clappers shall be left open during test to prevent damage.
All aboveground piping leakage shall be stopped.
TEST FLUSHING: Flow the required rate until water is clear es indicated by no collection of foreign material in burlap bags at outlets such as
DESCRIPTION hydrants and blow-offs. Flush at flows not less than 400 GPM(1514 L/min)for 4-inch pipe 600 GPM 12271 L/min)for 5-Inch pipe,
750 GPM(2839 L/min)for 6-inch pipe,1000 GPM(3785 L/min)fôr 8-inch pipe,1500 GPM(5678 L/min)for 10-inch pipe and 2000
GPM(7570 L/min)for 12-Inch pipe. When supply cannot produce stipulated flow rates,obtain maximum available.
PNEUMATIC:Establish 40 psi(2.7 bars)air pressure and measure drop which shall not exceed 1-14 psi(0.1 bars)in 24 hours. Test
pressure tans at normal water level and air pressure and measure air pressure drop which shall not exceed 1-%psi(0.1 bars)in 24 hours.
ALL PIPING HYDROSTATICALLY TESTED AT PSI FOR �-RS. IF NO,STATE REASON
DRY PIPING PNEUMATICALLY TESTED OYES ❑N T ;
• e /n ( C f i i�.....__
EQUIPMENT OPERATES PROPERLY OYES ❑NO /4 " "— I �"
DRAIN READING OF GAGE LOCATED R R SUPPLY TEST PIPE, R DUAL PR E WITH VALVE IN TEST PIPE OPEN WIDE
TESTS TEST STATIC PRESSURE: PSI PSI
Underground mains and le n connections to system risers flushed before connection made to sprinkler piping.
VERIFIED BY COPY OF THE U FORM NO.ass OYES ❑NO OTHER EXPLAIN
FLUSHED BY INSTALLER OF UNDER•
GROUND SPRINKLER PIPING OYES ONO
BLANK TESTING NUMBER USED LOCATIONS NUMBER REMOVED
GASKETS
WELDED PIPING ❑YES 11JNU
IF YES...
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES COMPLY
WITH THE REQUIREMENTS OF AT LEAST AWS 010.9,LEVEL AR-3 ❑YES ❑NO
DO YOU CERTIFY THAT THE WELOINO WAS PERFORMED BY WELDERS QUALIFIED IN
WELDING COMPLIANCE WITH THE REQUIREMENTS OF AT LEAST AWS 010.9,LEVEL AR-3 DYES 0 NO
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A
DOCUMENTED QUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE
RETRIEVED,THAT OPENINGS IN PIPING ARE SMOOTH,THAT SLAG AND OTHER
WELDING RESIDUE ARE REMOVED,AND THAT THE INTERNAL DIAMETERS OF DYES ❑NO
PIPING ARE NOT PENETRATED
HYDRAULIC NAMEPLATE PROVIDED IF NO,EXPLAIN
DATA �, ,/
NAMEPLATE Wertri.' ❑NO
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN:
REMARKS
NAME OF RINKLER CONTRACTOR
TESTS WITNESSED BY
SIGNATURES FOR PROPERTY OWNER(SIGNED) TITLE DATE
I 1
FORS NKLER CONTACT R(SIGNED) TITLE DAT -
(
ADDITIONAL EXPLA ATION AND NOTES
aSA BACK
Contractor's Material&Test Certificate for Aboveground Piping