HomeMy WebLinkAbout2018-09-20 Stantec Plan Review - 09-20 Galloway ResponseSeptember 20, 2018 Lee Mann City Engineer 2335 Highway 36 West St. Paul, MN 55113 Re: Public Storage – Plan and Drainage Design Review Dear Lee, Please find below our re-submittal package addressing the comments received on September 20, 2018. To facilitate your review, we have included the original comments in italicized font, and have provided our responses in bold. Sheet C4.1 – Utility Plan ·The plan view still indicates PVC watermain; the City requires ductile iron pipe for watermain. Response:Labels have been changed to reflect ductile iron pipe in addition to the materials note previously addressed. ·Include Detail Plate WAT-3, GATE VALVE AND BOX INSTALLATION. Response: Detail plate added to sheet C4.2. ·The hydrants and associated valves do are not shown on the plan view per the detail plate WAT-9. The valves need to be three feet from the hydrant. Response: Valves have been moved to be 3’ from hydrant. ·All fittings need to be epoxy coated. Response: Note #15 has been added specifying this. ·All water main pipe needs to be wrapped in poly for corrosion protection. Response: Note #16 has been added specifying this. ·It would be helpful to utilize the hexagonal symbol with the ID number for the Crossing Table, to tie to the symbols on the plan view. Response: Hex symbols added to ID number on Crossing Table. Lee Mann Public Storage, 5710 Memorial Avenue North September 11, 2018 ·Locate the watermain joints as far as possible from the crossing with the sanitary service (crossing #4). Response: The note calling out the crossing has been revised to specify this. ·There is a 4” sanitary service shown on the plan that parallels Memorial Avenue from the existing manhole to the point where the 4” service connection is being made to the existing 8” PVC. Response: This line was in error and has been removed. Only the 8” main below remains. ·The pavement removed for the sanitary service connection shall be replaced in kind. Response: A note labelling this has been added to the utility plan. ·The sewer and water systems that service the property will be privately owned and maintained. Response: Note number 19 has been added to indicate this. Sheet C4.2-3 – Utility Details ·Include Detail Plate WAT-3, GATE VALVE AND BOX INSTALLATION. Response: This detail has been added. ·On sheet C4.2, Plate WAT-8 is shown twice. Response: The duplicate has been removed. ·On sheet C4.3, Plate WAT-9 is shown twice. Response: The duplicate has been removed. Stormwater Drainage Review ·Provide the City with documentation of the conditions and approval from Brown’s Creek Watershed District. Response: The erosion control permit is currently in for administrative review with Brown’s Creek per BCWD rule 3. Final notice of approval will be provided upon receipt. Per the email included with this letter, this site falls within the Kern’s Pond drainage area. No stormwater drainage permit is needed, per Lee Mann Public Storage, 5710 Memorial Avenue North September 11, 2018 BCWD rule 2, since the pond is equipped to handle the drainage area of the site. General Comments ·The City reserves