HomeMy WebLinkAbout2021-02-11 Wet & Dry Inspection & Testing ReportLuke Heikkila 31453Inspection Ref: Conducted by: Report of Inspection/Test Property Americinn Oak Park Heights 1305 60th St N Oak Park Heights, MN 55082 Annual 1 wet 1 dry Gabrielle Justus (651)287-1047 Print Date:2/25/2021 February 11, 2021 Signatures Inspector - Printed Date CompletedInspector - Signature Luke Heikkila 2/11/21 I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted. Owner - Printed Date CompletedOwner - Signature Nardini 2/11/21 I acknowledge this report has been reviewed with me. Except as noted, there have been no changes to the original approved system. SK FCI 1234 12:30 02:00 Alarm Panel/CodeSystem Off System On Monitoring Company Monitoring Company Operator Central Station Test Yes Alarm, Trouble and Supervisory indication tested and verified with the central station? Owner Information Yes Has the occupancy classification and hazard of contents remained the same since the last inspection ? YesIs the building occupied ? Yes Has the system remained in service without modification since the last inspection ? YesAre all fire protection systems in service ? Yes Was the system free of actuations of devices or alarms since the last inspection ? Water Based System Yes Alarm devices free from physical damage?YesGauges on wet pipe system in good condition and showing normal water supply pressure? Yes Valve supervisory switches indicate movement?YesHydraulic nameplate, if provided, securely attached to riser and legible? Fire Department Connection Yes Couplings and swivels not damaged and rotate smoothly? YesVisible and accessible? Yes Gaskets in place and in good condition?YesPlugs or caps in place and undamaged? Yes Check valve is not leaking?YesIdentification sign(s) in place? Yes Interior free of obstructions (if caps are not in place) ?NAAutomatic drain valve in place and operating properly? NA Valve clapper operational over its full range (if caps are not in place) ? Pipe Yes Free of mechanical damage and not leaking ?YesIn good condition ? Yes Properly aligned ?YesNo external corrosion ? Yes Visible pipe hangers and seismic braces not damaged or loose ? YesNo external loads ? Yes Was an obstruction investigation conducted and the system flushed ? Print Date:2/25/2021 Copyright 2002-2016 Life Safety Inspector, OnSite Software Page 1 of 4 Report of Inspection/Test Americinn Oak Park HeightsProperty: 31453Inspection Ref: Annual 1 wet 1 dry February 11, 2021 Sprinklers Yes Proper number and type of spare sprinklers?YesSprinkler wrench with spare sprinklers? Yes Free of obstructions to spray patterns?YesFree of corrosion? Yes Free of physical damage?YesFree of foreign materials including paint? Yes Fast Response sprinklers in service for less than 20 years? If "no" test sample now and every 10 years. YesAre all sprinklers in service dated 1920 or later? Yes If sprinklers have been replaced, were they proper replacements? YesStandard sprinklers less than 50 years old ? If no test sample now and every 10 years. NA Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating systems replaced except for bulb-type which show no signs of grease buildup? Cold Weather Check Yes Interior of pipe in preaction and dry pipe systems which passes through freezers free of ice blockage? YesAdequate heat in areas with wet piping? Yes Auxillary drains drained in dry pipe, preaction and deluge systems prior to the onset of freezing weather? Dry Valve Yes Gauges on dry, preaction and deluge systems in good condition and showing normal air and water pressure? YesEnclosures around dry-pipe, preaction or deluge valves maintaining a minimum of 40 deg F? Yes Trim valves in appropriate (open or closed) position?YesFree from physical damage? Yes Interior of dry pipe, preaction and deluge valves passed internal inspection (required every 5th year if resetable without opening)? YesNo leakage from intermediate chamber? Yes Low air pressure signal passed test?YesPriming water level correct? Yes Automatic air maintenance devices on dry pipe and preaction systems passed test? YesQuick opening devices passed test? Yes Interior of dry pipe, preaction and deluge valves cleaned? YesDry pipe systems being maintained in dry condition? Valve Interior Inspection 5 Year Inspection NA Check valves internally inspected and all parts operate properly,move freely and are in good condition? NoAlarm valves and their associated strainers, filters and restriction orifices passed internal inspection? NA Gauges checked against calibrated gauge or replaced ? NoStrainers, filters, restricted orifices and diaphragm chambers on dry pipe, preaction and deluge valves passed internal inspection? Air Compressor Inspection Master Force Model of compressorManufacturer of compressor Compressor Description/TypeSize of compressor (HP) Yes Compressor appears free of leaks?YesCompressor appears to be in working condition? Yes Guages appear Ok and show normal PSIYesCompressor and motor are free of vibration and unusual noies? Yes Electrical connections Ok?YesOil appears clean with no burnt odor Yes Inlet air filter clean?YesBreaker in the ON Postion? Yes Tension on the belt is Ok?YesBelt is in good condition? Yes Dryer/Separator Ok?NAHas condensate/water been drained from the tank and/or water separator? Flow Test Connection FlowedSystem Alarms Actuate Static Resid Results comparable to prior test Pressure (psi) Static Waterflow devices pass test Outlet Size Main drain Yes2NAMECH RM NA645774 Print Date:2/25/2021 Copyright 2002-2016 Life Safety Inspector, OnSite Software Page 2 of 4 Report of Inspection/Test Americinn Oak Park HeightsProperty: 31453Inspection Ref: Annual 1 wet 1 dry February 11, 2021 Flow Test Connection FlowedSystem Alarms Actuate Static Resid Results comparable to prior test Pressure (psi) Static Waterflow devices pass test Outlet Size ITV Yes1/2"YesYes WATER FLOW TIMES: 65 SEC Auxiliary Drains System / Location Water Flow Observed ?Aux Drain Drained ?Drain Yes Valve Inspection List Valve TypeLocation / Description Easily AccessibleSigns Secured SizeQty Open Exercised Stem Lubricated YesSupervised YesYesYes4ButterflyControl Valve Chart/Insp/Maint 1 YesSupervised YesYesYesYes4OS&YControl Valve Chart/Insp/Maint 1 Dry Valve Trip Test - Dry Valve Size:Year:Q. O. D.Year: Make Model Serial no.Make Model Serial no. Time to Trip thru test pipe Water Pressure Air Pressure Trip point air pressure Time water reached test outlet Alarm Operated No Q.O.D. Comparable to previous tests ? secsecpsipsipsi 4 Central AG No QOD 124264 Low Air-21 Print Date:2/25/2021 Copyright 2002-2016 Life Safety Inspector, OnSite Software Page 3 of 4 Report of Inspection/Test Americinn Oak Park HeightsProperty: 31453Inspection Ref: Annual 1 wet 1 dry February 11, 2021 Deficiency / Recommendations Summary These items were deficient and do not meet the requirements of the applicable code at the time of the inspection. Items marked Recommendation are not required by the applicable code but are opportunities to improve the Life Safety of the property. Valve Interior Inspection 5 Year Inspection No Check valves internally inspected and all parts operate properly,move freely and are in good condition? NFPA-25-2002 12.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate properly, move freely, and are in good condition. No Gauges checked against calibrated gauge or replaced ? NFPA-25-2002 12.2.8.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. Gauges not accurate to within 3 percent of the full scale shall be recalibrated or replaced. Print Date:2/25/2021 Copyright 2002-2016 Life Safety Inspector, OnSite Software Page 4 of 4