Project Name: PANEL REPLACEMENT Permit Number: ELE2105-09334
Project location/address: 14250 55th St N, Oak Park Heights, Washington County, MN, 55082
Applicant: SUNSHINE ELECTRIC LLC Phone: (651) 442-1147
Owner: SCOTT ANDERSON Phone: (651) 442-1147
Inspection Type: Final Result: Corrections Required
Inspector Report
replace service panel and add recessed lighting and receptacles in basement (final)
2-new circuits (final)
**basement receptacles are required to be tamper resistant / GFCI AND AFCI protected
**the altered switch must be replaced with an uncompromised switch plate.
**the service has been upgraded from a 100 amp service to a 200 amp service, therefore
requiring an emergency disconnect to be installed.
(if the "emergency disconnect" is also the "service disconnect", then the service panel will need
to be converted to a sub-panel)
MN Rules 3801.3620, All electrical equipment, including luminaires, devices and appliances
used as part of or in connection with an electrical installation shall be listed and labeled by a
Nationally Recognized Testing Laboratory (NRTL) as having been tested and found suitable for a
specific purpose.
NEC 210.8(A) and 406.4 The ground-fault circuit-interrupter shall be installed in a readily
accessible location. Ground-fault circuit-interrupter (GFCI) protection shall be provided for all
125-volt through 250-volt, receptacle outlets installed outdoors, indoor damp and wet
locations, in boathouses, crawl spaces, basements, laundry areas, garages, accessory buildings,
bathrooms, at kitchen countertops and within 6-feet of the top inside edge of all sink bowls,
and within 6-feet from the outside edge of bathtubs and shower stalls.
GFCI protection shall be provided for all lighting outlets installed in crawl spaces.
NEC 210.12, All branch circuits supplying 125-volt, 15- and 20-amp outlets or devices in
dwelling unit kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens,
bedrooms, sunrooms, recreation rooms, laundry areas, closets, hallways or similar areas shall
be protected by a listed combination-type AFCI device. AFCI protection is also required where
branch circuit wiring in the above locations is modified, replaced or extended.
MN STATUTE 3266.37, There will be a charge of $35.00 for an extra inspection required to be
paid before the next inspection.
443 Lafayette Road N., St. Paul, MN 55155 1 (651) 284-5005 www.dli.mn.gov
nil DEPARTMENT OF .rr0
frA'
LABOR AND INDUSTRY fr
�
Inspection Report ° ` -F
NEC 110.3, Listed electrical equipment shall be installed and used in accordance with the
listing requirements and the manufacturer's installation instructions.
NEC 406.4 &t 406.12, All 125- and 250-volt, 15- and 20-amp receptacles installed or replaced in
dwelling units shall be listed as tamper-resistant (TR).
NEC 230.67, A dwelling electrical service must be protected by a Type 1 or Type 2 surge
protective device.
NEC 230.85, Each dwelling shall have an outdoor readily accessible emergency disconnect
installed. The emergency disconnect could be a service disconnect for the dwelling or it could
be a disconnect supplied by the serving utility. If the disconnect is the service disconnect, it
must be labeled as the "EMERGENCY DISCONNECT- SERVICE DISCONNECT". If the disconnect is
provided by the serving utility, and is not the service disconnect, the disconnect must be
labeled "EMERGENCY DISCONNECT - NOT SERVICE EQUIPMENT".
Inspected By: Donald Edel Email: don.edel.inspections@gmail.com
Phone: (507) 210-8233 Date: 6/1/2021
443 Lafayette Road N., St. Paul, MN 55155 (651)284-5005 I www.dli.mn.gov
MIDEPARTMENT OF D� D
LABOR AND INDUSTRY
❑ i o•.
Inspection Report
Project Name: PANEL REPLACEMENT Permit Number: ELE2105-09334
Project location/address: 14250 55th St N, Oak Park Heights, Washington County, MN, 55082
Applicant: SUNSHINE ELECTRIC LLC Phone: (651) 442-1147
Owner: SCOTT ANDERSON Phone: (651) 442-1147
Inspection Type: Final Result: Corrections Required
Inspector Report
443 Lafayette Road N., St. Paul, MN 55155 (651) 284-5005 I www.dli.mn.gov
mlDEPARTMENT OF
LABOR AND INDUSTRY
Inspection Report
Inspection Failed.
MN Rules 3801.3620, All electrical equipment, including luminaires, devices and appliances
used as part of or in connection with an electrical installation shall be listed and labeled by a
Nationally Recognized Testing Laboratory (NRTL) as having been tested and found suitable for a
specific purpose.
NEC 210.8(A) and 406.4 The ground-fault circuit-interrupter shall be installed in a readily
accessible location. Ground-fault circuit-interrupter (GFCI) protection shall be provided for all
125-volt through 250-volt, receptacle outlets installed outdoors, indoor damp and wet
locations, in boathouses, crawl spaces, basements, laundry areas, garages, accessory buildings,
bathrooms, at kitchen countertops and within 6-feet of the top inside edge of all sink bowls,
and within 6-feet from the outside edge of bathtubs and shower stalls.
GFCI protection shall be provided for all lighting outlets installed in crawl spaces.
NEC 210.12, All branch circuits supplying 125-volt, 15- and 20-amp outlets or devices in
dwelling unit kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens,
bedrooms, sunrooms, recreation rooms, laundry areas, closets, hallways or similar areas shall
be protected by a listed combination-type AFCI device. AFCI protection is also required where
branch circuit wiring in the above locations is modified, replaced or extended.
MN STATUTE 3266.37, There will be a charge of $35.00 for an extra inspection required to be
paid before the next inspection.
