HomeMy WebLinkAbout2024-02-05 Fire Alarm Inspection & Testing Report Nardini -PAEoBpARyKE-
R
Nardini Fire Equipment
405 County Road E W
Saint Paul MN 55126
(651)483-6631
Report Cover Page
SERVICE DATE:2/5/2024 SERVICE TICKET:ST00324503
BUILDING STREET CITY STATE ZIP
Americinn By Wyndham 13025 60TH Street N Oak Park MN 55082
Heights
BUILDING CONTACT PHONE
N/A 651-275-0980 ext 400
System Status: Pass Tag Color: Yellow
Please see the attached reports. If there are any questions, please reach out to the
above office.
Download your Report at:
https://customer.nardinifire.com
Signed 2/5/2024 Signed 2/5/2024
Inspector: Mike Hexum Building Contact: N/A
Title:
Service Ticket No. :ST00324503
Date : 2/5/2024
A Company of- Frequency: Annual
Nardini PYE•BARKER Service Ticket No. : ST00324503
FIRE EQUIPMENT FIRE &SAFETY Inspection Contract No. : 0001432678
PO No. :
Equipment Location : Front entry
Fire Alarm Inspection
Property : Americinn By Wyndham Owner : Americinn By Wyndham
Address : 13025 60TH Street N Address : 13025 60TH Street N
City : Oak Park Heights City : Oak Park Heights
State : MN State : MN
Zip : 55082 Zip : 55082
Phone : 651-275-0980 ext 400 Phone : 651-275-0980 ext 400
FIRE ALARM INSPECTION SUMMARY
Smoke Detector: 20 Horn / Strobe: 18
Pressure Switch: 1 Manual Pull Station: 6
Chime: 51 Heat Detector: 5
Strobe: 8 Waterflow Switch: 2
SYSTEM DETAILS
Panel Condition Normal On Arrival? Yes
Was sensitivity performed during this inspection? No
Monitoring Company Silent Knight
Operator N/A
Time Placed On Test 10:31am
Circuit Class B
Software Revision 6.0
Panel Make Gamewell FCi
Panel Model S3
Last Date Software Revised. 01/01/2023
SYSTEM POWER SUPPLY
Primary Normal Volts 120
Control Panel Amps _ 2.75
Over Current Type Circuit Breaker
Over Current Amps 20
Panel Location Panel PP-11
•405 County Road E W•Saint Paul MN•55126
Fire Alarm Inspection&Test Page 2 of 9
Service Ticket No. :ST00324503
Breaker# 43
SYSTEM TEST AND INSPECTIONS
Control Panel (FACP)
Specify type of inspection Visual and Functional
Sequence Of Operation
Specify type of inspection Visual & Functional
Interface Equipment
Specify type of inspection Visual and Functional
Lamps/Led
Specify type of inspection Visual and Functional
Fuses
Specify type of inspection Visual
Primary Power Supply
Specify type of inspection Visual and Functional
Trouble Signals
Specify type of inspection Visual and Functional
Disconnect Switches
Specify type of inspection Visual and Functional
Ground Fault Monitoring
Specify type of inspection N/A
Transiet Suppressors
Specify type of inspection N/A
Remote Annuciators
Specify type of inspection N/A
Door Holders
Specify type of inspection N/A
Heat Detectors
Were heat detectors tested with heat? N/A
FACP BATTERY TEST
Battery#1 AH Rating (2) 12vdc 12Ah
Battery#1 Type Sealed Lead-Acid
EMERG. COMM. EQUIP I NOTIFICATION APP.
