HomeMy WebLinkAbout2020-02-17 Fire Alarm Inspection & Testing Report Nardini
FIRE EQUIPMENT
www.nardinifire.com/sales@nardinifire.com St.Paul,MN
FIRE ALARM INSPECTION AND TESTING
Service Order Number: ST00148807 Work Site#: 39053
Date In: 2020-02-17 Time In: 11:00am I Date Out: 2020-02-17 Time Out: 03:OOpm
1. PROPERTY INFORMATION
Name of property: AMERICINN BY WYNDHAM
Address: 13025 60TH STREET N OAK PARK HEIGHTS,MN 55082
Description of property: Hotel
Name of property representative: PATEL,ROSHNI
Address: 13025 60TH STREET N OAK PARK HEIGHTS,MN 55082
Phone: 651-275-0980 Fax: E-mail:
2. TESTING AND MONITORING INFORMATION
Testing organization: Nardini Fire Equipment
Address: 405 Cty Rd E west St Paul MN 55126
Phone: 651-483-6631 Fax: E-mail: sales@nardinifire.com
Monitoring organization:
Address:
Phone: Fax: E-mail:
Means of transmission: POTS
Account number: Phone line 1/IP address: 651-275-4027 Phone line 2/IP address: 651-275-1230
Entity to which alarms are retransmitted: Phone:
3. DOCUMENTATION
On-site location of the required record documents and site-specific software:
4. DESCRIPTION OF SYSTEM OR SERVICE
4.1 Control Unit
Manufacturer: FCI Model number: 7100-2D
4.1.1 Circuit Styles: SLC
4.1.2 Number of Circuits: 1
4.1.3 Panel Locations: Front entry
Firmware revision number:
4.1.4 Was Firmware Updated? Yes No
Comments:
Does Alarm Panel Have Most Updated Firmware? Yes No
Comments:
43.1 Primary(Main)Power
Nominal voltage: 120VAC Amps: Location:
Overcurrent protection type: Circuit breaker Amps: 20 Disconnecting means location: PP11 ckt#43
4.3.2 Secondary Power
Type: 2 12v5ah 09/2019 Location: FACP
Battery type(if applicable): Sealed lead acid
Calculated capacity of batteries to drive the system: In standby mode(hours): In alarm mode(minutes):
Nardini
FIRE EQUIPMENT
www.nardinifire.com/sales@nardinifire.com
FIRE ALARM INSPECTION AND TESTING
5. NOTIFICATIONS MADE PRIOR TO TESTING
Monitoring organization Contact: USA Central Time: 11:15am
Building management Contact: Yes Time: 11:00am
Building occupants Contact: Yes Time: 11:00am
Authority having jurisdiction Contact: Time:
Other,if required Contact: Time:
6. TESTING RESULTS
6.1 Control Unit and Related Equipment
Visual Functional
Description Inspection Test Comments
Control Unit ® ►_
Lamps/LEDs/LCDs
Fuses ® ❑
Trouble Signals ® ►_
Disconnect Switches ❑ ❑
Ground-Fault Monitoring
Supervision ►_i ►_�
Local Annunciator ►:�
Remote Annunciators ❑ ❑
Remote Power Panels
Elevator Recall ❑ ❑
Shunt Trip ❑ ❑
Door Holder ❑ ❑
Area of Refuge ❑ ❑
❑ ❑
❑ ❑
FloN . •
ar ini
FIRE EQUIPMENT
www.nardinifire.com/sales@nardinifire.com
FIRE ALARM INSPECTION AND TESTING
6.2 Power Supplies
Power Battery Discharge Charger
Supply Location Condition Test Test Comments
CI FC-549 Electrical room Good Good Good 2 12v7ah 02/2020
6.3 Secondary Power Location: FACP
Visual Functional
Description Inspection Test Comments
Battery Condition ►_
Discharge Test
Charger Test
Nardini
FIRE EQUIPMENT
www.nardinifire.com/sales@nardinifire.com
FIRE ALARM INSPECTION AND TESTING
6.4 Alarm and Supervisory Initiating Device
Functional
Description Quantity Test Comments
Manual Pulls 6 181
Smoke Detectors 20
Heat Detectors 3 �1
Flame Detectors ❑
Beam Detectors ❑
Wet Water Flow 1 ❑ Tested with Escape
Dry Water Flow 1 ❑ Tested with Escape
Aspirating Smoke Detection ❑
Duct Detector ❑
Sprinkler Tamper(Supervisory) 2 ❑ Tested with Escape
Sprinkler Low/High(Supervisory) 1 ❑ Tested with Escape
CO Detector ❑
Building Temperature ❑
Fire Pump Running ❑
Fire Pump Phase Fail ❑
Fire Pump Phase Reversal ❑
Fire Pump Trouble 0
Kitchen System 0
Gas Detectors ❑
Other ❑
6.4.1 Aspirating Smoke Detection
FILTER AMBIENT ALARM ALARM TRANSPORT
NAME MFG MODEL DATE % ACTION ALERT 1 2 TIME
ar ini
FIRE EQUIPMENT
www.nardinifire.com/sales@nardinifire.com
FIRE ALARM INSPECTION AND TESTING
6.5 Notification Appliances
Functional
Description Quantity Test Comments
Horn/Strobe 16
Horn ❑
Strobe 4
Speaker ❑
Chime ❑
Other Piezo 50
6.5.1 Number of Alarm Notification Circuits 6
6.6 Supervising Station Monitoring
Description Yes No Time Comments
Alarm Signal ® ❑
Alarm Restoration ® ❑
Trouble Signal ® ❑
Trouble Restoration ® ❑
Supervisory Signal ® ❑
Supervisory Restoration ® ❑
7. COMMENTS
Tested normal
8. NOTIFICATIONS THAT TESTING IS COMPLETE
Monitoring organization Contact: USA Central Time:
Building management Contact: Yes Time:
Building occupants Contact: Yes Time:
Authority having jurisdiction Contact: Time:
Other,if required Contact: Time:
9. SYSTEM RESTORED TO NORMAL OPERATION
Date: 2020-02-17 Time: 03:OOpm
10. NARDINI FIRE TECHNICIAN
Printed Name: Kevin Jones Printed Name: Joshua Heller
11. CUSTOMER SIGNATURE '� x
Printed Name: Roshni Signature: _ =`