NEC 110.3, Listed electrical equipment shall be installed and used in accordance with the
listing requirements and the manufacturers installation instructions.
NEC 406.4 Et 406.12, All 125- and 250-volt, 15- and 20-amp receptacles installed or replaced in
dwelling units shall be listed as tamper-resistant (TR).
NEC 230.67, A dwelling electrical service must be protected by a Type 1 or Type 2 surge
protective device.
NEC 230.85, Each dwelling shall have an outdoor readily accessible emergency disconnect
installed. The emergency disconnect could be a service disconnect for the dwelling or it could
be a disconnect supplied by the serving utility. If the disconnect is the service disconnect, it
must be labeled as the "EMERGENCY DISCONNECT- SERVICE DISCONNECT". If the disconnect is
provided by the serving utility, and is not the service disconnect, the disconnect must be
labeled "EMERGENCY DISCONNECT- NOT SERVICE EQUIPMENT".
Inspected By: Donald Edel Email: don.edel.inspections®gmail.com
Phone: (507) 210-8233 Date: 7/28/2021
443 Lafayette Road N., St. Paul, MN 55155 (651) 284-5005 www.dli.mn.gov
rrilDEPARTMENT OF 443 Lafayette Road N.,St. Paul,MN 55155
LABOR AND INDUSTRY (651)284-5026,www.dli.mn.gov
Electrical Permit
Permit Number: ELE2105-09334
Permit Information as of 05/25/21
Structure Type:One-Family Dwelling I Existing Dwelling or Other Items Permit Status: Issued
Site County: Washington County Issued Date: 05/25/21
Site Address: 14250 55th St N, Oak Park Heights, MN 55082 Expiration Date: 05/25/22
Site Contact: SUNSHINE ELECTRIC Phone: Fees Paid:$136.00
Permit Applicant Information
SUNSHINE ELECTRIC LLC Phone: (612)221-3896
SUNSHINE ELECTRIC LLC Mobile: (651)442-1147
PO BOX 17348, MINNEAPOLIS, MN 55417 Email: sunshine.elect@gmail.com
Property Owner's Information
SCOTT ANDERSON Phone: (651)442-1147
SCOTT ANDERSON Mobile: (612) 221-3896
14250 55TH ST N, STILLWATER, MN55082 Email: sunshine.elect®gmaiLcom
Contracted Electrical Inspector's Information
Name:Donald Edel Phone: (507) 210-8233
Don Edel Inspections LLC Email Addres: mailto: don.edel.inspections@gmail.com
Project Information
Electrical Utility: Xcel Energy, Inc. Phone: Email: bclmn@xcelenergy.com
Rough-In Inspection Required: No Number of Inspections Requested: 1
Project Description: PANEL REPLACEMENT
PANEL REPLACEMENT
A rough-in inspection is required before any wiring is concealed by insulation, wall covering, ceiling cover, trench
backfill, etc. If wiring is concealed before inspection, the person responsible for concealing the wiring must cover the
cost associated with uncovering and replacing the covering material.
The installer must notify the inspector for final inspection when the wiring is complete and before the wiring is utilized
and the space is occupied.
Print Date: 05/25/2021
mlDEPARTMENT OF 443 Lafayette Road N.,St. Paul,MN 55155
LABOR AND INDUSTRY (651)284-5026,www.dli.mn.gov
Electrical Permit
Permit Number: ELE2111-01199
Permit Information as of 11/03/21
Structure Type: One-Family Dwelling I Existing Dwelling or Other Items Permit Status: Issued
Site County: Washington County Issued Date: 11/03/21
Site Address: 14250 55th St N, Oak Park Heights, MN 55082 Expiration Date: 11/03/22
Fees Paid: $36.00
Job Reference: AND2103
Permit Applicant Information
MERCURY ELECTRIC CORPORATION Phone: (651)464-1660
MERCURY ELECTRIC CORPORATION Mobile: (651)464-1660
10 N OAKS RD, VADNAIS HEIGHTS, MN 55127 Email: mercuryelectricmn@gmail.com
Property Owners Information
Scott Anderson Phone: (651)442-1147
14250 55th St. N., Stillwater, MN 55082
Contracted Electrical Inspectors Information
Name:Donald Edel Phone: (507) 210-8233
Don Edel Inspections LIC Email Address: mailto:
don.edel.inspections@gmail.com
Project Information
Electrical Utility: Xcel Energy, Inc. Phone: Email: bctmn@xcelenergy.com
Rough-In Inspection Required: No Number of Inspections Requested: 1
Project Description: replace meter
Replace meter
A rough-in inspection is required before any wiring is concealed by insulation, wall covering, ceiling cover, trench
backfill, etc. If wiring is concealed before inspection, the person responsible for concealing the wiring must cover the
cost associated with uncovering and replacing the covering material.
The installer must notify the inspector for final inspection when the wiring is complete and before the wiring is utilized
and the space is occupied.
Print Date: 11/03/2021
M1DEPARTMENT
ABORAND INDUSTRY 67,2 ax IFS
,,
Inspection Report ° F
Project Name: replace meter Permit Number: ELE2111-01199
Project location/address: 14250 55th St N, Oak Park Heights, Washington County, MN, 55082
Applicant: MERCURY ELECTRIC CORPORATION Phone: (651) 464-1660
Owner: Scott Anderson Phone: (651) 442-1147
Inspection Type: Final Result: Pass
Inspector Report
replace meter and add 200 amp disconnect / basement receptacles and plates (final)
Inspected By: Donald Edel Email: don.edel.inspections@gmail.com
Phone: (507) 210-8233 Date: 11/12/2021