Report of Inspection/Test
1 wet 1 dry #
* ESCAPE FIRE
March 2, 2023 `
auxPROTECTION
Property 4i' 3000 Centerville Rd
Americinn Oak Park Heights
r �'`' 6Little 51-771$874 MN 55117
lUa5
1305 60th St N Conducted by: Luke Heikkila
Oak Park Heights, MN 55082
Inspection Ref: 36858
Gabrielle Justus
(651)287-1047 Print Date: 3/3/2023
Signatures
Inspector-Printed Inspector-Signature Date Completed I state that the information on this form is correct at the
time and place of my inspection,and all equipment
Luke Heikkila 3/2/23 tested at this time was left in operational condition upon
completion of this inspection except as noted.
Owner-Printed Owner-Signature Date Completed I acknowledge this report has been reviewed with me.
ROShnI Patel Except as noted,there have been no changes to the
3/2/23 original approved system.
System Off 11:30 Monitoring Company Monitoring Company Operator Alarm Panel/Code
System On 02:00 SK Honeywell FCI
1800-2244
Central Station Test
Yes Alarm,Trouble and Supervisory indication tested and
verified with the central station?
Owner Information
Yes Is the building occupied? Yes Has the occupancy classification and hazard of
contents remained the same since the last inspection 2
Yes Are all fire protection systems in service? Yes Has the system remained in service without
modification since the last inspection?
Yes Was the system free of actuations of devices or alarms
since the last inspection?
Water Based System
Yes Gauges on wet pipe system in good condition and Yes Alarm devices free from physical damage?
showing normal water supply pressure?
Yes Hydraulic nameplate,if provided,securely attached to Yes Valve supervisory switches indicate movement?
riser and legible?
Fire Department Connection
Yes Visible and accessible? Yes Couplings and swivels not damaged and rotate
smoothly?
Yes Plugs or caps in place and undamaged? Yes Gaskets in place and in good condition?
Yes Identification sign(s)in place? Yes Check valve is not leaking?
Yes Automatic drain valve in place and operating properly? NA Interior free of obstructions(if caps are not in place)?
NA Valve clapper operational over its full range(if caps are
not in place)?
Pipe
Yes In good condition? Yes Free of mechanical damage and not leaking?
Yes No external corrosion? Yes Properly aligned 2
Yes No external loads? Yes Visible pipe hangers and seismic braces not damaged
or loose?
Yes Was an obstruction investigation conducted and the
system flushed?
Print Date: 3/3/2023 Page 1 of 4
Copyright 2002-2016 Life Safety Inspector,OnSite Software
Report of Inspection/Testi ti,
ry .
Annual 1 wet 1 dry ESCAPE FIRE
i� _,a PROTECTION
March 2, 2023 \\*.:;':tire.
h k Garuda.MN 5511]
Property: Americinn Oak Park Heights651,x,-ear.
Inspection Ref: 36858
Sprinklers
Yes Sprinkler wrench with spare sprinklers? Yes Proper number and type of spare sprinklers?
Yes Free of corrosion? Yes Free of obstructions to spray patterns?
Yes Free of foreign materials including paint? Yes Free of physical damage?
Yes Are all sprinklers in service dated 1920 or later? Yes Fast Response sprinklers in service for less than 20
years?If"no"test sample now and every 10 years.
Yes Standard sprinklers less than 50 years old? If no test Yes If sprinklers have been replaced,were they proper
sample now and every 10 years. replacements?
NA Sprinklers and spray nozzles protecting commercial
cooking equipment and ventilating systems replaced
except for bulb-type which show no signs of grease
buildup?
Cold Weather Check
Yes Adequate heat in areas with wet piping? Yes Interior of pipe in preaction and dry pipe systems which
passes through freezers free of ice blockage?
Yes Auxiliary drains drained in dry pipe,preaction and
deluge systems prior to the onset of freezing weather?
Dry Valve
Yes Enclosures around dry-pipe,preaction or deluge valves Yes Gauges on dry,preaction and deluge systems in good
maintaining a minimum of 40 deg F'? condition and showing normal air and water pressure?
Yes Free from physical damage? Yes Trim valves in appropriate(open or closed)position?
Yes No leakage from intermediate chamber? Yes Interior of dry pipe,preaction and deluge valves passed
internal inspection(required every 5th year if resetable
without opening)?
