Loading...
HomeMy WebLinkAbout2019 ECSI Fire Alarm Inspection Report )* ECSI- Fire Alarm Inspection and Testing I Form System Integrators Start Date 4/22/2019 Completion Date 4/22/19 Doc: INSP-A 1. Property information: Name of Property: City of oak Park Heights Address: 14168 Oak Park Blvd. North P.O. Box 2007 Oak Pak Heights,MN 55082 Description of Property: office Building �OccupancyType: office Name of Property Representative: JENNIFER PINSKI i Address: SAME Phone: 651-439-4439 Fax: E-mail: Authority having Jurisdiction over this Property: oak Park Hts Phone: Fax: E-mail: 2. Installation, Service and Testing Contractor Information: Electronic Communication Systems, LLC 2300 Territorial Road St. Paul,MN,55114 Inspection Frequency 1 Phone: (651)-735-7470 Fax: (651)735-7471 Inspector Name KEVIN CHAPEAU Qualification JT,PLT An Inspection Contract is in effect as of Contract Expires 3. Type of System or Service: ❑X Fire ❑ EVACS ❑ MNS ❑ Other ❑ UL ❑X NFPA NFPA Edition: ❑ Cert. of Completion ❑ UL Initial Cert Interval of this Inspection: X❑ Annual ❑ Quarterly 0 ❑ Semi Annual Monitoring Data: Monitoring Type: ❑X NFPA ❑ UL A Monitoring Contract is in Effect as of Monitoring Contract Expiration Date Monitoring Contractor Name SECURTAS 008447220 Central Station# 1-800-548-4478 Receiver Ph. Line# 1-800-643-9216/1-330-498-2163 System Ph Line 1 651-430-1767 System Ph Line 2 651-689-0154 Dialer manufacturer Notifier Model#: NFS2-100 Dialer Location L.L.Systems Room Breaker Location Electrical Rm Number of Zones >Lcl(DA CT Batt Type Sealed Lead Software Rev. Date 3.1 Prior To Testing Notifications: 0 Central station 0 Building ❑ AHJ 3. Type of System or Service(continued) 3.2 Control Unit 1 X❑ Standard ❑ Audio Evac Manufacturer Notifier Model# �NFS2 100 Software Rev 3.1 Manufacture Date Zones or Data Loops 1 SLC Audible Circuits 4 Printer Interface Serial Printer Type. NA Other NA iOther NA 3.3 Control Unit 2 ❑ Standard ❑ Audio Evac Manufacturer NA Model# NA Software Rev NA Software Rev Date NA Zones or Data Loops NA Audible Circuits NA Printer Interface NA Printer Type. NA Other NA Other NA 3.4 System Documentation ❑ UL Cert. PostedX❑ Drawings on site ❑ All Labels Placed ❑X System Up-loaded ❑X Manual on site 4. System Power 4.1 Controls Control#1 LL Systems Primary Pwr 12OVAC Breaker E1ec Rm Location Room LOC t ntrol#2 na Primary Pwr na Breaker na cation Loc 4.2 Engine Driven Generator ❑X This System does not have a generator I I Manufacturer:NA Location: NA Fuel Type: NA Fuel Location:NA 4.3 Uninterruptible Power Supply ❑X This System does not have a UPS Equipment powered by UPS: NA i Location of UPS: NA Calculated Capacity of UPS:NA Standby Mode(hrs): NA Alarm Mode (min):NA 4. System Power(continued) 4.4 Batteries(Control 1) Location FACP Type Acalded Lean Voltage 2/12VDC Amp/Hr 7.5 Calc. Capacity in Standby(hrs) 24 Calc. Capacity in Alarm Mode (min) 5 ❑ Batteries are marked with Date of manufacture 4.5 Batteries (Control 2) Location NA Type NA Voltage NA � Amp/Hr NA Calc. Capacity in Standby (hrs) NA Calc. Capacity in Alarm Mode (min) NA ❑ Batteries are marked with Date of manufacture 4.6 Remote Power Supplies Location 1 Location 2 Location 3 Location 4 Location 5 Location 6 NA NA NA NA NA NA Batt Amp/Hr Batt Amp/Hr Batt Amp/Hr Batt Amp/Hr Batt Amp/Hr Batt Amp/Hr NA NA NA NA NA NA Location AC Location AC Location AC Location AC Location AC Location AC NA NA NA NA NA NA 5. Annunciators Location Location Location Location Main Entrance NA NA NA ❑ This System Does Not have annunciators 6. Notifications Made Prior to Testing Contact Time Other note Central Station SECURTAS 8:00:00 AM Building management JENNIFER 8:00:00 AM Building Occupants All 8:00:00 AM Authority having Jurisdiction NA Other, If Required NA 7. Data Updates ❑ System Data on this Form did not require updating at the time of this inspection System Data had changed and required updating ❑ Devices or Components Added ❑ Control Changes or Replaced ❑ Devices or Components Removed ❑ Device Changes ❑ See Separate Form for Changes Reason For Changes 7.1 Device Counts: Fire Alarm Initiating Devices and Circuit Style Quantity Of MFG Model Circuit Style Other: Manual Pull Stat. 1 Notifier NBGI2LX-100 SLC-4 Ion Detectors NA Photo Detectors 5 Notifier Acclimate SLC-4 Duct Detectors Some Are Smoke Det 23 Notifier FSP-851R SLC-4 programmed as Duct Det. Heat Detectors NA Beam Detectors NA Supervisory Switches NA Other: Other: Alarm Indicating Devices: Quantity Of MFG Model Circuit Style Other: Bell NA Horns NA Horn/Strobes 22 Wheelock HSR Y Strobes 12 Wheelock STR Y Speakers NA Speaker/Strobes NA Chimes NA Other: Building Control Interface Quantity Of MFG Model Circuit Style Other: Air Handlers 1 Notifier FRM-1 SLC4 Dampers 22 Notifier FRM-1 SLC4 Elevator Recall 2 Notifier FRM-1 SLC4 Time Out Rooms NA NA NA NA NA Supervisory Devices and systems Quantity MFG Model Circuit Style Other: Fire Pump Pwr NA Fire Pump Running NA Fire Pump Auto Pos NA Fire Pump/Controller Trbl NA Generator in Auto Pos NA Generator/Controller Trouble NA Switch Transfer NA Generator Transfer NA Flow Switch 2 Notifier FMM-1 (100) SLC4 Tamper Switch 2 Notifier FMM-1 (100) SLC4 Post Indicator Valve NA Pressure Switches NA Other Other Other Code: Code: Code: Bldg. Interfaces Quantity MFG Model Circuit Style Other: Door mags NA Door Holders NA Fire Curtains NA Kitchen Hoods NA Pre-Action systems NA Gas/CO Detection NA Bldg.Temp NA Freezer/Cooler NA Boiler NA Agent Release System 1 Notifier FMM-1 (100) SLC4 NA 8. Testing Results 8.1 Control Unit and Related Equipment Description Visual Functional pass Fail N/A Comments Ins ection Test Control Unit ❑X ❑X ❑X I ❑ Lamps,LED's,LCD's ❑X ❑X ❑X ❑ Fuses 0 ❑ Trouble Signals X ❑ Disconnect Switches X ❑X ❑ Ground Fault Monitor 0 0 ❑X ❑ Supervision X ❑X X ❑ Local Annunciators x ❑X 0 ❑ ❑ Remote Annunciators X X X ❑ ❑ Remote Pwr. Supplies X X ❑X ❑ ❑ Isolation Modules ❑ ❑ ❑ ❑ ❑X Other(Specify) ❑ ❑ ❑ ❑ 0 8.2 Control Unit Power Supplies Description Visual Functional pass Fail N/A Comments Inspection Test 120 volt Power ❑X ❑X ❑X ❑ Generator or UPS ❑ ❑ ❑ ❑ ❑X Battery Condition a ❑X ❑X ❑ ❑ Load Voltage 0 ❑X ❑X ❑ ❑ Discharge Test ❑X 0 ❑X ❑ ❑ Charger Test X X FXK ❑ ❑ Other(Specify) ❑ ❑ ❑ ❑ ❑ 8.3 In Building Fire Emergency Voice Alarm Communication Equipment Description Visual Functional pass Fail N/A Comments Inspection Test Control Unit ❑ ❑ ❑ ❑ Ina Lamps,Leds,LCD's ❑ ❑ ❑ ❑ Fuses ❑ ❑ ❑ ❑ Primary Power Supply ❑ ❑ ❑ ❑ ❑X Secondary Power Supply ❑ ❑ ❑ R Trouble Signals ❑ ❑ ❑ ❑ FRI Disconnect Switches ❑ ❑ ❑ ❑ 0 Ground Fault Monitor ❑ ❑ ❑ ❑ Panel Supervision ❑ ❑ ❑ ❑ x 8.3 Evac Continued Sound Pressure Levels ❑ Visual ❑ Functional Occupied ❑ Yes ❑ No Ambient dBA Ina Alarm dBA Ina ❑ Passed ❑ Failed 8.4 Notification Appliance Power Extender Panels Description Visual Functional Pass Fail N/A Comments Inspection Test Lamps, LCDs, LEDsX❑ ❑X ❑X ❑ ❑ Fuses X X ❑ ❑ Primary Power supply X X ❑ ❑ Secondary Power supply 0 0 ❑ ❑ Trouble Signals a X ❑ ❑ Ground Fault Monitoring X X FRI ❑ ❑ Panel Supervision X ❑X X ❑ ❑ Other(Specify) ❑ ❑ ❑ ❑ X 8.5 Mass Notification Equipment ❑X This Section Does Not Apply to this System or Facility. Description Visual Functional pass Fail N/A Comments Inspection Test Functional Test ❑ ❑ ❑ ❑ ❑X Reset/Power down test ❑ ❑ ❑ ❑ ❑X Fuses ❑ ❑ ❑ ❑ ❑X Primary Power Supply ❑ ❑ ❑ ❑ ❑X UPS Power Test ❑ ❑ ❑ ❑ X Trouble Signals ❑ ❑ ❑ ❑ X Disconnect Switches ❑ ❑ ❑ ❑ FRI Ground Fault Monitoring ❑ ❑ ❑ ❑ 0 CCU Security Mechanism ❑ ❑ ❑ ❑ 0 Prerecorded message content ❑ ❑ ❑ ❑ ❑X Recorded message activation ❑ ❑ ❑ ❑ ❑X Software backup Performed ❑ ❑ ❑ ❑ X Test backup software ❑ ❑ ❑ ❑ 0 ❑ ❑ ❑ ❑ ❑X ❑ ❑ ❑ ❑ X ❑ ❑ ❑ ❑ ❑X ❑ ❑ ❑ ❑ ❑X Other: ❑ 0 ❑ ❑ X . 0 Testing Results continued 8 9 (continued) 8.5 Mass Notification Equipment(continued) X This Section Does Not Apply to this System or Facility. Sound Pressure Levels ❑ Visual ❑ Functional Occupied ❑ Yes ❑ No Ambient dBA na Alarm dBA Ina System Intelligibility ❑ Visual ❑ Functional ❑ CSI ❑ STI 8.6 Two-Way Communication Equipment ❑ This Section Does Not Apply to this System or Facility. Description Visual Functional Pass Fail N/A Comments Ins ection Test Phone Handsets ❑ ❑ ❑ ❑ N Phone Jacks ❑ ❑ ❑ ❑ 0 Off Hook Indicator ❑ ❑ ❑ ❑ 0 Call in Signal ❑ ❑ ❑ ❑ 0 System Performance ❑ ❑ ❑ ❑ 0 System Audibility ❑ ❑ ❑ ❑ 0 System Intelligibility ❑ ❑ ❑ ❑ X Radio Communications ❑ ❑ ❑ ❑ X Area of Refuge comm.system ❑ ❑ ❑ ❑ X Elev. Emergency Comm. System ❑ ❑ ❑ ❑ FRI Other(specify) ❑ ❑ ❑ ❑ 0 8.7 Combination Systems ❑X This Section Does Not Apply to this System or Facility. Description Visual Functional Pass Fail N/A Comments Ins ection Test Fire Extinguishing Monitoring El El 1:1 1:1Devices/system Phone Jacks ❑ ❑ ❑ ❑ X Off Hook Indicator ❑ ❑ ❑ ❑ X Call in Signal ❑ ❑ I ❑ 1 ❑ ❑X 8.0 Testing Results (continued) 8.8 Special Hazards Description Visual Functional pass Fail N/A Comments Inspection Test NA ❑ ❑ ❑ ❑ NA ❑ ❑ ❑ ❑ NA ❑ ❑ ❑ ❑ NA ❑ ❑ ❑ ❑ 8.9 Emergency Communication System ❑ Visual ❑ Simulated Operation ❑ Functional ❑ Ensure predischarge notification appliances of special hazard systems are not overridden by the MINIS. 8.10 Monitored Systems Description Visual Functional pass Fail N/A Comments Inspection Test Engine Driven Generator ❑ ❑ ❑ ❑ ❑X Fire Pump ❑ ❑ ❑ ❑ ❑X Special suppression systems ❑X ❑ ❑ ❑ ❑ Tested By Others Other El L1 El ❑ F-1Flow Sw: Quant:2 ❑X ❑ ❑ Tamper: Quant:2 X❑ ❑X ❑ ❑ Test Type: Flow ❑ Electronic ❑X ❑ ❑ ❑ Srinkler Test by: I Date: 8.11 Auxiliary Functions Description Visual Functional pass Fail N/A Comments Inspection Test Door Releasing Devices ❑ ❑ ❑ ❑ XX Fan Shutdown XX X XX ❑ ❑ Smoke management control ❑ ❑ ❑ ❑ ❑X Smoke Damper Operation ❑X ❑X ❑X ❑ ❑ Smoke Shutter Release ❑ ❑ ❑ ❑ R Door Unlocking ❑ ❑ ❑ ❑ R Elevator Recall ❑X ❑ ❑ ❑ ❑ No key for reset Elevator Shunt Trip ❑ ❑ ❑ ❑ ❑X MINIS override of FA signals ❑ ❑ ❑ ❑ 0 Other ❑ ❑ ❑ ❑ ❑X Other ❑ ❑ ❑ ❑ ❑X Other ❑ ❑ ❑ ❑ R ON ❑ ❑ ❑ ❑ 8.12 Alarm Initiating Device ❑X Device test results sheets attached listing all devices counted, tested and results 8.13 Supervisory Alarm Initiating Device a Device test results sheet attached listing all devices counted,tested and results 8.14 Alarm notification Appliances 0 Appliance test results sheet attached listing all appliances counted, tested and results 8.0 Testing Results (continued) 8.15 Supervisory Station Monitoring Description Visual Functional Time Signal Time Signal Comments Inspection Test Sent received Alarm Signal ❑X ❑X 8:30 AM 8:30 AM Alarm Restoration x ❑X 8:34 AM 18:34 AM Trouble Signal 0 0 8:35 AM 18:35 AM Trouble Restoration X X 12:46 PM 12:46 PM Supervisory Signal 0 X 9:27 AM 9:27 AM Supervisory Restoration X 0 9:28 AM 9:28 AM 9.0 Notification that Testing is Complete Monitoring Org. Building Mngt. Building Occupants AHJ Other Name: SECURTAS JENNIFER PINSKI All Time: 2:00 PM 2:00 PM 2:00 PM 10. System Restored to Normal Operation Date 4/22/19 Time 2:00 PM 11. System Operational or Repair Deficiencies. ❑X No Deficiencies were noted at the time of this inspection ❑ Deficiencies were noted at the time of this inspection. (See included deficiency report) ❑ Deficiencies noted were not corrected at the time of inspection ❑ Deficiencies noted were corrected at the time of Inspection ❑ Repairs Denied by customer ❑ **SYSTEM RED TAGGED. (System out of Service) IMMEDIATE ACTION REQUIRED. Repairs Corrected on: 12. Certification 12.1 Inspector Certification Inspector Name KEVIN CHAPEAU [Date, 4/22/19 12.2 Owner or Rep. Acceptance Signature Printed Name Organization Date ECSI-Facility Fire Alarm Device Location And Test Log Address Location Type Visual Funct. Pass Fail Comments 2019 OAK PARK HIGHTS CITY HALL Test 1 D001 IEVIDENCE ROOM 19 Su .L DUCTP X X X 1 D002 IEV15ENCE ROOM 19 Su .L DUCTP X ix X 1 D003 IEVIDENCE ROOM 19 Su .L DUCTP X ix X L1 D004 IEVIDENCE ROOM 19 Su .L DUCTP X ix X L1 D005 JUEVEL HALL/EVIDENCE Su .L DUCTP X IX X LlDO06 L.LEVEL MENS ROOM Su .L DUCTP X Ix X L1 D007 VOTING STORAGE ROOM Su .L DUCTP X ix X L1 D008 VOTING STORAGE ROOM Su .L DUCTP X ix X L1 D009 VOTING STORAGE ROOM Su .L DUCTP X ix X L1D010 L.LEVEL HALL ARCHIVE Su .L DUCTP X ix X L1 D012 IL.LEVEL HALL ARCHIVE Su .L DUCTP X Ix X L1 D013 L.LEVEL MECH/ELEC Su .L DUCTP X ix X Ll D014 EVIDENCE/BY GARAGE Su .L DUCTP X Ix X L1 D015 EVIDENCE RM 19 Su .L DUCTP X X X L1 DO16 AT FACP SMOKE PHOTO X X X L1D018 PUBLIC WORKS SMOKE PHOTO X X X LlD025 COUNCEL CHAMBERS Su .L DUCTP X X X L1 D026 COUNCEL CHAMBERS Su .L DUCTP X X X L1 D027 CONF.BY ROTUNDA Su .L DUCTP X ix X Ll D030 ELEV LOBBY L.LEVEL SMOKE PHOTO X IX X L1 D031 ELEV LOBBY 1 ST FL SMOKE PHOTO X IX X L1 D032 ELEV EQUIP ROOM SMOKE PHOTO X IX X L1D037 L.LEVEL MECH/ELEC Su .L DUCTP X Ix X LlD042 ABOVE FINANCE Su .L DUCTP X ix X L1 D043 ABOVE FINANCE Su .L DUCTP X IX X L1 D044 P.D.FILE ROOM Su .L DUCTP X ix ix LlD045 P.D.FILE ROOM Su .L DUCTP X ix X L1 D046 ABOVE WORK ROOM Su .L DUCTP L1 M001 DAMPER EVIDENCE ROOM 19 RELAY X X X L1 M002 DAMPER EVIDENCE ROOM 19 RELAY X X X L1 M003 DAMPER EVIDENCE ROOM 19 RELAY X X X L1 M004 DAMPER EVIDENCE ROOM 19 RELAY X X X L1 M005 L.LEVEL HALL/EVIDENCE RELAY X ix X L1 M006 L.LEVEL MENS ROOM RELAY X X X LIMONNOTING STORAGE ROOM RELAY X X X L1 M008 VOTING STORAGE ROOM RELAY X X X L1 M010 L.LEVEL HALL ARCHIVE RELAY X X X L1 M012 L.LEVEL HALL ARCHIVE RELAY X X X L1 M013 L.LEVEL MECH/ELEC RELAY X Ix X L1 M014 EVIDENCE BY GARAGE RELAY X ix X L1 M015 EVIDENCE BY ROOM 19 RELAY X Ix X L1 MO16 AT FACP L.LEVEL PULL STATION X IX IX L1 M025 COUNCEL CHAMBERS RELAY X X X L1 M026 COUNCEL CHAMBERS RELAY X X X L1 M027 CONF.BY ROTUNDA RELAY X X X L1 M029 SERVER RM SUPPRESION SYSTEM CONV SMOKE X X X L1M030 PRIMARY ELEV. RECALL RELAY X X X L1 M031 ISECONDARY ELEV. RECALL RELAY X ix X L1 M032 MECH RM. SMOKE RELAY X X X L1 M033 CITY HALL TAMPER TRACK SUPERV X X X L1 M034 CITY HALL WATER FLOW FLOW X X X Ll M035 PUBLIC WPRKS TAMPER ITRACK SUPERV X X X 1-1 M036 PUBLIC WORKS WATER FLOW FLOW X X X L1 M037 L.LEVEL MECH/ELEC RELAY X X X L1 M038 L.LEVEL MECH/ELEC RELAY X X X L1 M039 AHU 1 RETURN DUCT Su .L DUCTP X X X i ECSI-Facility Fire Alarm Device Location And Test Log Address Location Type Visual Funct. Pass Fail I Comments 2019 OAK PARK NIGHTS CITY HALL Test L1 M040 AHU 1 SUPPLY DUCT Su .L DUCTP X X X L1 M041 ILIEVEL MECH/ELEC RELAY X ix X L1 M042 ABOVE FURNACE RELAY X Ix X L1 M043 ABOVE FURNACE RELAY X ix X L1 M044 ABOVE POLICE RECEPTION RELAY X Ix X L1 M045 ABOVE POLICE RECEPTION RELAY X X X L1 M046 ABOVE WORK ROOM RELAY X X X