HomeMy WebLinkAbout2025-10-29 Nardini Fire - Suppression Chemical Inspection Report10/29/2025
NA
ZIP
SERVICE DATE:
Report Cover Page
BUILDING
5701 N St Croix Trail MN
(651) 483-6631
Saint Paul MN 55126
9528874547
SERVICE TICKET:
STREET CITY STATE
405 County Road E W
Xcel Substation--allen King 56357
Nardini Fire Equipment
PHONEBUILDING CONTACT
Oak Park
ST00419047
System Status:Pass Tag Color:Green
Please see the attached reports. If there are any questions, please reach out to the
above office.
Download your Report at:
Signed Signed
Inspector:Building Contact:
Title:
10/29/2025 10/29/2025
Scott Bazille NA
https://customer.nardinifire.com
0001429023
Equipment Location :
Frequency :
:5537956357
Inspection Contract No. :
Phone
MUST HAVE A ZIEGLER PO
9528874547
5701 N St Croix Trail
State
:
Address :
9528874575
:
Phone
State
Address
Generator
Ziegler Power SystemsOwner
Suppression Chemical Inspection Report
Xcel Substation--allen King
Zip
:
8050 County Road 101 E.
Property :
:
ST00419047
:
Oak Park ShakopeeCity
:
Date :
Service Ticket No. :
10/29/2025
MN
Zip
MN
City
Annual
:
:
:
PO No. :
None found at time of inspection.
DEFICIENCIES
MONITORING & NOTIFICATION
On/off Premises Monitoring
Panel Condition Normal On Arrival?Yes
Monitoring Agency Phone #0
Account Number Customer put on test
Account Password NA
Notifications Of Testing Completion
Building Management Notified?Yes
**Are There Any Monitoring Deficiencies To Report?No
HAZARD DETAIL
Type of System Dry Chemical
If scale was used, enter last calibration date N/A
If gauge was used, enter last calibration date N/A
**Are record drawings available?N/A
**Are flow calculations available?N/A
**Sequence of Operation is posted?N/A
**Proper warning signs in place?Yes
**Any changes to hazard since system was installed?Unable to Confirm
**Any changes to hazard since last inspection?Unable to Confirm
**Piping is properly supported?Yes
**Is piping proper type for the system?Yes
Suppression Inspection Page 2 of 7
• 405 County Road E W • Saint Paul MN • 55126
ST00419047Service Ticket No. :
**Are the fittings the proper type for the system?Yes
**Nozzle(s) are properly oriented?Yes
**Nozzle(s) are properly supported?Yes
**Agent container(s) are properly supported?Yes
**Discharge hose(s) are in good condition?N/A
Date on discharge hoses N/A
**Pilot hose(s) are in good condition?Yes
Date on pilot hoses N/A
**Did all initiating devices function?Yes
**Did all manual releasing devices function?Yes
**Did all maintenance switches function?Yes
**Did all abort stations function?N/A
**Did all release devices function?Yes
**Did all notification devices function?Yes
PANEL INFORMATION
Information
Type of transmission Relay
Circuit Class Class B
**Circuits are properly supervised?Yes
Detection Setup Single Zone
Method of Actuation Electric
Type of releasing device Pyrochem
Date of releasing device (if applicable)N/A
Panel Information
Panel Manufacturer Ansul
Panel Model AutoPulse Z10
Is this the primary panel?Yes
Over current protection type Circuit Breaker
Over current size (amps)15
Breaker location Left of transfer switch
Breaker number 13
**Dedicated circuit?Yes
**Breaker marked?Yes
Battery #1
Type Sealed Lead-Acid
Rated volts 12
Rated amp hour 7
Manufacture Date 04/2025
**Leaks or corrosion?Visual Only
**Connections tight?Pass
**Did battery pass?Yes
Suppression Inspection Page 3 of 7
• 405 County Road E W • Saint Paul MN • 55126
ST00419047Service Ticket No. :
**Was battery replaced?No
Battery #2
Type Sealed Lead-Acid
Rated volts 12
Rated amp hour 7
Manufacture date 04/2025
**Leaks or corrosion?Visual Only
**Connections tight?Pass
**Did battery pass?Yes
**Was battery replaced?No
**Was battery size confirmed with drawings?No Drawings on Site
System Function Summary & Test
