WET AGENT FIRE SUPPRESSION SYSTEM INSPECTION AND TESTING REPORT
Work Site#: 7351 Service Ticket#:ST00112229
Name of Facility: PHIL'S TARA HIDEAWAY Installation/ServtcrReport Date:02/11/2019
Street Address: 15021 60TH ST.NORTH Time In: 09:36am Time Out: 01:30pm
Last Maintenance Date: 2019-01-11
City:OAK PARK HEIGHTS State: MN Zip:55082 Last Maintained By:ML
Auth.Contact: BARBATSIS/NICK,PHIL Phone: 6514399850 System 1 of I System location:Back kitchen
Suppression System Type Panel Type(electrical only)
Manufacturer:Kidde Model:WHDR Kidde Manufacturer: Serial#: Rev#:
Type of Agent:Wet Agent Serial#:TBC036143 Model:
Water flow connection: Waterline union above system tank: Lockable valve accessible?
Water flow pressure_PSI Tamper Switch Functions:Gas shutdown_Electrical appliance shutdown_Alarm_Forced exhaust_Makeup air Other_
CONTROL/RELEASE DATA
Last
Mfg Internal #of Actuator Damage/
Manufacturer Mech/Elec Model Year Test Actuators Location Model Corrosion
EXPELLANT GAS LINE
Distance
Leak Damage/ within Inspected/
Expellant Line Material Test Hose Dates Corrosion Limit Cartridge Type Date Weight Replaced
Copper Pass 2018 No Pass Nitrogen 6/2028 237.5 Inspected
TANK/CYLINDER DATA
Pressure
Gauge in
Proper
last Range
Mfg Internal Cylinder Valve #of #of Coverage Damage/
Manufacturer Model Date Test Full Model Manifold?Nozzles IPI Flows Area Corrosion Serial#
Kidde WHDR-400S 5/2006 5/2018 Pass No 9 9 Entire Hazard No
NOZZLES
Plenum Duct Range Griddle Fryer Broiler Up.Broiler_ Chain Broiler_
Salamander Wok Tilt Skillet Kettle Pizza Oven Other
DETECTION DATA
Mechanical/ Temp of Type of Links/Tubing
Electric/Pneumatic #of Detectors Detector Detector #Replaced Operates Release Detector Housing Model Damage/Corrosion
Mechanical 3 500 Link No Pass Series No
1
11"
4 ar ni
cF. I . . 1 P iM E c. -mr-
www.nardinifire.com / sales @ nardinifire.com
REMOTE RELEASE DATA
Mechanical/ Height from Floor Distance from Hood Damage/
Electric/Pneumatic Manufacturer Operable? (Inches) At Pt. of Egress (Feet) Corrosion
GAS VALVE DATA
Manual
Mechanical/ Size Reset Damage/
Electric/Pneumatic Manufacturer (Inches) Location Relay Operable If no, why? Corrosion
Mechanical Kidde 1 Back to fryer No Yes No
ELECTRICAL FUNCTIONS
Micro/ Switch Breaker/ Damage/
Function Pressure Operates Relay Breaker/Relay Location Corrosion
NOTIFICATION/ANNUNCIATION
Dials
Out or Signals Building Monitor Co. System
Alarmed Local Received Fire Panel Location Monitoring Company Phone# Account#and password Normal
System/Hazard Inspection Yes/No/NA Comments
1. Blow off caps replaced/Nozzle seals? No
2. Filters installed and in good condition? Yes
3. System installed utilizing good construction practices? Yes
4. Hood penetrations sealed with UL listed device? No
5. Hazard changes? No
6. System installed per manufacturer specifications? Yes
7. System complies with all local codes and standards? Yes
8. System meets UL300 listing? Yes
9. System red tagged? No
10. Proper hand portable extinguisher near hood & serviced? Yes
Comments:
The report reflects the system is compliant upon completion of replacing detection line components
Lead Hernandez, G
2nd
Nardini Fire Technician Customer/Authorized Agent —Printed Name Customer/Authorized Agent - Signature