Report of Inspection/Test
Property
Americinn Oak Park Heights
1305 60th St N
Oak Park Heights, MN 55082
Annual 1 wet 1 dry
Gabrielle Justus
(651)287-1047 Print Date:3/6/2020
February 17, 2020
Signatures
Inspector - Printed Date CompletedInspector - Signature
DAVE L 2/17/20
I state that the information on this form is correct at the
time and place of my inspection, and all equipment
tested at this time was left in operational condition upon
completion of this inspection except as noted.
Owner - Printed Date CompletedOwner - Signature
MANAGER 2/17/20
I acknowledge this report has been reviewed with me.
Except as noted, there have been no changes to the
original approved system.
SK FCI
1234
11:00
02:00
Alarm Panel/CodeSystem Off
System On
Monitoring Company Monitoring Company Operator
Central Station Test
Yes Alarm, Trouble and Supervisory indication tested and
verified with the central station?
Owner Information
Yes Has the occupancy classification and hazard of
contents remained the same since the last inspection ?
YesIs the building occupied ?
Yes Has the system remained in service without
modification since the last inspection ?
YesAre all fire protection systems in service ?
Yes Was the system free of actuations of devices or alarms
since the last inspection ?
Water Based System
Yes Alarm devices free from physical damage?YesGauges on wet pipe system in good condition and
showing normal water supply pressure?
Yes Valve supervisory switches indicate movement?YesHydraulic nameplate, if provided, securely attached to
riser and legible?
Fire Department Connection
Yes Couplings and swivels not damaged and rotate
smoothly?
YesVisible and accessible?
Yes Gaskets in place and in good condition?YesPlugs or caps in place and undamaged?
Yes Check valve is not leaking?YesIdentification sign(s) in place?
Yes Interior free of obstructions (if caps are not in place) ?NAAutomatic drain valve in place and operating properly?
NA Valve clapper operational over its full range (if caps are
not in place) ?
Pipe
Yes Free of mechanical damage and not leaking ?YesIn good condition ?
Yes Properly aligned ?YesNo external corrosion ?
Yes Visible pipe hangers and seismic braces not damaged
or loose ?
YesNo external loads ?
Yes Was an obstruction investigation conducted and the
system flushed ?
Print Date:3/6/2020
Copyright 2002-2019 Life Safety Inspector, OnSite Software
Page 1 of 4
Report of Inspection/Test
Americinn Oak Park HeightsProperty:
31452Inspection Ref:
Annual 1 wet 1 dry
February 17, 2020
Sprinklers
Yes Proper number and type of spare sprinklers?YesSprinkler wrench with spare sprinklers?
Yes Free of obstructions to spray patterns?YesFree of corrosion?
Yes Free of physical damage?YesFree of foreign materials including paint?
Yes Fast Response sprinklers in service for less than 20
years? If "no" test sample now and every 10 years.
YesAre all sprinklers in service dated 1920 or later?
Yes If sprinklers have been replaced, were they proper
replacements?
YesStandard sprinklers less than 50 years old ? If no test
sample now and every 10 years.
Yes Sprinklers and spray nozzles protecting commercial
cooking equipment and ventilating systems replaced
except for bulb-type which show no signs of grease
buildup?
Cold Weather Check
Yes Interior of pipe in preaction and dry pipe systems which
passes through freezers free of ice blockage?
YesAdequate heat in areas with wet piping?
Yes Auxillary drains drained in dry pipe, preaction and
deluge systems prior to the onset of freezing weather?
Dry Valve
Yes Gauges on dry, preaction and deluge systems in good
condition and showing normal air and water pressure?
YesEnclosures around dry-pipe, preaction or deluge valves
maintaining a minimum of 40 deg F?
Yes Trim valves in appropriate (open or closed) position?YesFree from physical damage?
Yes Interior of dry pipe, preaction and deluge valves passed
internal inspection (required every 5th year if resetable
without opening)?
YesNo leakage from intermediate chamber?
Yes Low air pressure signal passed test?YesPriming water level correct?
NA Automatic air maintenance devices on dry pipe and
preaction systems passed test?
YesQuick opening devices passed test?
Yes Interior of dry pipe, preaction and deluge valves
cleaned?
YesDry pipe systems being maintained in dry condition?
Valve Interior Inspection
NA Check valves internally inspected and all parts operate
properly,move freely and are in good condition?
NoAlarm valves and their associated strainers, filters and
restriction orifices passed internal inspection?
NA Gauges checked against calibrated gauge or replaced
?
NoStrainers, filters, restricted orifices and diaphragm
chambers on dry pipe, preaction and deluge valves
passed internal inspection?
Air Compressor Inspection
Model of compressorManufacturer of compressor
Compressor Description/TypeSize of compressor (HP)
Yes Compressor appears free of leaks?YesCompressor appears to be in working condition?
Yes Guages appear Ok and show normal PSIYesCompressor and motor are free of vibration and
unusual noies?
Yes Electrical connections Ok?YesOil appears clean with no burnt odor
Yes Inlet air filter clean?YesBreaker in the ON Postion?
Yes Tension on the belt is Ok?YesBelt is in good condition?
Yes Dryer/Separator Ok?NAHas condensate/water been drained from the tank
and/or water separator?
Flow Test
Connection FlowedSystem Alarms Actuate
Static Resid
Results
comparable to
prior test
Pressure (psi)
Static
Waterflow
devices pass
test
Outlet
Size
Main drain Yes2YesMECH RM Yes655575
Print Date:3/6/2020
Copyright 2002-2019 Life Safety Inspector, OnSite Software
Page 2 of 4
Report of Inspection/Test
Americinn Oak Park HeightsProperty:
31452Inspection Ref:
Annual 1 wet 1 dry
February 17, 2020
Flow Test
Connection FlowedSystem Alarms Actuate
Static Resid
Results
comparable to
prior test
Pressure (psi)
Static
Waterflow
devices pass
test
Outlet
Size
ITV Yes1/2"YesYes
WATER FLOW TIMES: 66 SEC
Auxiliary Drains
System / Location Water Flow Observed ?Aux Drain Drained ?Drain
Yes
Valve Inspection List
Valve TypeLocation / Description
Easily AccessibleSigns Secured SizeQty
Open Exercised Stem Lubricated YesSupervised YesYesYes4ButterflyControl Valve Chart/Insp/Maint 1
YesSupervised YesYesYesYes4OS&YControl Valve Chart/Insp/Maint 1
Dry Valve Trip Test -
Dry Valve Size:Year:Q. O. D.Year:
Make Model Serial no.Make Model Serial no.
Time to Trip thru
test pipe Water Pressure Air Pressure Trip point
air pressure
Time water reached
test outlet Alarm Operated
No Q.O.D.
Comparable to previous tests ?
secsecpsipsipsi
4
Central AG
No QOD
4675 11
LOW AIR-22
Print Date:3/6/2020
Copyright 2002-2019 Life Safety Inspector, OnSite Software
Page 3 of 4
Report of Inspection/Test
Americinn Oak Park HeightsProperty:
31452Inspection Ref:
Annual 1 wet 1 dry
February 17, 2020
Deficiency / Recommendations Summary
These items were deficient and do not meet the requirements of the applicable code at the time of the inspection. Items marked
Recommendation are not required by the applicable code but are opportunities to improve the Life Safety of the property.
Valve Interior Inspection
No Check valves internally inspected and all parts operate properly,move freely and are in
good condition?
NFPA-25-2002 12.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate properly, move freely, and
are in good condition.
No Gauges checked against calibrated gauge or replaced ?
NFPA-25-2002 12.2.8.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. Gauges not
accurate to within 3 percent of the full scale shall be recalibrated or replaced.
Print Date:3/6/2020