HomeMy WebLinkAbout2018-09-07 Nardini Fire Equipment - Inspection & Testing Report 1 g. ar ini
FIRE EQUIPM• ENT
www.nardinifire.com/sales@nardinifire.com
5/2016
ENGINEERED SYSTEM INSPECTION AND TESTING REPORT St.Paul,MN
Name of Facility: PENNIES FROM HEAVEN BOAT-NORTH DOCK-SLIP#3 Installation/Service Report Date: 09/07/2018
X
Street: 6413 ST.CROIX TRAIL Time In: 0700
AM 0 ime Out: 1030 M❑
City: OAK PARK HEIGHTS State: MN Zip: 55082 Last Maintenance Date: 2006-09-07 Installation 0
Authorized Contact: , Last Maintained By: Other Quarterly 0
Phone: 651 Semi-Annual ❑x
Annual 0
Suppression Type Panel Type
Manufacturer of System: Kidde Manufacturer: N/A Revision:
Type of Agent: Co2 Model: Intelligent 0 Conventional 0
Chip#:
System Location: Boat Engine Compartment Electrical Disconnect Location: Hazard Description: Engine Compartment
Manual Release Operable? Yes 0 No x❑ Qty: ( 2 ) Alarms Operable? Yes 0 No X❑
Abort Operable? Yes 0 No 0 Qty: ( 0 ) Lockout Valve? Yes 0 No ❑ N/A ❑x
Bypass Switch Operable? Yes 0 No 0 Qty: ( 0 ) Odorizer? Yes 0 No 0 N/A X❑
Actuator Operable? Yes 0 No ❑X Date: Type: Kidde 81-872365-000 Time Delay? Yes 0 No 0 N/A El
Auto Detection Operable? Ye s 0 No ❑x Discharge Hose Date: 1999-09-07
Detection Type: Ion( ) Photo( ) Heat 0 HIt)Temps: Optical( ) Aspirating( ) Other( )
Notification Type: Bells( I ) Horns( ) Horn/Strobes( ) Strobes( ) Other( ) Model:
Auxiliary Functions Relay Press Low High Tested Batteries
Switch Volt Volt
Shutdown Equipment 0 0 0 ,+ Size Qty. Date(s)
Shutdown Ventilation 0 , 0 0 _4 N/A
Shutdown Dampers 0 0 0 0 0
Building/Local Alarm Tie-In 0 0 0 0 0
Panel Transfer to Battery?Yes 0 No 0 Load Test:
Charger Test:
Type of Release: Single Zone( X) Cross Zoned( ) Counting Zone( ) Other( ) Discharge Delay- 0 Seconds Pneumatic/Electric
Sequence of Operations: 1°Alarm- Bell off of P/S 2nd Alarm- Discharge- Abort Delay- Seconds PNEUMATIC
Perimeter Doors Sealed Yes 0 No r'_ Ceiling Tiles Clipped Yes 0 No 0 N/A el
Warning Signs Yes 0 No r_ Hazard Changes Yes 0 No® N/A 0
Checked Hazards for Leaks Yes 61 No 0 Nozzles Cl.(8"dia.) Yes C No 0 N/A 0
Is actuator on cylinder and strapped? Yes® No 0 Serial# Not Sealed
Comments:
Red Tagged total nonfunctional system.Bilge Blowers dont shut down on pressure switch only a bell comes on. No engine shutdown on pressure switch 75#Co2 needs Hydrotest last test 11/99 and now
empty Kidde 3/4 Discharge hose expired (3)Discharge nozzle are marked with a 7+Bad kidde control head 81-872365-000 wouldnt trip with cable or monometer (3)HID detectors not working with
pipe disconnected No signs System discharged on its own several minutes after the testing was completed and everything was armed.Now empty Co2 Cylinder!!Customer wants price on new system.
>5.--.>
LeMoine,D Steve Bratrud _
Nardini Fire Teclmician(s) Customer/Authorized Agent—Printed Name Customer/Authorized Agent-Signature
1
IF41 Nardini
FIRE EQUIPMENT
www.nardinifire.com/sales@nardinifire.com
5/2016
Aspirating Smoke Detection
FILTER TRANSPORT
NAME MFG MODEL DATE AMBIENT% ACTION ALERT ALARM I ALARM 2 TIME
5/2016
2
Nardini
FIRE EQUIPMENT
www.nardinifire.com/sales(a�nardinifire.com
Tanks
SERIAL NUMBER FILL WT. GROSS WT. ACT.WT./LL TEST DATE PSIG VALVE MODEL
1. 75 1999 Kidde
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
40.
41.
42.
43.
44.
45.
46.
47.
48.
49.
50.
51.
52.
53.
54.
3