the right to inspect the construction of the project. The City or its designee shall be present for water and sanitary sewer service connections to the City’s systems. Response: Noted. ·The Owner will need to comply with all requirements of the NPDES Construction Stormwater Permit and the Brown’s Creek Watershed District. The City reserves the right to require additional erosion control measures as determined/necessary during the construction of the project. Response: Noted. ·Parking, lighting, landscaping and building improvements to be reviewed by others. Response: Noted. ·The Owner shall be responsible for obtaining all required permits. Response: Noted. ·Utility construction and improvements in the right-of-way need to conform to the City’s Standard Detail Plates. The City’s details will be provided upon request. Response: Noted. Sincerely, Galloway & Company, Inc. Adam Koester Applicant AdamKoester@GallowayUS.com 1 Adam Koester From:Karen Kill <KKill@mnwcd.org> Sent:Monday, April 9, 2018 12:29 PM To:Adam Koester Cc:Jeff Weeder; Eric Johnson Subject:RE: Public Storage - Oak Park Heights, MN - Drainage Memo Adam, Thank you for contacting me regarding the proposed redevelopment activity at the Public Storage in the Kern Center in Oak Park Heights, MN. From our discussion and information you sent over last Friday, I understand that the redevelopment activity will decrease impervious area by 7,200 sq. ft. resulting in a net decrease in developed runoff from the site. I understand that all disturbance activity and impervious will be within the Kern Center Pond subwatershed (highlighted in blue below). Although a Brown’s Creek Watershed District permit will be required, I agree that the project will be subject to the Kern Center Pond agreement with the city of Oak Park Heights, which will satisfy BCWD Rule 2.0 Stormwater Management. Please let me know if you have any further questions. Best Regards, Karen Karen Kill Administrator Brown’s Creek Watershed District 455 Hayward Ave N Oakdale, MN 55128 651-330-8220 x26 (office) 651-331-8316 (cell) www.bcwd.org 2 From: Adam Koester [mailto:AdamKoester@gallowayus.com] Sent: Friday, April 06, 2018 9:18 AM To: Karen Kill Cc: Jeff Weeder Subject: Public Storage - Oak Park Heights, MN - Drainage Memo Hi Karen, Thanks for taking the time to discuss the Public Storage project with us yesterday. As we discussed, attached is our proposed grading and drainage plan and a memo discussing the proposed drainage system. As we discussed we have submitted our CUP application to Oak Park Heights and one of their comments is that we confirm that the district is in concurrence with our proposed drainage concept so we would appreciate some correspondence on this matter. Thanks for your time and efforts on this! Galloway Planning. Architecture. Engineering. ADAM KOESTER,PE, CPESC, CIVIL ENGINEERING PROJECT MANAGER, ASSOCIATE 6162 S. Willow Drive, Suite 320 Greenwood Village, CO 80111 303.770.8884 O 303.887.4104 C AdamKoester@GallowayUS.com www.GallowayUS.com Colorado | Utah | California Licensed in more than 40 states to better serve you. This message and any attachments are intended only for the recipient