Loading...
HomeMy WebLinkAbout2017-08-02 Sumit Fire Protection Backflow Preventer Inspection Form ,eAr Form for Inspection,Testingand Maintenance of SUMMIT Backflow Preventers Work Order: 1309913 FIRE P$QTreT,ON The work covered on this form is performed annually: Owner: Owner's Phone Number: Owner's Address: Property Being Evaluated: ALDI Property Address: 13747-60TH STREET N,OAK PARK HEIGHTS,MN 55082 Date of Work: 812/17 All responses refer to the current work(inspection,testing and maintenance)performed on this date. Location of Assembly: Back stockroom Backflow Preventer Serves: Domestic and irrigation Type of Assembly:0 RPZ 0 DCV 0 PVB Size:1-1/2" Manufacture: Wilkins Zurn Model: 975XL Serial#: 3391232 Check Valve#2 Check Valve#2 Cheek Valve#1 Relief Valve Test#1 Test#2 Pressure Back Pressure Confirmation Vacuum Breaker 0 Leaked 0 Leaked 0 Leaked Opened: 0 Y ❑N C]Closed Tight Opened: 0 Y 0 N 0 Closed Tight 0 Closed Tight Air inlet opened at: Differential pressure Differential pressure Differential pressure psi across check valve: Opened at: 2.0 psi across check valve: across check valve: 0 Leaked 9.9 psi , psi psi _ 0 Held at: psi ❑Cleaned Only 0 Cleaned Only 0 Cleaned Only 0 CIeaned Only 0 Cleaned Only Replaced: Replaced: Replaced: Replaced: Replaced: ❑Rubber Kit 0 Rubber Kit 0 Rubber Kit 0 Rubber Kit 0 Rubber Kit 1 l CV Assembly 0 CV Assembly 0 CV Assembly 0 CV Assembly 0 CV Assembly or or or or or ❑Disk 0 Disk 0 Disk 0 Disk 0 Disk ❑0-Rings ❑0-Rings ❑0-Rings ❑0-Rings ❑0-Rings ❑Seat 0 Seat 0 Seat 0 Seat 0 Seat ❑Spring ❑Spring 0 Spring 0 Spring ❑Spring 0 Stem/Guide 0 Stein/Guide 0 Stem/Guide 0 Stem i Guide 0 Stem/Guide ❑Retainer 0 Retainer 0 Retainer 0 Retainer 0 Retainer ❑Lock Nuts 0 Lock Nuts 0 Lock Nuts 0 Lock Nuts 0 Lock Nuts ❑Other: 0 Other: 0 Other: 0 Other. 0 Other: Differential pressure Differential pressure Differential pressure Air inlet: psi across check salve: Opened at: psi across check valve: across check valve: Check valve: psi psi psi psi Note:All repairs shall be completed within ten(10)days. Install Date: Rebuild Done:0 Y 0 N Rebuild Date: Coments Check#2 FAILS. NEEDS TO BE REBUILT. FAILED LAST Inspector's Information YEAR ALSO.❑ Inspector Reed Lord Company: Summit Companies I THINK THIS BACKFLOW IS IN THE WRONG SPOT. I Company Address: 575 Minnehaha Ave,St.Paul,MN 55103 THINK IT WAS MEANT TO SEPARATE THE IRRIGATION I state that the information on this form is correct at the time and place FROM THE DOMESTIC. THERE IS NOT ANYTHING DOING THAT. SERIOUS PROBLEM. of my inspection,and that all equipment tested at this time was left in operating condition upon completion of this inspection except as noted in the comment section above. Signature of Inspector. Date: 8/2117 License or Certification Number(if applicable): BT710638 State License Number - MN:C0075 / IA:FP-036 i WI:656060 Summit Fire Protection 1575 Minnehaha Avenue West-St.Paul,MN 55103 1 Phone(651)251-18801 Page 1 of 1