Report Cover Page
SERVICE DATE:4/20/2023 SERVICE TICKET:ST00276201
BUILDING STREET CITY STATE ZIP
Xcel Substation--alien Kin0 5701 N St Croix Trail Oak Park MN 56357
BUILDING CONTACT PHONE
Xx 9528874547
Please see the attached reports. If there are any questions, please reach out to the
above office.
Download your Report at:
https://customer.nardinifire.com
Signed 4/20/2023 Signed 4/20/2023
Inspector: Scott Bazille Building Contact: Xx
Title:
Date : 4/20/2023
Frequency: Annual
Nardini
-A company of
PY - Service Ticket No. : ST00276201
rA E•BARKE
FIRE Ec FIRE R& 8 A F E T Y Inspection Contract No. : 0001429023
PO No. : P0508056
Equipment Location : Generator
Suppression Chemical Inspection Report
Property : Xcel Substation--allen King Owner : Ziegler Power Systems
Address : 5701 N St Croix Trail Address : 8050 County Road 101 E.
City : Oak Park City : Shakopee
State : MN State : MN
Zip : 56357 Zip : 55379
Phone : 9528874575 Phone : 9528874547
MONITORING & NOTIFICATION
On/off Premises Monitoring
Monitoring Agency Phone# Jason put on test
Account Number NA
Account Password NA
**Alarm Signal - Received? Pass
**Alarm Restore- Received? Pass
**Trouble Signal - Received? Pass
**Trouble Restored- Received? Pass
**Supervisory Signal- Received? N/A
**Supervisory Restore- Received? N/A
Notifications Of Testing Completion
Building Management Notified? Yes
Monitoring Agency Notified? Yes
**Panel Condition Normal On Departure? Yes
HAZARD DETAIL
Type of System Dry Chemical
If scale was used, enter last calibration date N/A
If gauge was used, enter last calibration date N/A
**Are record drawings available? Yes
**Are flow calculations available? Yes
**Sequence of Operation is posted? N/A
**Proper warning signs in place? Yes
•405 County Road E W•Saint Paul MN•55126
Suppression Inspection Page 2 of 7
Service Ticket No. :ST00276201
**Any changes to hazard since system was installed? No
**Any changes to hazard since last inspection? No
**Piping is properly supported? Yes
**Is piping proper type for the system? Yes
**Are the fittings the proper type for the system? Yes
**Nozzle(s) are properly oriented? Yes
**Nozzle(s) are properly supported? Yes
**Agent container(s)are properly supported? Yes
**Discharge hose(s)are in good condition? N/A
Date on discharge hoses N/A
**Pilot hose(s)are in good condition? N/A
Date on pilot hoses N/A
**Did all initiating devices function? Yes
**Did all manual releasing devices function? Yes
**Did all maintenance switches function? Yes
**Did all abort stations function? N/A
**Did all release devices function? Yes
**Did all notification devices function? Yes
PANEL INFORMATION
Information
Type of transmission Relay
Circuit Class Class B
**Circuits are properly supervised? Yes
Detection Setup Single Zone
Method of Actuation Electric
Type of releasing device Pyrochem
Date of releasing device (if applicable) N/A
Panel Information
Panel Manufacturer Ansul
Panel Model AutoPulse Z10
Is this the primary panel? No
Over current protection type Circuit Breaker
Over current size (amps) 15
Breaker location Left of transfer switch
Breaker number 13
•
**Dedicated circuit? Yes
**Breaker marked? Yes
Battery#1
Type Sealed Lead-Acid
Rated volts 12
Rated amp hour 7
•405 County Road E W•Saint Paul MN•55126
Suppression Inspection Page 3 of 7
Service Ticket No. :ST00276201
Manufacture Date 04/2022
**Leaks or corrosion? Pass
**Connections tight? Pass
**Did battery pass? Yes
**Was battery replaced? No
Battery#2
Type Sealed Lead-Acid
Rated volts 12
Rated amp hour 7
Manufacture date 04/2022
**Leaks or corrosion? Pass
**Connections tight? Pass
**Did battery pass? Yes
**Was battery replaced? No
**Was battery size confirmed with drawings? Yes
System Function Summary&Test
**Alarm Bells/Horns/Strobe evacuation alarms function properly? Yes
**Loss of AC power is detected by the panel? Yes
**Loss of secondary power is detected by the panel? Yes
**Electrical opens in indicating circuits are detected? Yes
**Electrical shorts in indicating circuits are detected? Yes
**Panel was in good operational condition upon arrival? Yes
"**Panel and surrounding equipment, conduit and wiring well secured and in good Yes
condition?"
**Are all troubleshooting LEDs operating correctly? Yes
**Primary power supply operates properly under full load? Yes
**Transient Suppressors visually inspected? N/A
**Have all fuses been checked for rating and supervision? N/A
**Are wires labeled and identified? N/A
System Test&Inspection
Control Panel Visual and Functional
Interface Equipment Visual and Functional
Lamps/LEDs Visual and Functional
Primary Power Supply Visual and Functional
Trouble Signals Visual and Functional
Ground Fault Monitoring Visual and Functional
Ancillary Devices
Power Shutdown Present
SEQUENCE OF OPERATIONS
First Alarm
Building Activation Alarm
•405 County Road E W•Saint Paul MN•55126
Suppression Inspection Page 4 of 7
Service Ticket No. :ST00276201
First Initiating device(s) Heat Detector
Notification Horn/Storbe
Second Notification Horn/Strobe
Time Delay No time delay
Ancillary device shutdown Pass
Second Alarm
Building Activation N/A
Second Initiating device(s) NA
Notification N/A
Second Notification N/A
Time Delay N/A
Ancillary device shutdown NA
Panel Piezo with LEDs
Release Device
Location Below FACP
Zone or Address 0
***Pass/Fail Pass
Manual Release
Building Activation Alarm
Notification Horn/Strobe
Second Notification Horn/Strobe
Time Delay No Time Delay
Ancillary device shutdown NA
Panel Piezo with LEDs
Discharge Alarm
Building Activation Alarm
Notification Horn/Strobe
Second Notification Horn/Strobe
Panel Piezo with LEDs
Ancillary device shutdown Pass
Abort
Are abort device(s) present? N/A
Abort Type N/A
ENCLOSURE INSPECTION
**Does enclosure integrity apply? Yes
•
**Visual condition appears to be okay? Yes
**Proper door sweeps present? Yes
**Proper seals on door jambs present? Yes
**Proper astragal around double doors? N/A
**Proper seal around windows? N/A
**Wall partitions extend from floor slab to roof? N/A
•405 County Road E W•Saint Paul MN•55126
Suppression Inspection Page 5 of 7
Service Ticket No. :ST00276201
"Holes, cracks, or other openings in walls? N/A
**Bottom of walls at floor properly sealed? N/A
**If walls are porous, are they properly sealed? N/A
**If dampers present, 100% air shutoff? Yes
**Floor drains have proper liquid? N/A
**Raceways appear to be properly sealed? Yes
TANKS/CYLINDERS
Location Below Facp
Manufacturer PyroChem
Model # ABC Drychem
Tank/Cylinder Manufactured Date 07/20/2018
Tank/Cylinder Type Steel
Tank/Cylinder Size NA
Tank/Cylinder Serial Number ATM736254
Agent Weight 35
Gross Weight 0
Fill Weight 35
Measured Weight 0
Gauge Pressure ( PSIG ) 350
Date Of Last Recharge 07/20/2018
**Did Tank/Cylinder Pass Inspection yes
DEVICE INSPECTION REPORT
Total Inspected:5 Total Failed:0 Total Passed:5
Device Location Zone or Type Make Model Sensitivity Range Sensitivity Pass/ Comments
Address Alarm Point Fail
Above Generator Heat Detector Pass
Engine
Below Facp Manual Pull Station Pass
Below Facp Maintenance Switch NA NA Pass
Maintenance Bypass
Exterior Of Enclosure-1 Horn/Strobe Pass
Exterior Of Enclosure-2 Horn/Strobe Pass
•405 County Road E W•Saint Paul MN•55126
Suppression Inspection Page 6 of 7
Service Ticket No. :ST00276201
SIGNATURE
This report was reviewed with: Nardini Fire Equipment
Print Name : Xx Technician
Scott Bazille
Signature • Signature :
Date : 4/20/2023 Date : 4/20/2023