**Alarm Bells/Horns/Strobe evacuation alarms function properly?Yes
**Loss of AC power is detected by the panel?Yes
**Loss of secondary power is detected by the panel?Yes
**Electrical opens in indicating circuits are detected?Yes
**Electrical shorts in indicating circuits are detected?N/A
**Panel was in good operational condition upon arrival?Yes
"**Panel and surrounding equipment, conduit and wiring well secured and in good
condition?"Yes
**Are all troubleshooting LEDs operating correctly?Yes
**Primary power supply operates properly under full load?Yes
**Transient Suppressors visually inspected?N/A
**Have all fuses been checked for rating and supervision?N/A
**Are wires labeled and identified?N/A
System Test & Inspection
Control Panel Visual and Functional
Lamps/LEDs Visual and Functional
Primary Power Supply Visual and Functional
Trouble Signals Visual and Functional
Ancillary Devices
Power Shutdown Present
SEQUENCE OF OPERATIONS
First Alarm
Building Activation Alarm
First Initiating device(s)Heat Detector
Notification Horn/Storbe
Second Notification Horn/Strobe outside area/room
Time Delay No time delay
Ancillary device shutdown Pass
Second Alarm
Suppression Inspection Page 4 of 7
• 405 County Road E W • Saint Paul MN • 55126
ST00419047Service Ticket No. :
Building Activation N/A
Second Initiating device(s)NA
Notification N/A
Second Notification N/A
Time Delay N/A
Ancillary device shutdown NA
Panel Piezo with LEDs
Release Device
Location Below FACP
Zone or Address Release
***Pass/Fail Pass
Manual Release
Building Activation Alarm
Notification Horn/Strobe
Second Notification Horn/Strobe outside area/room
Time Delay No Time Delay
Ancillary device shutdown Pass
Panel Piezo with LEDs
Discharge Alarm
Building Activation Alarm
Notification Horn/Strobe
Second Notification Horn/Strobe outside area/room
Panel Piezo with LEDs
Ancillary device shutdown Pass
Abort
Are abort device(s) present?N/A
Abort Type N/A
ENCLOSURE INSPECTION
**Does enclosure integrity apply?Yes
**Visual condition appears to be okay?Yes
**Proper door sweeps present?Yes
**Proper seals on door jambs present?N/A
**Proper astragal around double doors?N/A
**Proper seal around windows?N/A
**Wall partitions extend from floor slab to roof?N/A
**Holes, cracks, or other openings in walls?N/A
**Bottom of walls at floor properly sealed?N/A
**If walls are porous, are they properly sealed?N/A
**If dampers present, 100% air shutoff?Yes
**Floor drains have proper liquid?N/A
Suppression Inspection Page 5 of 7
• 405 County Road E W • Saint Paul MN • 55126
ST00419047Service Ticket No. :
**Raceways appear to be properly sealed?Yes
TANKS/ CYLINDERS
Location Below Facp
Manufacturer PyroChem
Model #ABC Drychem
Manufactured Date 07/2018
Type Steel
Size NA
Serial Number ATM736254
Agent Weight 35
Gross Weight 0
Fill Weight 35
Measured Weight 35
Gauge Pressure ( PSIG )350
Date Of Last Recharge 07/2018
Date Of Last 5-Year Inspection N/A
Date of Last 5-Year Agent/ Fluid Swap N/A
Date Of Last 6-Year Hydrostatic Test N/A
Date Of Last 12-Year Hydrostatic Test N/A
Measuring Device Used N/A
**Did Tank/ Cylinder Pass Inspection yes
Comments
DEVICE INSPECTION REPORT
Device Location
Total Inspected:6
Zone or
Address
Pass /
FailMakeType
Total Passed:6Total Failed:0
Model Sensitivity
Range
Sensitivity
Alarm Point
Above Generator
Engine PassHeat Detector
Below Facp
Maintenance Bypass PassNAMaintenance Switch NA
Exterior Of Enclosure- 1 PassHorn / Strobe
Exterior Of Enclosure- 2 PassHorn / Strobe
Left Of Facp Pressure
Switch PassTycoPressure Switch NA
Manual Release PassAnsulElectrical Manual
Release Ansul
Suppression Inspection Page 6 of 7
• 405 County Road E W • Saint Paul MN • 55126
ST00419047Service Ticket No. :
SIGNATURE
This report was reviewed with:Nardini Fire Equipment
:
:
NA
DateDate
Signature
:
10/29/2025
:
Scott Bazille
10/29/2025:
:Technician
Signature
Print Name
Suppression Inspection Page 7 of 7
• 405 County Road E W • Saint Paul MN • 55126