HomeMy WebLinkAbout2023-11-01 Nardini Fire - Suppression Chemical Inspection Report -A Compa�yot-
Nardini PrE•BARKER
Nardini Fire Equipment i, 1/
405 County Road E W 4 `� ' �� "'"� 1 p
��
Saint Paul MN 55126
(651)483-6631
Report Cover Page
SERVICE DATE:11/1/2023 SERVICE TICKET:ST00303566
BUILDING STREET CITY STATE ZIP
Xcel Substation--allen King 5701 N St Croix Trail Oak Park MN 56357
BUILDING CONTACT PHONE
Xx 9528874547
System Status: Pass Tag Color: Blue
Please see the attached reports. If there are any questions, please reach out to the
above office.
Download your Report at:
https://customer.nardinifire.com
Signed 11/1/2023 Signed 11/1/2023
Inspector: Scott Bazille Building Contact: Xx
Title:
Date: 11/1/2023
-A Company of- Frequency: Annual
Nardini PYE•BARKER Service Ticket No. : ST00303566
FIRE & SAFETY Inspection Contract No. 0001429023
PO No. :
Equipment Location : Generator
Suppression Chemical Inspection Report
Property : Xcel Substation--allen King Owner : Ziegler Power Systems
Address : 5701 N St Croix Trail Address : 8050 County Road 101 E.
City : Oak Park City : Shakopee
State : MN State : MN
Zip : 56357 Zip : 55379
Phone : 9528874575 Phone : 9528874547
MONITORING & NOTIFICATION
On/off Premises Monitoring
Monitoring Agency Phone# 0
Account Number Customer put on test
Account Password NA
**Alarm Signal - Received? N/A
**Alarm Restore- Received? N/A
**Trouble Signal - Received? N/A
**Trouble Restored- Received? N/A
**Supervisory Signal - Received? N/A
**Supervisory Restore- Received? N/A
Notifications Of Testing Completion
Building Management Notified? Yes
**Fire Alarm Panel Condition Normal On Departure? Yes
HAZARD DETAIL
Type of System Dry Chemical
If scale was used, enter last calibration date N/A
If gauge was used, enter last calibration date N/A
**Are record drawings available? N/A
**Are flow calculations available? N/A
**Sequence of Operation is posted? N/A
**Proper warning signs in place? Yes
**Any changes to hazard since system was installed? No
•405 County Road E W•Saint Paul MN•55126
Suppression Inspection Page 2 of 7
Service Ticket No. :ST00303566
**Any changes to hazard since last inspection? No
**Piping is properly supported? Yes
**Is piping proper type for the system? Yes
**Are the fittings the proper type for the system? Yes
'Nozzle(s)are properly oriented? Yes
'Nozzle(s) are properly supported? Yes
**Agent container(s) are properly supported? Yes
**Discharge hose(s)are in good condition? N/A
Date on discharge hoses N/A
**Pilot hose(s)are in good condition? N/A
Date on pilot hoses N/A
**Did all initiating devices function? Yes
**Did all manual releasing devices function? Yes
**Did all maintenance switches function? Yes
**Did all abort stations function? N/A
**Did all release devices function? Yes
**Did all notification devices function? Yes
PANEL INFORMATION
Information
Type of transmission Relay
Circuit Class Class B
**Circuits are properly supervised? Yes
Detection Setup Single Zone
Method of Actuation Electric
Type of releasing device Pyrochem
Date of releasing device (if applicable) N/A
Panel Information
Panel Manufacturer Ansul
Panel Model AutoPulse Z10
Is this the primary panel? Yes
Over current protection type Circuit Breaker
Over current size (amps) 15
Breaker location Left of transfer switch
Breaker number 13
**Dedicated circuit? Yes
**Breaker marked? Yes
Battery#1
Type _ Sealed Lead-Acid
Rated volts 12
Rated amp hour 7
Manufacture Date 04/2022
•405 County Road E W•Saint Paul MN•55126
Suppression Inspection Page 3 of 7
Service Ticket No. :ST00303566
**Leaks or corrosion? Visual Only
**Connections tight? Pass
**Did battery pass? Yes
**Was battery replaced? No
Battery#2
Type Sealed Lead-Acid
Rated volts 12
Rated amp hour 7
Manufacture date 04/2022
**Leaks or corrosion? Visual Only
**Connections tight? Pass
**Did battery pass? Yes
**Was battery replaced? No
**Was battery size confirmed with drawings? Yes
System Function Summary&Test
**Alarm Bells/Horns/Strobe evacuation alarms function properly? Yes
**Loss of AC power is detected by the panel? Yes
**Loss of secondary power is detected by the panel? Yes
**Electrical opens in indicating circuits are detected? Yes
**Electrical shorts in indicating circuits are detected? Yes
**Panel was in good operational condition upon arrival? Yes
"**Panel and surrounding equipment, conduit and wiring well secured and in good Yes
condition?"