named. If you are not the intended recipient you are notified that any dissemination, disclosing, copying, distributing or taking any action in reliance on the contents of this information is strictly prohibited. Galloway & Company, Inc. considers any design data to be in final form only when plotted, stamped and signed. Galloway & Company, Inc. assumes no responsibility for the unauthorized use of this data. SSSSSSSSSSSSSSSSSSSSSSSSSSSSW W W MEMORIALAVENUENORTHEXISTINGBUILDING10,025SQ.FT.(ATEXTERIORFOOTPRINT)EXISTINGBUILDING16,172SQ.FT.(ATEXTERIORFOOTPRINT)EXISTINGBUILDING14,989SQ.FT.(ATEXTERIORFOOTPRINT)EXISTINGBUILDING10,000SQ.FT.(ATEXTERIORFOOTPRINT)EXISTINGBUILDING6,703SQ.FT.(ATEXTERIORFOOTPRINT)EXISTINGBUILDING11,660SQ.FT.(ATEXTERIORFOOTPRINT)EXISTINGBUILDING22,344SQ.FT.(ATEXTERIORFOOTPRINT)EXISTING BUILDING 11,192 SQ.FT. (AT EXTERIOR FOOTPRINT)WWWWSS SS SS W STMSTMSTMSS SS N30°56'15"E481.27N54°53'32"W 835.00 N35°06'28"E480.00N54°53'32"W 800.00 U T UTWWWWWWWWWUTUTUTUTUTUTUTUTUTUTUEUEUEUEUEUEUEUEUEUEUEUEUEGGGGGGGGGGGGGUTUTUTUTUTUTUTUTUTUTUTUTUTUTUTUTUTUTUTUTUTSTM STM STM STMX G G UE UE UEUE UEXXXXX X X X X X X X X X X X X X X X X X X X XUEUE UE UE UE UE U T WWWWWWWWWWWWWWWWWWWWWWWW W W W W W WW WWWWWWWWWWLOBBY PUBLIC STORAGE CANOPY =2,123 SF STORAGE BLDG FOOTPRINT =39,375 SF TOTAL BLDG FOOTPRINT =41,498 SF 3 STORIES TOTAL STORAGE BLDG =120,248 SF TOTAL BUILDING =122,371 SF FFE =943.86 8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W8''W6''W 6''W 6''W 6''W 6''W 1 1/2''WUEUEUE UE UE UE UE UE UE UE UE UE UE UE UE UE UE U E UEG G GGGGGGGGGGGG G G G G G G G G G G G G G G G G G G G G G G G UT UT UTUTUTUTUT UT UT UT UT UT UT UT UT UT UT 4''SS 4''SS 4''SS 4''SS 4''SS 4''SS 4''SS 4''SS 4''SS 4''SS 4''SS 4''SS 4''SS4''SS 4''SS 4''SS 4''SS 4''SS 4''SS 4''SS 4''SS 4''SS 4''SS 4''SS 4''SS ASSUMED LOCATION OF EXISTING WATER LINE. CONTRACTOR TO VERIFY. SIZE ASSUMED 6"CONNECT TO EXISTING WATER MAIN. CONTRACTOR TO VERIFY EXISTING LOCATION AND ELEVATION PRIOR TO CONSTRUCTION. PROPOSED WATER LINE TO CONNECT TO EXISTING STUB. CONTRACTOR TO VERIFY ELEVATION PRIOR TO CONSTRUCTION. 36.02' 6" DIP 25.74'6"DIP 26.80' 6" DIP 3.00' 8" DIP 4 0. 5 3' 8" D I P 167.74'8"PVC 16.61' 8" DIP 8.16' 8" DIP 50.03' 6" DIP 15.71' 6" DIP 11.23' 8" DIP 221.68' 8" DIP 8" 45 DEGREE BEND N=204600.83 E=494115.35 8" 45 DEGREE BEND N=204577.02 E=494120.55 8" 45 DEGREE BEND N=204416.53 E=494348.97 8" 45 DEGREE BEND N=204376.01 E=494348.97 8" 45 DEGREE BEND N=204928.27 E=494346.68 8" 45 DEGREE BEND W/ 8" X 6" REDUCER TO SE N=204930.81 E=494360.68 1.5" DOMESTIC SERVICE TAP W/ CORP STOP N=204734.65 E=494210.64 8" X 6" SWIVEL TEE W/ THRUST BLOCK & GATE VALVE W/ BOX TO THE NORTHWEST N=204727.33 E=494206.81 8" X 6" SWIVEL TEE W/ THRUST BLOCK & GATE VALVE W/ BOX TO THE NORTHWEST N=204710.54 E=494193.71 8" X 6" SWIVEL TEE W/ THRUST BLOCK & GATE VALVE W/ BOX TO THE NORTHWEST N=204914.59 E=494337.19 8" X 6" SWIVEL TEE W/ THRUST BLOCK & GATE VALVE W/ BOX TO THE NORTHWEST N=204623.76 E=494132.77 8" X 6" SWIVEL TEE W/ THRUST BLOCK & GATE VALVE TO THE SOUTHWEST N=204543.97 E=494167.58 8" GATE VALVE & BOX W/ 8"X6" REDUCER TO SE N=204280.18 E=494484.81 50.03' 1 12" TYPE K COPPER 