HomeMy WebLinkAbout2020-03-13 Ahern Annual Sprinkler Inspection Report ,3705 26'" Avenue, Suite 110 Sprinkler Inspection
Minneapolis, MN 55441
main 763.268.0515 fax 763.268.0516 Annual
HERN E www . ahernfire . com Work Order: 1338828
Agreement: 36071
Inspection Start Date : 03/13/2020
Customer PO: SC-2003-0070-1-4
Inspection Location
Contact: Greg Inman
Goodwill Easter Seals Cell#: (612)221.7367
5980 Krueger Lane N Phone#: (763) 591.5588
Oak Park Heights MN 55082 E-Mail: gsinman@eganco.com
Cust ID: 101250 Loc ID: 032
Check Valve
Qty: 1 Status: Complete Eq ID: 032-CHKVLV2
Customer System ID
Manufacturer ID Unknown
Model ID U
Size 4"
Location In Buildin• NE corner
Question Result
10 What date was the last internal ins section serformed on the check valve? 2017-04-01
Bldg/Ovvner Questions SP 032-GENSPQUES1 -General SP Questions
Qty: 1 Status: Corn.lete E. ID: 032-SPBOQUESI
Question , Result
0� Did owner verify that there is adequate heat(40°F min.)in all areas with water-filled Yes
i.in ?
Check Valve 032-GENSPQUESI -General SP Questions
Qty: 1 Status: Corn lete E. ID: 032-CHKVLV1
Customer System ID
Manufacturer ID deringer
Model ID 20
Size 4"
Location In Building riser room
Question Result
10 What date was the last internal inspection performed on the check valve? 2017-04-01
Fire Department Connection 032-GENSPQUESI -General SP Questions
Qty: 1 Status: Complete Eq ID: 032-FDC1
FDC Type Wall Exposed
Size 5x4 Storz
Location In Building NE corner
Question Result
10 Is the F.D.C.Visible and Accessible? Yes
20 Are the plugs and caps in place and undamaged? Yes
30 Are couplings and swivels free of damage and rotate smoothly,are gaskets in place and in Yes
good condition,are identification signs in place?
40 Is the F.D.C. Check Valve free of Leaks,is the automatic drain valve in place and
Yes
operating properly,are the clappers in place and operating properly?
Sprinkler Questions 032-GENSPQUESI -General SP Questions
Qty: 1 Status: Complete Eq ID: 032-SPQUESI
Question Result
10 Gauges in good condition and showing normal water or air pressure? Yes
20 At the time of inspection,was there adequate heat(40°F min.or 70°F min. for diesel NA
Thomas D Yorkson
Page 1 of 3
pumps without engine heater)in all valve and pump houses?
50 Hydraulic nameplate(calculated systems only) securely attached to riser and legible? Yes
60 Alarm devices free from mechanical damage? Yes
100 Date gauges were last tested with calibrated gauge or replaced? 2017-04-01
110 System information sign legible and securely attached to riser supplying an antifreeze loop, NA
dry system,preaction system,or auxiliary system control valve?
130 Visible pipe hangers and seismic braces free from damage and securely attached? Yes
140 Visible pipe and fittings free from mechanical damage,leakage,and external corrosion? Yes
150 Visible piping free from external loads? Yes
155 Has any heat tape on sprinkler piping been inspected per manufacturer's requirements? NA
160 Date of last internal inspection of the piping? 2017-04-01
170 Visible sprinklers free from leakage,corrosion,foreign materials,paint,and physical No DEF
damage?
180 Visible sprinklers installed in the proper orientation? Yes
190 Liquid in all visible glass bulb sprinklers? Yes
200 Minimum clearance being maintained below all sprinklers? .Yes
220 Proper number and type of spare sprinklers and wrenches?— " — Yes
230 Visible sprinklers dated 1920 or later? Yes
240 Fast response sprinklers 20 or more years old replaced or successfully sample tested NA
within last 10 years?
250 Standard response sprinklers 50 or more years old replaced or successfully sample tested NA
within last 10 years?
260 Standard response sprinklers 75 or more years old replaced or successfully sample tested NA
within last 5 years?
270 Extra high temperature solder-type sprinklers or sprinklers in corrosive environments NA
replaced or successfully sample tested within last 5 years?
280 Dry sprinklers replaced or successfully sample tested within last 10 years? NA
Valve Inspection Record
o
x
U
4.7
w O .4 cn v 'y
y Qcu
O. O yH
to aiz �,
i.
O
es et x o
Valve ID Valve Type Size Secured A 4-' 4 H a w a
Control Valve AF Check Butterfly 4" Supervised Yes Yes N/A Yes Yes Yes N/A
Control Valve BF Check Butterfly 4" Supervised Yes Yes N/A Yes Yes Yes N/A
Water Flow Alarm Tests
System Number Time to Alarm(sec.) Results acceptable?
Flow Switch 50 Yes
Main Drain Tests
System Number Static Pressure Residual Pressure Time for Pressure Size of Drain Are test results
Before Test(P.S.I.) (P.S.I.) to return to acceptable?
original(sec)
Main Drain 65 58 2 2 Yes
Thomas D Yorkson Page 2 of 3
Deficiency Recap:
032-SPQUES1-Sprinkler Questions 032-GENSPQUES1-General SP Questions
Question ID: 170 Task: Annual Location:
Question: Visible sprinklers free from leakage,corrosion,foreign materials, No
paint,and physical damage?
Tech Notes There is(1)upright head in loading dock area that has tape on it.This should be able to be removed with a 12'
ladder
Deficiency NFPA 25-2011 Edition Section: 5.2.1.1.2
Authority Any sprinkler that shows signs of any of the following shall be replaced: (1)Leakage(2)
Corrosion(3)Physical damage(4)Loss of fluid in the glass bulb heat responsive element(5)
Loading(6)Painting unless painted by the sprinkler manufacturer
Additional Notes:
No Additional Notes
NOTES:
Any backflow preventers tested as part of this inspection were tested in accordance with all applicable state rules and
regulations and all readings are true and accurate to the best of my knowledge.
Any comments or findings in this inspection report are not in any way to be considered a fire protection engineering review.
All fire protection system inspection and testing,as contracted with Customer is performed to the following NFPA codes and
editions (listed as code-edition);10—2013,11-2005,12-2008,12A-2004,16-2007,17-2013,17A—2013,25-2011,72-2010,96—
2014,409-2011,750-2006,1962—2013,2001—2008 and Life Safety 101 (Chapter 7)-2012.
Inspection Contractor: AFP Twin Cities Service
13705 26th Ave
Minneapolis,MN 55441-3635
Building Owner or Authorized Representative: Technician:
Signature: Signature:
Name: Thomas D Yorkson
Name: Greg Inman
License#:
Customer
Signature 03/13/2020 Inspection 03/13/2020
Date: End Date:
This inspection report is expressly subject to the terms and conditions of sale located at JF Ahern Terms and Conditions which are
incorporated by reference as if fully set forth herein.By accepting this inspection report you are deemed to have read,understood and
accepted the electronic terms and conditions of sale.
An experienced Fire Protection professional will be contacting you shortly to discuss how we might help eliminate any
deficiencies identified in this inspection.
This document is the property of the inspecting entity.Copyright J.F.Ahern Co/Ahern Fire Protection.
REPRODUCTION IN ANY FORM VIOLATES COPYRIGHT.
Thomas D Yorkson Page 3 of 3