System Performance
**Visual Pass
**Functional Pass
Audible
**Visual Pass
•405 County Road E W•Saint Paul MN•55126
Fire Alarm Inspection&Test Page 3 of 9
Service Ticket No. :ST00324503
**Functional Pass
Visual
**Visual Pass
**Functional Pass
Speakers
**Visual N/A
**Functional N/A
Phone Set
**Visual N/A
**Functional N/A
Phone Jack
**Visual N/A
**Functional N/A
Off Hook Indicator
**Visual N/A
**Functional N/A
Amplifiers
**Visual N/A
**Functional N/A
Tone Generators
**Visual N/A
**Functional N/A
Call In Signal
**Visual N/A
**Functional N/A
Voice Clarity
**Visual N/A
**Functional N/A
Fireman Phone
**Visual N/A
**Functional N/A
Was dBA meter utilized? No
MONITORING & NOTIFICATION
On/off Premises Monitoring
Monitoring Agency Phone# 9528810344
Account Number 1800-2244
Account Password 1800-2244
**Alarm Signal - Received? Pass
**Alarm Restore- Received? Pass
•405 County Road E W•Saint Paul MN•55126
Fire Alarm Inspection&Test Page 4 of 9
Service Ticket No. :ST00324503
**Trouble Signal - Received? Pass
**Trouble Restored- Received? Pass
**Supervisory Signal - Received? Pass
**Supervisory Restore- Received? Pass
Notifications Of Testing Completion
**Fire Alarm Panel Condition Normal On Departure? Yes
WATERFLOW SWITCH - Location: Dry Sprinkler Waterflow
Zone or Address M052
Switch Type Paddle Type
Size (inches) 0
**Pass/Fail Pass
WATERFLOW SWITCH #2 - Location:Wet Sprinkler Waterflow
Zone or Address M060
Switch Type Paddle Type
Size (inches) 0
•
**Pass/Fail Pass
BOOSTER NAC
Location Electrical Room Behind Front
Desk
Manufacturer FCi
Model # FC-5495
Battery Size (2) 12vdc 7Ah
Battery Type Sealed Lead-Acid
**Visual Condition Pass
**Battery/Charger( Pass or Fail ) Pass
•405 County Road E W•Saint Paul MN•55126
Fire Alarm Inspection&Test Page 5 of 9
Service Ticket No. :ST00324503
DEVICE INSPECTION REPORT
Total Inspected:109 Total Failed:0 Total Passed:109
Zone or Sensitivity Sensitivity Pass/
Device Location Comments
Address Type Make Model Range Alarm Point Fail
Lobby Smoke S002 Smoke Detector FCi ASD-PL Pass
Lobby Smoke S003 Smoke Detector FCi ASD-PL Pass
Lobby Smoke S004 Smoke Detector FCi ASD-PL Pass
Lobby Smoke S005 Smoke Detector FCi ASD-PL Pass
Conference Room S006 Smoke Detector FCi ASD-PL Pass
Smoke
1st Floor Corridor S009 Smoke Detector FCi ASD-PL Pass
Smoke
1st Floor Corridor S010 Smoke Detector FCi ASD-PL Pass
Smoke
1st Floor Corridor S011 Smoke Detector FCi ASD-PL Pass
Smoke
1st Floor Corridor S012 Smoke Detector FCi ASD-PL Pass
Smoke
1st Floor Corridor S013 Smoke Detector FCi ASD-PL Pass
Smoke
2nd Floor Corridor S015 Smoke Detector FCi ASD-PL Pass
Smoke
2nd Floor Corridor S016 Smoke Detector FCi ASD-PL Pass
Smoke
2nd Floor Corridor S017 Smoke Detector FCi ASD-PL Pass
Smoke
2nd Floor Corridor S018 Smoke Detector FCi ASD-PL Pass
Smoke
2nd Floor Corridor S019 Smoke Detector FCi ASD-PL Pass
Smoke
2nd Floor Corridor S020 Smoke Detector FCi ASD-PL Pass
Smoke
2nd Floor Corridor S021 Smoke Detector FCi ASD-PL Pass
Smoke
Laundry Chute Smoke S022 Smoke Detector FCi ASD-PL Pass
2nd Floor Lobby Smoke S024 Smoke Detector FCi ASD-PL Pass
1st Floor Corridor S040 Smoke Detector FCi ASD-PL Pass
Smoke
Main Laundry Heat S007 Heat Detector FCi ATD-RL Pass
