Loading...
HomeMy WebLinkAbout2023-11-01 Nardini Fire - Suppression Chemical Inspection Report -A Compa�yot- Nardini PrE•BARKER Nardini Fire Equipment i, 1/ 405 County Road E W 4 `� ' �� "'"� 1 p �� Saint Paul MN 55126 (651)483-6631 Report Cover Page SERVICE DATE:11/1/2023 SERVICE TICKET:ST00303566 BUILDING STREET CITY STATE ZIP Xcel Substation--allen King 5701 N St Croix Trail Oak Park MN 56357 BUILDING CONTACT PHONE Xx 9528874547 System Status: Pass Tag Color: Blue Please see the attached reports. If there are any questions, please reach out to the above office. Download your Report at: https://customer.nardinifire.com Signed 11/1/2023 Signed 11/1/2023 Inspector: Scott Bazille Building Contact: Xx Title: Date: 11/1/2023 -A Company of- Frequency: Annual Nardini PYE•BARKER Service Ticket No. : ST00303566 FIRE & SAFETY Inspection Contract No. 0001429023 PO No. : Equipment Location : Generator Suppression Chemical Inspection Report Property : Xcel Substation--allen King Owner : Ziegler Power Systems Address : 5701 N St Croix Trail Address : 8050 County Road 101 E. City : Oak Park City : Shakopee State : MN State : MN Zip : 56357 Zip : 55379 Phone : 9528874575 Phone : 9528874547 MONITORING & NOTIFICATION On/off Premises Monitoring Monitoring Agency Phone# 0 Account Number Customer put on test Account Password NA **Alarm Signal - Received? N/A **Alarm Restore- Received? N/A **Trouble Signal - Received? N/A **Trouble Restored- Received? N/A **Supervisory Signal - Received? N/A **Supervisory Restore- Received? N/A Notifications Of Testing Completion Building Management Notified? Yes **Fire Alarm Panel Condition Normal On Departure? Yes HAZARD DETAIL Type of System Dry Chemical If scale was used, enter last calibration date N/A If gauge was used, enter last calibration date N/A **Are record drawings available? N/A **Are flow calculations available? N/A **Sequence of Operation is posted? N/A **Proper warning signs in place? Yes **Any changes to hazard since system was installed? No •405 County Road E W•Saint Paul MN•55126 Suppression Inspection Page 2 of 7 Service Ticket No. :ST00303566 **Any changes to hazard since last inspection? No **Piping is properly supported? Yes **Is piping proper type for the system? Yes **Are the fittings the proper type for the system? Yes 'Nozzle(s)are properly oriented? Yes 'Nozzle(s) are properly supported? Yes **Agent container(s) are properly supported? Yes **Discharge hose(s)are in good condition? N/A Date on discharge hoses N/A **Pilot hose(s)are in good condition? N/A Date on pilot hoses N/A **Did all initiating devices function? Yes **Did all manual releasing devices function? Yes **Did all maintenance switches function? Yes **Did all abort stations function? N/A **Did all release devices function? Yes **Did all notification devices function? Yes PANEL INFORMATION Information Type of transmission Relay Circuit Class Class B **Circuits are properly supervised? Yes Detection Setup Single Zone Method of Actuation Electric Type of releasing device Pyrochem Date of releasing device (if applicable) N/A Panel Information Panel Manufacturer Ansul Panel Model AutoPulse Z10 Is this the primary panel? Yes Over current protection type Circuit Breaker Over current size (amps) 15 Breaker location Left of transfer switch Breaker number 13 **Dedicated circuit? Yes **Breaker marked? Yes Battery#1 Type _ Sealed Lead-Acid Rated volts 12 Rated amp hour 7 Manufacture Date 04/2022 •405 County Road E W•Saint Paul MN•55126 Suppression Inspection Page 3 of 7 Service Ticket No. :ST00303566 **Leaks or corrosion? Visual Only **Connections tight? Pass **Did battery pass? Yes **Was battery replaced? No Battery#2 Type Sealed Lead-Acid Rated volts 12 Rated amp hour 7 Manufacture date 04/2022 **Leaks or corrosion? Visual Only **Connections tight? Pass **Did battery pass? Yes **Was battery replaced? No **Was battery size confirmed with drawings? Yes System Function Summary&Test **Alarm Bells/Horns/Strobe evacuation alarms function properly? Yes **Loss of AC power is detected by the panel? Yes **Loss of secondary power is detected by the panel? Yes **Electrical opens in indicating circuits are detected? Yes **Electrical shorts in indicating circuits are detected? Yes **Panel was in good operational condition upon arrival? Yes "**Panel and surrounding equipment, conduit and wiring well secured and in good Yes condition?" **Are all troubleshooting LEDs operating correctly? Yes **Primary power supply operates properly under full load? Yes **Transient Suppressors visually inspected? N/A **Have all fuses been checked for rating and supervision? N/A **Are wires labeled and identified? N/A System Test&Inspection Control Panel Visual and Functional Interface Equipment Visual and Functional Lamps/LEDs Visual and Functional Primary Power Supply Visual and Functional Trouble Signals Visual and Functional SEQUENCE OF OPERATIONS First Alarm Building Activation Alarm First Initiating device(s) Heat Detector Notification Horn/Strobe outside area/room Second Notification Horn/Strobe outside area/room •405 County Road E W•Saint Paul MN•55126 Suppression Inspection Page 4 of 7 Service Ticket No. :ST00303566 Time Delay No time delay Ancillary device shutdown Pass Second Alarm Building Activation N/A Second Initiating device(s) NA Notification N/A Second Notification N/A Time Delay N/A Ancillary device shutdown NA Panel Piezo with LEDs Release Device Location Below FACP Zone or Address Release ***Pass/Fail Pass Manual Release Building Activation Alarm Notification Horn/Strobe outside area/room Second Notification Horn/Strobe outside area/room Time Delay No Time Delay Ancillary device shutdown Pass Panel Piezo with LEDs Discharge Alarm Building Activation Alarm Notification Horn/Strobe outside area/room Second Notification Horn/Strobe outside area/room Panel Piezo with LEDs and code number on panel Ancillary device shutdown Pass Abort Are abort device(s) present? N/A Abort Type N/A ENCLOSURE INSPECTION **Does enclosure integrity apply? Yes **Visual condition appears to be okay? Yes **Proper door sweeps present? N/A **Proper seals on door jambs present? N/A **Proper astragal around double doors? N/A **Proper seal around windows? N/A **Wall partitions extend from floor slab to roof? N/A •405 County Road E W•Saint Paul MN•55126 Suppression Inspection Page 5 of 7 Service Ticket No. :ST00303566 **Holes, cracks, or other openings in walls? N/A **Bottom of walls at floor properly sealed? N/A **If walls are porous, are they properly sealed? N/A **If dampers present, 100% air shutoff? Yes **Floor drains have proper liquid? N/A **Raceways appear to be properly sealed? Yes TANKS/CYLINDERS Location Below Facp Manufacturer PyroChem Model # ABC Drychem Manufactured Date 07/2018 Type Steel Size NA Serial Number ATM736254 Agent Weight 35 Gross Weight 0 Fill Weight 35 Measured Weight 0 Gauge Pressure ( PSIG ) 340 Date Of Last Recharge 07/2018 Date Of Last 5-Year Inspection N/A Date of Last 5-Year Agent/Fluid Swap N/A Date Of Last 6-Year Hydrostatic Test N/A Date Of Last 12-Year Hydrostatic Test N/A Measuring Device Used N/A **Did Tank/Cylinder Pass Inspection yes DEVICE INSPECTION REPORT Total Inspected:6 Total Failed:0 Total Passed:6 Device Location Zone or Type Make Model Sensitivity Sensitivity Pass/ Comments Address Range Alarm Point Fail Above Generator Engine Heat Detector Pass Below Facp Manual Pull Station Pass Below Facp Maintenance Switch NA NA Pass Maintenance Bypass Exterior Of Enclosure-1 Horn/Strobe Pass Exterior Of Horn/Strobe Pass •405 County Road E W•Saint Paul MN•55126 Suppression Inspection Page 6 of 7 Service Ticket No. :ST00303566 Enclosure-2 Left Of Facp Pressure Pressure Switch Tyco NA Pass Switch SIGNATURE This report was reviewed with: Nardini Fire Equipment Print Name : Xx Technician : Scott Bazille Signature Signature Date : 11/1/2023 Date : 11/1/2023 •405 County Road E W•Saint Paul MN•55126 Suppression Inspection Page 7 of 7