HomeMy WebLinkAbout2019-12-13 Nardini Fire Wet Agent FSS Inspection & Testing Report ra
j Nardini
www.nardinifire.com/ sales@nardinifire.com st.Paul.MN
WET AGENT FIRE SUPPRESSION SYSTEM INSPECTION AND TESTING REPORT
Work Site#: 7351 Service Ticket#: ST00127064
Name of Facility: PHIL'S TARA HIDEAWAY Installation/Service Report Date: I2/I 3/2019
Street Address: 15021 60TH ST.NORTH Time In: 07:59am Time Out: 08:56am
Last Maintenance Date: 2019-01-11
City: OAK PARK HEIGHTS State: MN Zip: 55082 Last Maintained By: GH
Auth.Contact: BARBATSIS/NICK,PHIL Phone: 6514399850 System 1 of I System location: Kitchen Hood
Suppression System Type Panel Type(electrical only)
Manufacturer:Kidde Model:WHDR Kidde Manufacturer: Serial#: Ret i
Type of Agent:Wet Agent Serial#: Model:
Water flow connection: Waterline union above system tank: Lockable valve accessible?
Water flow pressure PSI Tamper Switch Functions:Gas shutdown Electrical appliance shutdown_Alarm Forced exhaust_Makeup air Other_
CONTROL/RELEASE DATA
Last
Mfg Internal #of Actuator Damage/
Manufacturer Mech/Elec Model Year Test Actuators Location Model Corrosion
Kidde Mechanical XV 2015 2018 I Tank SVA No
EXPELLANT GAS LINE
Distance
Leak Damage/ within Inspected/
Expellant Line Material Test Hose Dates Corrosion Limit Cartridge Type Date Weight Replaced
S.S.Hose Pass No Pass Nitrogen 6/2018 237.5 Grams Inspected
TANK/CYLINDER DATA
Pressure
Gauge in
Proper
Last Range/
Mfg Internal Cylinder Valve #of #of Coverage Damage/
Manufacturer Model Date Test Full Model Manifold?Nozzles IPI Flows Area Corrosion Serial#
Kidde WHDR-4005 5/2006 5/2018 Pass No 9 Pass 11 Entire Hazard No
NOZZLES
Plenum I Duct I Range 3 Griddle I Fryer 2 Broiler I Up.Broiler I Chain Broiler
Salamander Wok Tilt Skillet Kettle Pizza Oven Other
DETECTION DATA
Mechanical/ Temp of Type of Links/Tubing
Electric/Pneumatic #of Detectors Detector Detector #Replaced Operates Release Detector Housing Model Damage/Corrosion
Mechanical I 360 Link I Pass Other No
Mechanical 2 500 Link 2 Pass Other No
1
11.071 Nardini
www.nardinifire.com/ sales@nardinifire.com
REMOTE RELEASE DATA
Mechanical/ Height from Floor Distance from Hood Damage/
Electric/Pneumatic Manufacturer Operable? (Inches) At Pt.of Egress (Feet) Corrosion
Mechanical Kidde Pass 57 Pass 10 No
GAS VALVE DATA
Manual
Mechanical/ Size Reset Damage/
Electric/Pneumatic Manufacturer (Inches) Location Relay Operable If no.why? Corrosion
Mechanical Kidde I Back of fryer No Yes No
ELECTRICAL FUNCTIONS
Micro/ Switch Breaker/ Damage/
Function Pressure Operates Relay Breaker/Relay Location Corrosion
NOTIFICATION/ANNUNCIATION
Dials
Out or Signals Building Monitor Co. System
Alarmed Local Received Fire Panel Location Monitoring Company Phone# Account#and password NormaI
No
System/Hazard Inspection Yes/No/NA Comments
I, Blow off caps replaced/Nozzle seals? No
2. Filters installed and in good condition? Yes
3. System installed utilizing good construction practices? Yes
4. Hood penetrations sealed with UL listed device? Yes
5. Hazard changes? No
6. System installed per manufacturer specifications? No Ranges as griddle protection do not meet mfg specs.
7. System complies with all local codes and standards? Yes
S. System meets UL300 listing? Yes
9. System red tagged? Yes
10. Proper hand portable extinguisher near hood&serviced? Yes
Comments:
Pipe nozzles for ranges and griddle low proximity to meet manufacturer requirements for system.
Lead Asa Engstrum
2nd N/A
Nardini Fire Technician Customer/Authorized Agent—Printed Name Customer/Authorized Agent-Signature
2