**Are all troubleshooting LEDs operating correctly? Yes
**Primary power supply operates properly under full load? Yes
**Transient Suppressors visually inspected? N/A
**Have all fuses been checked for rating and supervision? N/A
**Are wires labeled and identified? N/A
System Test&Inspection
Control Panel Visual and Functional
Interface Equipment Visual and Functional
Lamps/LEDs Visual and Functional
Primary Power Supply Visual and Functional
Trouble Signals Visual and Functional
SEQUENCE OF OPERATIONS
First Alarm
Building Activation Alarm
First Initiating device(s) Heat Detector
Notification Horn/Strobe outside area/room
Second Notification Horn/Strobe outside area/room
•405 County Road E W•Saint Paul MN•55126
Suppression Inspection Page 4 of 7
Service Ticket No. :ST00303566
Time Delay No time delay
Ancillary device shutdown Pass
Second Alarm
Building Activation N/A
Second Initiating device(s) NA
Notification N/A
Second Notification N/A
Time Delay N/A
Ancillary device shutdown NA
Panel Piezo with LEDs
Release Device
Location Below FACP
Zone or Address Release
***Pass/Fail Pass
Manual Release
Building Activation Alarm
Notification Horn/Strobe outside area/room
Second Notification Horn/Strobe outside area/room
Time Delay No Time Delay
Ancillary device shutdown Pass
Panel Piezo with LEDs
Discharge Alarm
Building Activation Alarm
Notification Horn/Strobe outside area/room
Second Notification Horn/Strobe outside area/room
Panel Piezo with LEDs and code number
on panel
Ancillary device shutdown Pass
Abort
Are abort device(s) present? N/A
Abort Type N/A
ENCLOSURE INSPECTION
**Does enclosure integrity apply? Yes
**Visual condition appears to be okay? Yes
**Proper door sweeps present? N/A
**Proper seals on door jambs present? N/A
**Proper astragal around double doors? N/A
**Proper seal around windows? N/A
**Wall partitions extend from floor slab to roof? N/A
•405 County Road E W•Saint Paul MN•55126
Suppression Inspection Page 5 of 7
Service Ticket No. :ST00303566
**Holes, cracks, or other openings in walls? N/A
**Bottom of walls at floor properly sealed? N/A
**If walls are porous, are they properly sealed? N/A
**If dampers present, 100% air shutoff? Yes
**Floor drains have proper liquid? N/A
**Raceways appear to be properly sealed? Yes
TANKS/CYLINDERS
Location Below Facp
Manufacturer PyroChem
Model # ABC Drychem
Manufactured Date 07/2018
Type Steel
Size NA
Serial Number ATM736254
Agent Weight 35
Gross Weight 0
Fill Weight 35
Measured Weight 0
Gauge Pressure ( PSIG ) 340
Date Of Last Recharge 07/2018
Date Of Last 5-Year Inspection N/A
Date of Last 5-Year Agent/Fluid Swap N/A
Date Of Last 6-Year Hydrostatic Test N/A
Date Of Last 12-Year Hydrostatic Test N/A
Measuring Device Used N/A
**Did Tank/Cylinder Pass Inspection yes
DEVICE INSPECTION REPORT
Total Inspected:6 Total Failed:0 Total Passed:6
Device Location Zone or Type Make Model Sensitivity Sensitivity Pass/ Comments
Address Range Alarm Point Fail
Above Generator
Engine Heat Detector Pass
Below Facp Manual Pull Station Pass
Below Facp Maintenance Switch NA NA Pass
Maintenance Bypass
Exterior Of Enclosure-1 Horn/Strobe Pass
Exterior Of Horn/Strobe Pass
•405 County Road E W•Saint Paul MN•55126
Suppression Inspection Page 6 of 7
Service Ticket No. :ST00303566
Enclosure-2
Left Of Facp Pressure Pressure Switch Tyco NA Pass
Switch
SIGNATURE
This report was reviewed with: Nardini Fire Equipment
Print Name : Xx Technician : Scott Bazille
Signature Signature
Date : 11/1/2023 Date : 11/1/2023
•405 County Road E W•Saint Paul MN•55126
Suppression Inspection Page 7 of 7