HomeMy WebLinkAbout2016-10-20 Armor Scurity Inspection and Testing Form ARMOR SECURITY INSPECTION AND TESTING FORM
ARP DATE: 10/20/2016
TIME: 9:30:00 AM
VIDEO • ACCESS FIRE • SECURITY INITIAL ANNUAL (circle one)
SERVICE ORGANIZATION PROPERTY NAME(USER)
Name Armor Security, Inc. Name: Joseph's Family Restaurant
Address: 2601 Stevens Ave S,Minneapolis, MN 55408 Address: 14608 North 60th Street,Oak Park Heights,MN 55082
Kristen Schuelke Owner
Representative: Contact: Joseph Kohler
License No: TS00070 Telephone:
(651)439-3336
(612) 870-4142 Panel
Telephone: Pri/Sec (651)439-4258 (651)439-3336
Transmission Type Digital MONITORING ENTITY APPROVING AGENCY
Testing Frequency Annually Contact: Curtis Pierre Oak Park Heights FM
RECOMMENDATIONS/COMMENTS: Phone: 877-536-0371 (651)402-0789
Signaling Line Circuits
Qty 0
Style(s) 0
Control Unit Manufacturer/Model: Bosch 2071
Control Styles Number of Circuits: 3
Software Rev: N/A FC/Account Number Non-UL
Last Service Performed: Last Software Change
ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION
Quantity Circuit Style
0 N/A Manual Fire Alarm Boxes
0 N/A Ion Detectors
0 N/A Photo Detectors
0 N/A Duct Detectors
0 N/A Heat Detectors
1 A Waterfow Switches
0 N/A Photobeams
0 N/A Fire Panel Alarm
ALARM NOTIFICATION APPLICANCES AND CIRCUIT INFORMATION
Quantity Circuit Style
0 N/A Bells
0 N/A Horns
0 N/A Chimes
0 N/A Strobes
0 N/A Speakers
0 N/A Horn/Strobe
Number of alarm notification appliance circuits: 0
Are circuits monitored for integrity? X Yes ❑ No
SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION
Quantity Circuit Style
1 B Low Temp(NON-UL)
3 B Supervisory Switches
0 N/A Fire Pump Power
0 N/A Fire Pump Running
0 N/A Fire Pump Phase Reversal
0 N/A Generator or Controller Trouble
0 N/A Generator Engine Running
0 N/A Fire Panel Trouble
0 N/A Magnetic Lock Supervision Relay
ARMOR SECURITY INSPECTION AND TESTING FORM (PAGE 1)
ARMOR SECURITY INSPECTION AND TESTING FORM (PAGE 2)
SYSTEM POWER SUPPLIES
(a)Primary(Main): Nominal Voltage 120 Amps 1.5
Overcurrent Protection: Type Breaker Amps 10
Location(of Primary Supply Panelboard) Main A
Disconnecting Means Location: Main A#26
(b)Secondary(Standby): BATTERY Storage Battery:Amp-Hr Rating 7
Calculated capacity to operate system,in hours: x 24 60
Engine-driven generator dedicated to fire alarm system: None
Location of fuel storage: None
BATTERY TYPE :Sealed Lead-Acid
(c)Emergency or standby system used as a backup to primary power supply,instead of using a secondary power supply:
None
PRIOR TO ANY TESTING
NOTIFICATIONS ARE MADE Yes No Who Time
Monitoring Entity X O Criticom Intl
Building Occupants X O OK
Building Management X O OK
Other(Specify) O O
AHJ Notified of Any Impairments O O
SYSTEM TESTS AND INSPECTIONS
Type Visual Functional Comments
Control Unit X X OK
Interface Equipment X O
Lamps/LEDS X O
Fuses X O
Primary Power Supply X O
Trouble Signals X X OK
Disconnect Switches X O
Ground-Fault Monitoring X X OK
TYPE Visual Functional Comments
Battery Condition X X OK
Load Voltage X X OK
Discharge Test X X OK
Charger Test X X OK
Transient Suppressors O O
Remote Annunciators O O
NOTIFICATION APPLIANCES
Audible X X OK
Visible X X OK
Speakers O O
Voice Clarity O O
EMERGENCY COMMUNICATIONS EQUIPMENT Visual Functional Comments
Phone Set X X OK
Phone Jacks O O
Off-Hook Indicator O O
Amplifier(s) O O
Tone Generator(s) 0 O
Call-in Signal 0 O
System Performance X X OK
NOTIFICATIONS TESTING IS COMPLETE Yes No Who Time
Building Management X O
Monitoring Agency X 0 OK 10:34:04
Building Occupants X O
The following did not operate correctly/recommendations:
System restored to normal operation: Date: 10/20/2016 Time: 10:40:00 AM
THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.
Name of Inspector: KB BALLA Date: 10/20/16 Time: 10:34:04
Insp.Signature:
Name of Owner or
Representative: JOE KOHLER
Owner Signature: AVAILABLE UPON REQUEST Date: Time: