2018-10-25 Nardini Fire Inspection Report - Xcel Substation 5701 St. Croix Trail N
r4ar ni FIPF EQUIPMiENT www.nardinifire.com/sales@nardinifire.com St.Paul,MN ENGINEERED SYSTEM INSPECTION AND TESTING REPORT Work Site#: 24708 Service Order#: ST00099438 Name of Facility: XCEL SUBSTATION--ALLEN KING Installation/Service Report Date: 10/25/2018 j G 1 W` ^IMA t I Time In: 1300 PM® Time Out. 1430 PM Street: 5701 N ST CROIX TRAIL � `�l1 1V LI PM PM ID City: OAK PARK State--MN Zip: 56357 Last Maintenance Date: 2018-04-25 Installation ❑ Quarterly ❑ Authorized Contact: WEIBEL,HAROLD Last Maintained By: Nardini Fire Semi-Annualx❑ Phone: 9528874575 Annual ❑ Suppression Type Panel Type Manufacturer of System: Ansul Manufacturer: Ansul Revision: Type of Agent: ABC Dry Chem Model: AutoPulse 1000 Intelligent 0 Conventional El Chip#: System Location: Generator Enclosure Electrical Disconnect Location: CKT#13 Hazard Description: Generator Enclosure Manual Release Operable? Yes IN No 0 Qty: ( 1 ) Alarms Operable? Yes ❑x No gi Abort Operable? Yes ❑ No ❑ Qty: ( 0 ) Lockout Valve? Yes ❑ No 0 N/A ❑x Bypass Switch Operable? Yes 0 No 0 Qty: ( 0 ) Odorizer? Yes ❑ No ❑ N/A x❑ Actuator Operable? Yes ® No 0 Date: Type: Ansul PN 73327 Time Delay? Yes ❑ No ❑ N/A Auto Detection Operable? Ye s® No ❑ Discharge Hose Date: Detection Type: Ion( ) Photo( ) Heat( 1 )Temps: Optical( ) Aspirating( ) Other( ) Notification Type: Bells( ) Horns( ) Horn/Strobes( 1 ) Strobes( ) Other( ) Model: Wheelock Auxiliary Functions Relay Press Low High Tested . Batteries Switch Volt Volt Shutdown Equipment .3 0 0 0 igi Size Qty. Date(s) Shutdown Ventilation ® 0 0 0 ® 12v 5ah 2 3-2016 Shutdown Dampers _+. 0 0 ❑ ea Building/Local Alarm Tie-In ® 0 0 0 Panel Transfer to Battery?Yes® No 0 Load Test: Good Charger Test: Good Type of Release: Single Zone( x ) Cross Zoned( ) Counting Zone( ) Other( ) Discharge Delay- 30 Seconds Pneumatic/Electric Sequence of Operations: 1"Alarm- 14/S 2nd Alarm- Discharge- H/S Abort Delay- N/A Seconds ELECTRIC Perimeter Doors Sealed Yes® No❑ Ceiling Tiles Clipped Yes 0 No 0 N/A IN Warning Signs Yes❑ No® Hazard Changes Yes 0 No r': N/A 0 Checked Hazards for Leaks Yes® No 0 Nozzles Cl.(8"dia.) Yes® No 0 N/A 0 Is actuator on cylinder and strapped? Yes® No 0 Serial# 9538 Comments: System tagged good.Tank needs hydro testing and no warning signs on doors.Horn Strobe outside only horn function is working. Pfeifer,Z Nardini Fire Technician(s) Customer/Authorized Agent—Printed Name Customer/Authorized Agent-Signature 1 rooN ar ini FIRE EQUI ivL , www.nardinifire.com/sales@nardinifire.com Aspirating Smoke Detection FILTER TRANSPORT NAME MFG MODEL DATE AMBIENT% ACTION ALERT ALARM I ALARM 2 TIME 2 Nardini FIRE EQUIPMENT www.nardinifire.com/salesnanardinifire.com Tanks SERIAL NUMBER FILL WT. GROSS WT. ACT.WT./LL TEST DATE PSIG VALVE MODEL 1. ATM71894 50 6-2006 365 Ansul 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. 34. 35. 36. 37. 38. 39. 40. 41. 42. 43. 44. 45. 46. 47. 48. 49. 50. 51. 52. 53. 54. 3