HomeMy WebLinkAbout2010-04-07 Firenet Systems Testing Report RETROTEC DISCHARGE SIMULATOR VER. HA5. 1 HP RETENTION TIME PREDICTION MODEL Location: Oak Park Heights City Hall Room Name: Server Room 004 Testing Company: FIRENET SYSTEMS INC. Technician: HONMYHR Date: 4/7/10 Test #: testi Whole Room Test. All Outputs are in IMPERIAL Units. (except pascals) Gas Being Modelled: FE 25 Lbs./Kgs. of Agent In Cylinder(s) : 91 .00 Net Room Volume (ft3) : 3264. 50 Room Height (ft) : 13.00 Minimum Protected Height ( ft) : 9. 75 Minimum Retention Time (min) : 10.00 Initial Gas Concentration (%) : 8. 11 Static Pressure @ Discharge: 0.00 Equivalent Leakage Area (ELA ft2) : 0. 31 Hole in Ceiling ( in2) : 22 .22 Hole in Floor (BCLA in2) : 22 .22 This Room PASSES the Test as the Predicted Retention Time is 15.8 minutes for the agent/air interface to drop below the minimum protected height. Witnessed By: X Software Conforms To 1992 NFPA 12A/2001 TCD Room Integrity Procedure. Maximum Allowable ELA (in2) : 69 . 75 Interface Height @ 10 Minutes: 10.89 PAGE 1 OF 2 Licensed To: FIRENET SYSTEMS INC. Registration #: 145 * 7_ 5* �' ' �- a h_ - t � - - __-_,-,-..,,,,,,,,--------,----a.- - --- �.,, ° - -- . :. �ti <� ate,,-�" l u.�; Date of Test/Inspectionv�`�. i — j ► Time: 41 , R [ -, _ . t . i I ` F°1 , a :,7.s ' . — 1 ,Au � _ ,xi Imitirm-s . �,� t�, i, � - NAME: r Ark.Firenet Systems, Inc. ADDRESS: 6224 Lakeland Ave. N., Suite 100 ADDRESS: " ; Brooklyn Park, MN 55428 i�t' rk , REP: OWNER CONT.: LICENSE NO.: TS00253 TELEPHONE: TELEPHONE: 763 536-3950 t41(:)t;''''1.'C'''';':.**'' 'r � t�a�- _ -ice _ �': k ct A CONTACT: TELEPHONE: TELEPHONE: MONITORING ACCT. NO: Panel Manufacturer: -,. ; -- I -4 Model No: tit zt, t �� "fix �� Circuit Styles: '. . ; No. of Notification Ckts. �, Manual Stations i [K [, ok. No. of Initiating Ckts. 1. Ion Detectors [ ] [ ] Panel Firmware Rev. AlPhoto Detectors a D4 foQ014. Program Software Rev. ! Duct Detectors [ ] [ ] ' -- Heat Detectors [ ] [ ] Control Panel [, j( Supervisory Sw. [ ] [ ] Interface EQ {}I' Other: Lamps/LEDs {] CO { ( ' �(' ok Fuses g OIL [ ] [ ] Primary Power Supply [,1t (3f( [ ] [ ] Trouble Signals [/' X0k [ ] [ ] Battery Condition [ [ 6f Comments: Remote Annunciator [ ] [ ] Comments: _ 3 � 1 7 Phone Set [ 1 [ l k . .4-. _ : , ' - _: v,:- _.,,. .. r Phone ks [ 1 [ ] Audible Off-Hook In or [ ] [ ] Visual Amplifier(s) [ ] [ ] Speakers [ ] [ ] Tone Generators [ [ ] Voice Clarity [ ] [ ] Call In Signal [ , [ ] Comments: Comments: 7 .".--4-...,......\ Additional Comments: G c A 0 075- )r ery 4 Ae j sa se‘N - a.'?' ,H"'i"` ,. '" x-- „sem u, _ i*- .#} 't s..�,, Name of Inspector: ----)2-114„,a /....0-t/ Owner Rep: Date: —/ -/,,t Date: Si nature: --------- .) g — / _..eee Signature: FAN TEST READINGS & DATA 2- Location: Oak Park Heights City Hall Room Name: Server Room 004 Test #: testi Temperature IN: 70 Temperature OUT: 70 Static Pressure (a Fan Test: 0 DEPRESSURE PRESSURE Operator and Gauges Location IN IN Room Pressure Gauge Reading 13 .0 13.0 Corrected Room Delta P(pa) -13.0 13.0 Blower Range Config Used 1 .4 1 .4 Flow Pressure Gauge Reading 64 .0 55.0 Corrected Flow Pressure 64.0 42.0 Calculated Air Flow (cfm) 190.4 154.2 Temp. Corrected Air Flow 190.4 154.2 Leakage Area (in2) 49. 1 39.8 Average Leakage Area (in2) 44.4 RN= 1 .515 PC= 12.2 PA= 12.2 AT= 0.017 ALL= 0.009 FA= 0.500 C3= 2.259 C4= 0.000 CF= 1 .000 GD= 5.060 K1= 2.7240 K2= 0.0063 AR= 23.329 T= 946.832 EL= 0.000 TD= 70.000 PAGE 2 OF 2 Licensed To: FIRENET SYSTEMS INC. Registration #:145