Yes Priming water level correct? Yes Low air pressure signal passed test?
Yes Quick opening devices passed test? Yes Automatic air maintenance devices on dry pipe and
preaction systems passed test?
Yes Dry pipe systems being maintained in dry condition? Yes Interior of dry pipe,preaction and deluge valves
cleaned?
Valve Interior Inspection 5 Year Inspection
NA Alarm valves and their associated strainers,filters and No Check valves internally inspected and all parts operate
restriction orifices passed internal inspection? properly,move freely and are in good condition?
NA Strainers,filters,restricted orifices and diaphragm No Gauges checked against calibrated gauge or replaced
chambers on dry pipe,preaction and deluge valves ?
passed internal inspection?
Air Compressor Inspection
Master Force Manufacturer of compressor Model of compressor
Size of compressor(HP) Compressor Description/Type
Yes Compressor appears to be in working condition? Yes Compressor appears free of leaks?
Yes Compressor and motor are free of vibration and Yes Guages appear Ok and show normal PSI
unusual noies?
Yes Oil appears clean with no burnt odor Yes Electrical connections Ok?
Yes Inlet air filter clean? Yes Breaker in the ON Postion?
Yes Belt is in good condition? Yes Tension on the belt is Ok?
Yes Has condensate/water been drained from the tank NA Dryer/Separator Ok?
and/or water separator?
Flow Test
Outlet Pressure(psi) Waterflow Results
System Connection Flowed Alarms Actuate devices pass comparable to
Size
Static Resid Static test prior test
MECH RM Main drain 2 63 55 63 NA NA Yes
Print Date: 3/3/2023 Page 2 of 4
Copyright 2002-2016 Life Safety Inspector,OnSite Software
Report of Inspection/Test A'' �fk
` '�' ESCAPE FIRE
Annual 1 wet 1 dry �� PROTECTION
March 2, 2023 ;'?....4,,,,
!!�� 6000 Cenlende Rd
V'r' � le Canada MN 55117
Property: Americinn Oak Park Heights \\ 651„18974
Inspection Ref: 36858
Flow Test
Outlet Pressure(psi) Waterflow Results
System Connection Flowed Alarms Actuate devices pass comparable to
Size test prior test
Static Resid Static
ITV 1/2 Yes Yes Yes
Flow Time-66 sec
Auxiliary Drains
System/Location Drain Aux Drain Drained? Water Flow Observed .
Yes
Valve Inspection List
a
TO
Location/Description Qty Valve Type SizeSecured Q .N N 2
0 w (7)' inn
Q w -../
Control Valve Chart/lnsp/Maint 1 Butterfly4 Supervised Yes Yes Yes Yes
Control Valve Chart/Insp/Maint 1 OS&Y 4 Supervised Yes Yes Yes Yes Yes
Dry Valve Trip Test-
Dry Valve Size: 4 Year Q. 0D. No QOD Year.
Make Model Serial no. Make Model Serial no.
Central AG
Time to Trip thru water Pressure Air Pressure Trip point Time water reached Alarm Operated
test pipe air pressure test outlet
No Q.O.D. sec 63 psi 42 psi 1 1 psi sec
Comparable to previous tests?
Low Air-20
Print Date: 3/3/2023 Page 3 of 4
Copyright 2002-2016 Life Safety Inspector,OnSite Software
Report of Inspection/Test , 4 ,
Annual 1 wet 1 dry __ ` ESCAPE FIRE
March 2, 2023 ,, PROTECTION
Property: Americinn Oak Park Heights °r� `='� 651.771""`°'88°'A"'"'
Canada
8874
Inspection Ref: 36858
Deficiency / Recommendations Summary
These items were deficient and do not meet the requirements of the applicable code at the time of the inspection. Items marked
Recommendation are not required by the applicable code but are opportunities to improve the Life Safety of the property.
Valve Interior Inspection 5 Year Inspection
N Check valves internally inspected and all parts operate properly,move freely and are in
good condition?
NFPA-25-2002 12.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate properly,move freely,and
are in good condition.
N Gauges checked against calibrated gauge or replaced?
NFPA-25-2002 12.2.8.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge.Gauges not
accurate to within 3 percent of the full scale shall be recalibrated or replaced.
Print Date: 3/3/2023 Page 4 of 4