HomeMy WebLinkAboutFP 2016-00293 Fire Protection - New Holiday Station CITY OF OAK PARK HEIGHTS PERMIT NO.: 2016-00293
14168 OAK PARK BLVD N. #2007
OAK PARK HEIGHTS, MN 55082-2007 DATE ISSUED: 11/21/2016
(651)351-1661 FAX: (651) 439-0574
ADDRESS : 5997 OSGOOD AVE N
PIN : 04.029.20.11.0001
LEGAL DESC : N/A
: LOT 0 BLOCK 0
PERMIT TYPE : FIRE PROTECTION
PROPERTY TYPE : COMMERCIAL
CONSTRUCTION TYPE : FIRE PROTECTION
VALUATION : $ 33,700.00
NOTE: PERMIT ISSUED FOR FIRE PROTECTION SYSTEM TO NEW HOLIDAY STATION. WORK SHALL COMPLY WITH APPROVED
PLAN,FIRE MARSHAL PLAN REVIEW,MN STATE CODE AND DEVICE SPECIFICATIONS.
•
APPLICANT FIRE PROTECTION BASE FEE 482.65
FIRE PROTECTION PLAN REVIEW 313.72
VIKING AUTOMATIC SPRINKLER CO STATE SURCHARGE-BUILDING 16.85
301 YORK AVE
ST. PAUL, MN 55130- TOTAL 813.22
(651)588-3300 Payment(s)
Minnesota State License#: FIPR-COOS CHECK 10045160 813.22
OWNER
HOLIDAY STATION STORES INC
4567 AMERICAN BLVD.
PO BOX 1224
MINNEAPOLIS, MN 55440-
AGREEMENT AND SWORN STATEMENT
The work for which this permit is issued shall be performed
according to: (1)the conditions of this permit;(2)the
approval plans and specifications;(3)the applicable city
approvals, Ordinances,and Codes;and,(4)the State Building
Code.This permit is for only the work described,and does
not grant permission for additional or related work which
requires separate permits.This permit will expire and become
null and void if work is not started within 180 days, or if work
is suspended or abandoned for a period of 180 days any time
after work has commenced. The applicant is responsible for
assuring all required inspections are requested in conformance
with the Minnesota State Building Code.
SEPARATE PERMITS REQUIRED FOR WORK OTHER THAN DESCRIBED ABOVE.
..., , , il,„„tik,,„„t„,,,„t
. ,
k
( 284 N.3rd Street •Bayport,MN. 55003 •Hall 1651]275-4401 •fax[651]275-4402
AY P0f4
MIN Nr SOTA
Fire Inspection Review
Date:11/11/16
.
Viking Automatic(Trinkle! ( 0.301 Nort. .s,ye St
Job: Holiday Station Store-Sprinkler Plan Review-5997 Osgood Ave.N.
Page# Item Comments Corrective action
Fire Department lock box is required
1 Lock box for all sprinklered buildings (Typically Provide FD lock box
• provided by the general contractor) 1 ,
Provide single 2 1/2" fire department
1 FDC ,, Provide single 2 1/2" FDC
connection for 3or smaller riser.
Double ; Cut sheet shows control valves above 1 Provide tamper
I ,
1 Check and below the check assembly. Just monitored control
,
Assembly want to be sure they are provided. valves if not included
with check assembly.
: Provide sprinkler
Garage If standard raise garage doors, provide .
1 ]
doors protection in the open position. coverage for garage
doors.
— ,
. ,
. , .
; 1
1
, 1
. 11/10/16
. ,
, . !
,
. ,
Prill/dij SMPY/V Me tosifiliflitiss of 4ilyport •Baytauffi *ask Pet NaltAts •Iitst LIMN!