Re: M&I Bank
Bonestroo file No. 55-08-000
Deai ic
` �w�N�
September 29, 2008 � °�l "���
Mr. Eric Johnson
We have reviewed the Development Plans, for M&I Bank as submitted by McCombs Frank Roos Associates.
Following are our comments and/or recommendations.
Sheet['Z.O1A
1. Verify the location of the northerly property line,
2. An easement needs to be dedicated for the trail on the north side of the property.
8leet[-3.O1A
1. A pedestrian ramp should be called out at the Wal-Mart Diive.
2. A "Fire Lane, No Padking^ sign is shown on the plans; however the location of the sign is not
identified on the site pan.
3. The plan calls out bollards at 14 locations; however these locations are not easy to identify.
Sheet[-4.O1AA
1 On the wes side there is an existing 936.0 contour that forms a drainage area or swale within the
property line. The proposed contours do not dentify the Iocation of the new 936.0 contour and
how it wiH connect with the existing 936.0 contour. The pro d contours direc storm water to
the west, rather than to the north as it currently exists.
2. Verify that the cross siope on the path is at a maximum 2%. It appeais that the grade along the
south side of the path isst937.O and the north side isatg36.O.
3. Clearly identify the high points on the plans.
4. Verify the contour lines southwest of the transformer pad. They appear to be greater than 3:1.
SheetL1.O1A
1. Verify that the proposed Iandscaping wiH not be in conflict with the site utilities
5heetC5.O1A
1. The line type shown in the plan view for silt fence and limits of disturbance do not match the line
type in the legend.
Z. The limits of disturbance should be identified on the south end of the property,
2335 Highwa 36 W
St. Paul, MN 55113
Tel 651-636-4600
Fax 651-636-1311
Su Paul
St. Cloud
Rochester
Milwaukee
Chicago
Engineering
Planning
innovation
City cv Oak Park Heights Page
M&1 Bank September 2R2ooa
Sheet[-G.O1A
1 Verify that the existing public utilities at the north end of the property are shown correctly,
induding the flow directiona arrows. The construction plans for the utility improvement along
60t stree have been sent to MFRA, Inc.
2. The plans currently show an underground storrn water system. Following are the items related to
this system:
a. The underground system must be a minimum of 1 0 from any public utilities.
b. The plans currently show a gate valve beneath the system The storm tech system
should be revised to account for the gate vaive box.
c. Insulation shall be placed between the water service and the storage system.
d. The storm tech system should be revised to account for the footings of the monument
sign.
3. The connection to the public wate main shall be shown as a we tap.
Sheet[-8.O1A
1. Note 5 for the pedestrian ramp has a call out for either a granite panel or stamped concrete
truncated dome. The City will not accept stamped concrete truncated domes.
2. There are several details that are missing information (For example: pavement section details).
General Comments
Sincerely,
1. The following items still need to be submitted for review:
BONESTROO
a[opy of the Approval Ietter from the Browns Creek Watershed District.
b. Storm Sewer Sizing Calculations,
c. Verify the need for a MNDOT permit for construction within the right-of-way for utility
connections and/or grading within the ditch.
If you have any questions or require additional information, 'ease contact mf- at (651) 604-4788 or Dennis
Postier at (651) 604-4815.