HomeMy WebLinkAboutBP 2021-00127 Storage Shed - Electrical Permit & Inspection Report r DEPARTMENT OF 443 Lafayette Road N.,St. Paul, MN 55155
LABOR AND INDUSTRY (651) 284-5026,www.dli.mn.gov
Electrical Permit Bext l _ o o l art
Permit Number: ELE2110-06489
Permit Information as of 10/15/21
Structure Type:One-Family Dwelling I Existing Dwelling or Other Items Permit Status: Issued
Site County: Washington County Issued Date: 10/15/21
Site Address: 5565 Peller Ave N, Oak Park Heights, MN 55082 Expiration Date: 10/15/22
Fees Paid: $71.00
Permit Applicant Information
ALL TECH ELECTRIC LLC Phone: (651) 303-8882
ALL TECH ELECTRIC LLC Mobile: (651) 303-8882
11240 STILLWATER BLVD N, LAKE ELMO, MN55042 Email: brandon@alltechmn.com
Property Owner's Information
Tom Thiets Phone: (651) 788-5112
5655 Peller Ave N, Bayport, MN 55082 Mobile: (651) 788-5112
Contracted Electrical Inspector's Information
Name: Donald Edel Phone: (507) 210-8233
Don Edel Inspections LLC Email Address: mailto:
don.edel.inspections@gmail.com
Project Information
Electrical Utility: Xcel Energy, Inc. Phone: Email: bctmn@xcelenergy.com
Rough-In Inspection Required: Yes Number of Inspections Requested: 2
Directions to Job Site: Why 36 east to Osgood ave south to 59th street east. 59th street becomes 60th street follow to
Peller Ave N take a right the house is on the left side of the street
Project Description: Install emergency generator transfer switch and feeder from generator, plus underground ckt to shed
Install 200 amp emergency generator transfer switch for service, plus 60 amp feeder from generator. Install 20 amp 120
volt underground branch circuit to shed.
A rough-in inspection is required before any wiring is concealed by insulation, wall covering, ceiling cover, trench
backfill, etc. If wiring is concealed before inspection, the person responsible for concealing the wiring must cover the
cost associated with uncovering and replacing the covering material.
The installer must notify the inspector for final inspection when the wiring is complete and before the wiring is utilized
and the space is occupied.
Print Date: 10/15/2021
DEPARTMENT OF , • ,r0
• LABOR AND INDUSTRY - ;
ti
Inspection Report
Project Name: Install emergency generator transfer Permit Number: ELE2110-06489
switch and feeder from generator, plus underground
ckt to shed
Project location/address: 5565 Peller Ave N, Oak Park Heights, Washington County, MN, 55082
Applicant: ALL TECH ELECTRIC LLC Phone: (651) 303-8882
Owner: Tom Thiets Phone: (651) 788-5112
Inspection Type: Final Result: Pass with Conditions
Inspector Report
Install 200 amp emergency generator transfer switch for service, plus 60 amp feeder from
generator. Install 20 amp 120 volt underground branch circuit to shed. (final)
(the main breaker in the shed panel needs to have a retaining device to lock the breaker in
place)
(2-ground rods are required at the garage service)
NEC 250.53, Unless a rod, pipe and plate electrode has a resistance to ground of 25 ohms or
less, it shall be supplemented with another acceptable electrode other than an underground
water pipe.
NEC 408.36, Back-fed overcurrent devices shall be secured by an additional approved fastener
that requires a tool for removal.
MN STATUTE326B.36, Correct the noted deficiencies. Return a signed copy of the Inspection
Report to the inspector when the corrections are complete but no later than 14 days from the
date of issuance unless otherwise instructed by the inspector.
Inspected By: Donald Edel Email: don.edel.inspections@gmail.com
Phone: (507) 210-8233 Date: 12/7/2021
443 Lafayette Road N., St. Paul, MN 55155 1 (651) 284-50051 www.dli.mn.gov