8" GATE VALVE N=204626.23 E=494134.46 8" GATE VALVE N=204545.70 E=494165.1321.30'8"DIPCONNECT TO EXISTING GAS LINE IN ROAD.CONTRACTOR TO COORDINATE WITH UTILITY PROVIDER PRIOR TO CONSTRUCTION.FIRE HYDRANT ASSEMBLY FLANGE=943.71 N=204929.94 E=494314.96 FIRE HYDRANT ASSEMBLY FLANGE=943.61 N=204731.71 E=494163.63 FIRE HYDRANT ASSEMBLY FLANGE=942.65 N=204639.49 E=494110.17 FIRE HYDRANT ASSEMBLY FLANGE=941.15 N=204530.82 E=494158.32 ABANDONED SEPTIC SYSTEM TO BE REMOVED IF ENCOUNTERED. PROVIDE AS BID ALTERNATE. 54.48' 8" DIP 3.00' 8" DIP 3.00' 8" DIP 103.04'8"DIPEXISTING PRIVATE WELL TO BE REMOVED.SEE DEMO PLAN. 8" GATE VALVE W/ BOX N=204930.27 E=494357.73 23.92'8"DIP28.35'8"DIPPAVEMENT REMOVED FOR SANITARY CONNECTION SHALL BE R EPLACED IN KIND. LOCALIZED WATER LOWERING BENEATH SANITARY SERVICE. CONTRACTOR SHALL CENTER ONE FULL STICK OF WATER PIPE AT CROSSING CLEAR=± 2.00 N=204888.56 E=494318.77 CAUTION - NOTICE TO CONTRACTOR 1. ALL UTILITY LOCATIONS SHOWN ARE BASED ON MAPS PROVIDED BY THE APPROPRIATE UTILITY COMPANY AND FIELD SURFACE EVIDENCE AT THE TIME OF SURVEY AND IS TO BE CONSIDERED AN APPROXIMATE LOCATION ONLY. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY THE LOCATION OF ALL UTILITIES, PUBLIC OR PRIVATE, WHETHER SHOWN ON THE PLANS OR NOT, PRIOR TO CONSTRUCTION. REPORT ANY DISCREPANCIES TO THE ENGINEER PRIOR TO CONSTRUCTION. 2. WHERE A PROPOSED UTILITY CROSSES AN EXISTING UTILITY, IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY THE HORIZONTAL AND VERTICAL LOCATION OF SUCH EXISTING UTILITY, EITHER THROUGH POTHOLING OR ALTERNATIVE METHOD. REPORT INFORMATION TO THE ENGINEER PRIOR TO CONSTRUCTION. Know what's before you dig. # THESE PLANS ARE AN INSTRUMENT OF SERVICE AND ARE THE PROPERTY OF GALLOWAY, AND MAY NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. COPYRIGHTS AND INFRINGEMENTS WILL BE ENFORCED AND PROSECUTED. 6162 S. Willow Drive, Suite 320 Greenwood Village, CO 80111 303.770.8884 O www.gallowayUS.com C 2015. Galloway & Company, Inc. All Rights Reserved Date: Drawn By: Project No: Checked By:H:\PublicStorage\MN,OakParkHeights-PS000050-5710MemorialAveN\CADD\3CD\PS050_C4.1-UtilPlan.dwg-AdamKoester-2015-04-16PS0000050 07/03/2018 1 2 OWNERSHIP AND MAINTENANCE ALL STORM SEWER LINES AND APPURTENANCES, INCLUDING THE DOWNSPOUT COLLECTION SYSTEM, PROPOSED AS A PART OF THIS PLAN WILL BE PRIVATELY OWNED AND MAINTAINED BY THE PROPERTY OWNER THEREOF OR THEIR ASSIGNS. SCHEDULE INSTALL PAD &TRANSFORMER PER UTILITY PROVIDER STANDARDS 2 3 PROPOSED 6-INCH FIRE SUPPRESSION SERVICE 7 PROPOSED 1.5-INCH DOMESTIC SERVICE 8 4 EXISTING WATER MAIN TO REMAIN.SIZE TO BE VERIFIED BY CONTRACTOR 5 1 6 9 REMOVE EXISTING FIRE HYDRANT BUILDING CONNECTION FOR FIRE SUPPRESSION SERVICE WITH INTERNAL DOUBLE DETECTOR CHECK VALVE BUILDING CONNECTION DOMESTIC WATER SERVICE WITH INTERNAL REDUCED PRESSURE BACK FLOW PREVENTER INSTALL SECONDARY ELECTRICAL.2"SCH 40 PVC CONDUIT AND CONDUCTOR BY CONTRACTOR NOTE: CONTRACTOR MUST COORDINATE WORK WITH UTILITY COMPANY AND CITY PRIOR TO BEGINNING WORK AND IS RESPONSIBLE FOR ALL MATERIALS, LABOR, REPAIRS, ETC. TO COMPLETE WORK AND RESTORE AREA TO SAME STATE PRIOR TO STARTING WORK LEGAL DESCRIPTION PROPERTY