Electrical Room Heat S008 Heat Detector FCi ATD-RL Pass
South Laundry Heat S014 Heat Detector FCi ATD-RL Pass
2nd Floor Electrical S023 Heat Detector FCi ATD-RL Pass
Room Heat
2nd Floor Storage S025 Heat Detector FCi ATD-RL Pass
Room Heat
Main Entry Pull M030 Manual Pull Station FCi MS-2 Pass
Front Desk Pull M031 Manual Pull Station FCi MS-2 Pass
Main Laundry Pull M032 Manual Pull Station FCi MS-2 Pass
South Pull M033 Manual Pull Station FCi MS-2 Pass
•405 County Road E W•Saint Paul MN•55126
Fire Alarm Inspection&Test Page 6 of 9
Service Ticket No. :ST00324503
2nd Floor Corridor Pull M026 Manual Pull Station FCi MS-2 Pass
2nd Floor Corridor Pull M027 Manual Pull Station FCi MS-2 Pass
Dry System Low Air M050 Pressure Switch Pass
Pool Area Horn/Strobe Pass
Pool Area By Exit Door Horn/Strobe Pass
Pool Area Restroom Strobe Pass
Outside Hospitality Horn/Strobe Pass
Room
Hospitality Room Strobe Pass
Restroom
Hospitality Room Horn/Strobe Pass
Restroom By Front Strobe Pass
Desk
By Main Entrance Horn/Strobe Pass
By Vending Machines Horn/Strobe Pass
Kitchen Storage By Strobe Pass
Front Desk
Laundry Room Behind Horn/Strobe Pass
Front Desk
By Room 105 Horn/Strobe Pass
By Room 118 Horn/Strobe Pass
By Room 129 Horn/Strobe Pass
1st Floor Guest Laundry Strobe Pass
1st Floor South Exit Horn/Strobe Pass
By Room 229 Horn/Strobe Pass
By Room 218 Horn/Strobe Pass
By Room 206 Horn/Strobe Pass
By Room 205 Horn/Strobe Pass
In Room 105 Chime Pass
In Room 106 Chime Pass
In Room 108 Chime Pass
In Room 107 Chime Pass
In Room 109 Chime Pass
In Room 110 Chime Pass
In Room 112 Chime Pass
In Room 111 Chime Pass
In Room 113 Chime Pass
In Room 114 Chime Pass
In Room 116 Chime Pass
In Room 115 Chime Pass
In Room 117 Chime Pass
In Room 118 Horn 1 Strobe Pass
Room 118 Bathroom Strobe Pass
In Room 120 Horn/Strobe Pass
•405 County Road E W•Saint Paul MN•55126
Fire Alarm Inspection&Test Page 7 of 9
Service Ticket No. :ST00324503
Room 120 Bathroom Strobe Pass
In Room 119 Chime Pass
In Room 121 Chime Pass
In Room 122 Horn/Strobe Pass
Room 122 Bathroom Strobe Pass
In Room 124 Chime Pass
In Room 123 Chime Pass
In Room 125 Chime Pass
In Room 126 Chime Pass
In Room 128 Chime Pass
In Room 127 Chime Pass
In Room 129 Chime Pass
In Room 229 Chime Pass
In Room 227 Chime Pass
In Room 228 Chime Pass
In Room 226 Chime Pass
In Room 225 Chime Pass
In Room 223 Chime Pass
In Room 224 Chime Pass
In Room 222 Chime Pass
In Room 221 Chime Pass
In Room 219 Chime Pass
In Room 220 Chime Pass
In Room 218 Chime Pass
In Room 217 Chime Pass
In Room 215 Chime Pass
In Room 216 Chime Pass
In Room 214 Chime Pass
In Room 213 Chime Pass
In Room 211 Chime Pass
In Room 212 Chime Pass
In Room 210 Chime Pass
In Room 209 Chime Pass
In Room 207 Chime Pass
In Room 208 Chime Pass
In Room 206 Chime Pass
In Room 205 Chime Pass
In Room 204 Chime Pass
In Room 204 Chime Pass
In Room 203 Chime Pass
In Room 202 Chime Pass
•405 County Road E W•Saint Paul MN•55126
Fire Alarm Inspection&Test Page 8 of 9
Service Ticket No. :ST00324503
SIGNATURE
This report was reviewed with: Nardini Fire Equipment
Print Name : N/A Technician : Mike Hexum
Signature Z" / Signature •
Date : 2/5/2024 Date : 2/5/2024
•405 County Road E W•Saint Paul MN•55126