DESCRIPTION PER FIRST AMERICAN TITLE INSURANCE COMPANY TITLE COMMITMENT NUMBER NCS-865695-LA2. LOTS EIGHT (8), NINE (9), AND TEN (10), BLOCK TWO (2), KERN CENTER 2ND ADDITION, WASHINGTON COUNTY, MINNESOTA. BASIS OF BEARING THE BEARINGS SHOWN ON THE SURVEY ARE BASED ON THE WASHINGTON COUNTY COORDINATES N.A.D. 1983 (1986 ADJ.), US SURVEY FEET AND THE VERTICAL DATUM IS N.A.V.D. 1988, HOLDING TO MINNESOTA DEPARTMENT OF TRANSPORTATION CONTROL POINT "8214M", CONTOURS SHOWN AT 1 FOOT INTERVALS. BENCHMARK TOP NUT OF EXISTING FIRE HYDRANT ALONG SOUTH PROPOERTY LINE. ELEVATION=944.08 SCALE: 1"=30' 0 15 30 DMP CTS UTILITY PLAN C4.1 UTILITY LINE NOTES 1.ALL WORKMANSHIP AND MATERIALS SHALL CONFORM TO THE STANDARDS AND SPECIFICATIONS FOR CITY, COUNTY, STATE AND REGULATORY AGENCIES, CURRENT EDITION. 2.THE CONTRACTOR SHALL NOTIFY THE CITY, COUNTY AND REGULATORY AGENCY 48 WORKING HOURS PRIOR TO BEGINNING CONSTRUCTION. 3.THE CONTRACTOR SHALL HAVE ONE SIGNED COPY OF THE APPROVED PLANS, ONE COPY OF THE APPROPRIATE STANDARDS AND SPECIFICATIONS AND A COPY OF ANY PERMITS AND EXTENSION AGREEMENTS NEEDED AT THE JOB SITE AT ALL TIMES. 4.DISTANCES FOR UTILITY LINES ARE THE HORIZONTAL DISTANCES BETWEEN CENTER OF FITTING/CLEANOUT TO CENTER OF FITTING/CLEANOUT. THEREFORE, DISTANCES SHOWN ON THE PLANS ARE APPROXIMATE AND COULD VARY DUE TO VERTICAL ALIGNMENT AND FITTING DIMENSIONS. 5.PROVIDE A MINIMUM OF 7.5 FEET OF COVER OVER WATER LINES. 6.CONTRACTOR TO VERIFY SIZE AND THE HORIZONTAL AND VERTICAL LOCATION OF ALL UTILITIES, WHETHER SHOWN OR NOT, PRIOR TO CONSTRUCTION. REPORT ANY CONFLICTS TO THE ENGINEER. 7.REFER TO BUILDING PLANS FOR EXACT LOCATION OF ALL UTILITY STUBS. 8.CONTRACTOR IS RESPONSIBLE FOR ALL SURFACE RESTORATION (I.E. LANDSCAPE, ASPHALT, CONCRETE, ETC.). 9.ALL TRENCH EXCAVATION SHALL BE PROPERLY SLOPED, SHORED, OR OTHERWISE SUPPORTED IN A MANNER REQUIRED BY OSHA OR AS REQUIRED BY STATE OR LOCAL LAWS. 10. MAINTAIN 2-FOOT MINIMUM VERTICAL CLEARANCE DISTANCE WHEN WATER CROSSES OVER SANITARY SEWER. 11. CONTRACTOR TO REFER TO THE JURISDICTIONS STANDARD DETAILS FOR UNDERGROUND UTILITY INSTALLATION. 12. ALL UTILITIES SHALL HAVE A MINIMUM OF EIGHTEEN INCHES (18") VERTICAL AND TEN FEET (10') HORIZONTAL SEPARATION FROM WATERMAIN. 13. ALL DISTRIBUTION WATER MAIN AND FIRE HYDRANT LATERALS SHALL BE DIP CL 52 COMPLYING WITH AWWA C151 UNLESS NOTED OTHERWISE. ALL WATER SERVICE LINES SHALL BE TYPE K COPPER. 14. SANITARY SEWER SHALL BE PVC SDR 35 COMPLYING WITH ASTM D3034. 15. ALL FITTINGS SHALL BE EPOXY COATED. 16. ALL WATER MAIN PIPES MUST BE WRAPPED IN POLY FOR CORROSION PROTECTION. 17. ROOF DRAINS TO DAYLIGHT TO CONCRETE CHANNEL. 18. CONNECTIONS TO THE CITY'S WATER AND SANITARY SEWER SYSTEMS WILL BE COORDINATED WITH AND APPROVED BY THE CITY'S REPRESENTATIVE(S). 19. ALL SANITARY SEWER AND WATER SYSTEMS THAT SERVICE THE PROPERTY WILL BE PRIVATELY OWNED AND MAINTAINED. 10 BUILDING CONNECTION FOR ELECTRICAL SERVICE 11 BUILDING CONNECTION FOR TELEPHONE AND DATA SERVICE 12 BUILDING CONNECTION FOR GAS SERVICE SEPTIC SYSTEM REMOVAL NOTES 1. THE CONTRACTOR SHALL TAKE ALL PRECAUTIONS TO PREVENT HUMAN CONTACT WITH THE CONTAMINATED MATERIALS. THESE INCLUDE THE DISTRIBUTION MEDIA, THE SURROUNDING SOIL OR SAND MATERIALS WITHIN A THREE FOOT DISTANCE OF THE SYSTEM BOTTOM, DISTRIBUTION PIPES, THE SEWAGE TANKS AND ANY CONTAMINATED SOIL AROUND LEAKY SEWAGE TANKS. CONTAMINATED MATERIAL ALSO INCLUDES ANY SOIL THAT RECEIVED SEWAGE FROM A SURFACING EFFLUENT. 2. CONTAMINATED DISTRIBUTION PIPING, MANIFOLD, GEOTEXTILE FABRIC, AND OTHER MATERIALS SHALL BE DRIED AND DISPOSED OF IN A MIXED MUNICIPAL SOLID WASTE LANDFILL; THEY SHALL NOT BE DISPOSED OF IN A DEMOLITION LANDFILL. 3. REMOVAL OF THE SEPTIC SYSTEM SHALL BE CONDUCTED BY A LICENSED MAINTAINER PER APPLICABLE STATE AND LOCAL CODES. INSTALL PRIMARY ELECTRICAL.4"SCH 40 PVC CONDUIT BY CONTRACTOR,CONDUCTOR BY UTILITY COMPANY CROSSING TABLE ID HIGH UTILITY BOTTOM OF PIPE ELEVATION LOW UTILITY TOP OF PIPE ELEVATION CLEARANCE (FEET) 1 ELECTRICAL +/- 940.70 *SANITARY 936.63 +/- 4.07 * 2 GAS +/- 940.55 *SANITARY 936.13 +/- 4.42 * 3 TELEPHONE +/- 940.60 *SANITARY 936.10 +/- 4.50 * 4 SANITARY +/- 935.61*WATER 933.61 +/-2.00 * 5 TELEPHONE +/- 940.36 *SANITARY 929.71 +/- 10.65 * 6 ELECTRICAL +/- 939.70 *SANITARY 927.69 +/- 12.01 * 7 TELEPHONE +/- 936.90 *SANITARY 926.00 +/- 10.90 * 8 TELEPHONE +/- 936.65 *SANITARY 925.88 +/- 10.77 * 9 STORM +/- 936.56 *SANITARY 925.83 +/- 10.73 * 10 GAS +/- 936.35 *SANITARY 925.80 +/- 10.55 * 11 ELECTRICAL +/- 936.31 *SANITARY 925.75 +/- 10.56 * 12 ELECTRICAL +/- 936.28 *SANITARY 925.75 +/- 10.53 * 13 TELEPHONE +/- 936.25 *SANITARY 925.73 +/- 10.52 * 2 2 2 Date Issue / Description# STAMP THESE PLANS ARE AN INSTRUMENT OF SERVICE AND ARE THE PROPERTY OF GALLOWAY, AND MAY NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. COPYRIGHTS AND INFRINGEMENTS WILL BE ENFORCED AND PROSECUTED. COPYRIGHT CLIENT LOGO 6162 S. Willow Drive, Suite 320 Greenwood Village, CO 80111 303.770.8884 Planning. Architecture. Engineering. O www.gallowayUS.com C 2015. Galloway & Company, Inc. All Rights Reserved Init. NOT FOR CONSTRUCTION Date: Drawn By: Project No: Checked By:PUBLIC STORAGECIVIL CONSTRUCTION DRAWINGS5710 MEMORIAL AVENUE NORTHOAK PARK HEIGHTS, MINNESOTACLIENT LOGO PS0000050 07/03/2018 1 8/13/18 BID ADDENDUM DP 2 9/20/18 PROPOSAL REQUEST #1 DP DMP CTS UTILITY DETAILS C4.2 2 Date Issue / Description# STAMP THESE PLANS ARE AN INSTRUMENT OF SERVICE AND ARE THE PROPERTY OF GALLOWAY, AND MAY NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. COPYRIGHTS AND INFRINGEMENTS WILL BE ENFORCED AND PROSECUTED. COPYRIGHT CLIENT LOGO 6162 S. Willow Drive, Suite 320 Greenwood Village, CO 80111 303.770.8884 Planning. Architecture. Engineering. O www.gallowayUS.com C 2015. Galloway & Company, Inc. All Rights Reserved Init. NOT FOR CONSTRUCTION Date: Drawn By: Project No: Checked By:PUBLIC STORAGECIVIL CONSTRUCTION DRAWINGS5710 MEMORIAL AVENUE NORTHOAK PARK HEIGHTS, MINNESOTACLIENT LOGO PS0000050 07/03/2018 1 8/13/18 BID ADDENDUM DP 2 9/20/18 PROPOSAL REQUEST #1 DP DMP CTS UTILITY DETAILS C4.3 2 Julie Hultman From: Adam Koester <AdamKoester@gallowayus.com> Sent: Thursday, September 20, 2018 5:40 PM To: Mann, Lee; Eric Johnson Cc: Andrew Kegley; Scott Richards (Scott@PlanningCo.com);Julie Hultman; Lisa Danielson; 'Kevin Sandstrom';Jeff Weeder; Zell Cantrell; David Ploense Subject: RE: Public Storage Plan Review - Revised Attachments: PS0050_3rd Submittal.pdf Follow Up Flag: Flag for follow up Flag Status: Flagged Lee, thank you for your timeliness on providing these comments. This was greatly appreciated. Please see the revised sheets with remaining comments along with our response. Please note that the Erosion Control Permit is being processed by Brown's Creek at this time and that no stormwater drainage permit is needed. We have attached correspondence to this effect in the response letter. Thanks! Galloway Adam Koester, PE, CPESC CIVIL ENGINEERING PROJECT MANAGER ASSOCIATE 6162 S.Willow Drive, Suite 320 Greenwood Village, CO 80111 0 303.770.8884 AdamKoester alloway_US_com GallowayUS.com COLORADO I CALIFORNIA I UTAH Nationally Recognized. Locally Preferred. From: Mann, Lee<Lee.Mann@stantec.com> Sent:Thursday, September 20, 2018 2:50 PM To: Eric Johnson (eajohnson@cityofoakparkheights.com)<eajohnson@cityofoakparkheights.com> Cc: Andrew Kegley<akegley@cityofoakparkheights.com>; Scott Richards (Scott@PlanningCo.com) <Scott@PlanningCo.com>; 'jhultman@cityofoakparkheights.com' <jhultman@cityofoakparkheights.com>; Lisa Danielson <LDanielson@cityofoakparkheights.com>; 'Kevin Sandstrom' <ksandstrom@eckberglammers.com>; Adam Koester <AdamKoester@GallowayUS.com>;Jeff Weeder<JeffWeeder@GallowayUS.com> Subject: RE: Public Storage Plan Review- Revised Hi Eric. Attached is a revised letter with one additional comment regarding ownership of utilities under the Utility Plan comments. Please disregard the previous letter. Let me know if you have any questions. 1 MN,WI, CA Principal Direct: 651 604-4850 Mobile: 651 775-5956 Lee.Mann@stantec.com Stantec 2335 Highway 36 West St. Paul MN 55113-3819 US 31? Stantec The content of this email is the confidential property of Stantec and should not be copied,modified retransmitted,or used for any purpose except with Stantec's written authorization.If you are not the intended recipient,please delete all copies and notify us immediately. From: Mann, Lee Sent:Thursday, September 20, 2018 2:21 PM To: Eric Johnson (>alohnson@ cityofoakparkheights.com) <ea'ohnson'Dcit ofoak•arkhei hts.com> Cc:Andrew Kegley<akegley@cityofoakparkheights.com>; Scott Richards (Scott _ Plannin_Co.com) <Scott(/PlanningCo.com>; 'jhultman@cityofoakparkheights.com' <jhultrnan@cityofoakparkheights.com>; Lisa Danielson <LDanielson@cityofoakparkheights.corn>; 'Kevin Sandstrom' <ksandstrom@eckberglammers.com>; Adam Koester <AdamKoester@gallowayus.com>;Jeff Weeder<JeffWeeder@gallowayus.com> Subject: Public Storage Plan Review Hi Eric, Attached is our review of the plans for Public Storage that were submitted to us 9/19/2018. Let me know if you have any questions. EE,E, ; .$ fn, PE MN, WI, CA Principal Direct: 651 604-4850 Mobile: 651 775-5956 Lee.Mann@stantec.com Stantec 2335 Highway 36 West St. Paul MN 55113-3819 US Stantec The content of this email is the confidential property of Stantec and should not be copiedmodified,retransmitted or used for any purpose except with Stantec's written authorization.If you are not the intended recipient,please delete all copies and notify us immediately. 2