HomeMy WebLinkAbout2011-06-08 Viking Automatic Sprinkler Letter Forwarding Fire Pump Test Reports , . FIRE PUMP TEST REPORT JOB# VI kll N 0 Viking Automatic Sprinkler Co. INSPECTOR 301 York Ave, St. Paul, MN 55130 FAX: GENERAL INFO PUMP INFO DRIVER INFO Name: A.S. KING PLANT Serial #: Manufacturer: Address:1103 KING PLANT RD Manufacturer: ITT-AC Type: City: BAYPORT, MN Type: Power: GPM: 1000 Engine Hours: Inspector: MIKE CRUZ Pressure: 70 Gear Ratio: Date: 6-8-11 RPM: 3550 Pump On: Jockey On: Jockey Off: Rating: �O0 70; RPM: :3550 Chum: 0 gpm 85.4 psi TEST RESULT PASSED Rated 1000 gpm 70 psi 150% 1500 gpm 45.5 psi . ': :- ., . ii.... , . . aura 00 vca ll. 84 iiiiii 0.975 1"b' Briliartiireali;` 0 0 0 0 0 0 0 0 0 83 . Ee:2, 476,4 miximism 0.975 -0,..,.. Eat ,i.0. -._ 12 ..,-. 1 E.,,z1 am 0 0 0 0 0 0 0 0 0 83 °'3556 IIIMEEIM 61 RE] 0.975 EsE30:102mrsi 504 504 0 0 0 0 0 1,008 1,006 61 - 2554 - Eali J, 0,5 : rEiffiej 0.975 Ess t 32. ',, Ej sai i , ..o- .--" EA pai 504 504 504 0 0 0 0 1,512 1,510 47 -- -1 Pump Curves 00 CO CO — 40 ' ■ 3 • _, _____ , — I 1 I ■ I I -------- ---- 0 . -200 0 200 400 600 800 1000 1200 1400 1600 GPM •III•Pump Rating , -0—Pump Test _I Rev 2-1 -1 1 ,.. 301 YORK AVENUE Aril *ILI INI 0 ST. PAUL, MINNESOTA 55130 73 -4 C SPRINKLER CO. (651) 558-3300 • (800) 229-6263 .1 , r Setting The Standard... Fax (651)558-3310 NAME `A C. 4 ( ik . •N LOCATION 12K-1 la,. / Lail q Pc, ii BY Iv\ AC DATE 68 I' - SYSTEMS INVOLVED WATER SUPPLY WITNESS BY Suction Disch Net R.P.M. Volts/ Nozzle TOTAL Press Press Press Amps Size I l'i i` P k i 17 ki / / / / Disch. ( iS & 44 Pitot cb C" 9z.. r 6 8(1 35i(i , I'' Li GPM di (S-4 tit , VS 46 Pilot 34 3 I k) 4/ - lb i3 4 i 3s G fis'i L + GPM/ _cog , I Do 8 0 rio ' iti S 4 1 Pito t 3 Z 7 3 ? 3 L- es 1-rz. L i ? 555 tos'/ 6g GPM S) i 0 q S&/ 7 ICI ,,, Z pita 3 z • C L Ptiti4' Gpms I/ Pitot GPM ' Pitot • GPM PUMP SPECIFICATIONS MOTOR SPECIFICATIONS MFR 1 1 1 - (V H.P. So Rpm 3s4 TYPE Ce s , t GPM I (x)0 y s k 3' ° PH J CYCL VOLTS • HEAD Ft 11, PSI 1 0 0 IQ- 1 tommENTs . 0'4 - 0 i ? 5 '' ("1 — 01/ t ..., 4. • FIRE PUMP TEST REPORT JOB# C t, kI N` Viking Automatic Sprinkler Co. INSPECTOR n urawicaPIwn.ERCO. 301 York Ave, St. Paul, MN 55130 FAX: GENERAL INFO PUMP INFO DRIVER INFO Name: A.S. KING PLANT Serial #: Manufacturer: Address:1103 KING PLANT RD Manufacturer: FAIRBANKS Type: City: BAYPORT, MN Type: Power: GPM: 2500 Engine Hours: Inspector: MIKE CRUZ Pressure: 131 Gear Ratio: Date: 6 -8 -11 RPM: 1770 Pump On: Jockey On: Jockey Off: Rating: o o - 4131,. RPM: ' ro Chum: 0 gpm 160 psi TEST RESULT PASSED Rated: 2500 gpm 131 psi 150 %: 3750 gpm 85.2 psi 1781,. iM ° ' 0.906 .':Q 4 4 T 1 ll - 41" i . 0 0 0 0 0 0 0 0 0 176 1781 `179'1 0. 178 2.5 0 . 9 0 6 c "" t; , 0 0 0 0 0 0 0 0 0 176 dive 1788:• x123. : 123 2.5 0.906 =!4- " . �° m pQ s` 632 632 632 632 0 0 0 2,528 2,534 124 17 93 40' 93 2.5 0.906 '14 "`14 ;i ,. .._ .,,t.fi r * ,.1. -' . 632 632 632 632 632 832 0 3,792 3,820 94 Pump Curves 200 180 - __ __`_ ... - -._. __-__. _ 120 E 100 _ ■ t 80— _...: _ 60 I 0 1 -500 0 500 1000 1500 2000 2500 3000 3500 4000 4500 GPM L.- Pump Rating —e— Pump Test Rev 2 -1 -11 V _ 301 YORK AVENUE . 1 ST. PAUL, MINNESOTA 55130 A UTCMAATIC SPRINKLER CO. (651) 558 -3300 • (800) 229 -6263 Setting The Standard... Fax (651)558- 3310 NAME )(LI 6 - k . ,, LOCATION BY Wit- DATE & . 8 it SYSTEMS INVOLVED WATER SUPPLY WITNESS BY Suction Disch Net R.P.M. Volts/ Nozzle TOTAL Press Press Press Amps Size 2 f 2 �' 2' t 2 t 2' 'L ii / Disch. Pitot 0 E.. CV— 6 i 13 ,ribt GPM C 0 . , Pitot 1 R! 1 i L i 1 LI ko f) 11.:1 12 3 116 GPM6 f GCE b 3 t 6 3i ZSLI roc 1(I 1`1 1 I 1c IV 14/ 1 4 Ck 93 c13 13-Si GPM6 631 43/ 631 63' Gat 4 Pitot GPM . Pitot GPM Pitot • GPM PUMP SPECIFICATIONS MOTOR SPECIFICATIONS MFR C'. - nes - 1�'�o.s c H.P. 3'00 RPM 1 lbo TYPE 00, L GPM 2w PH -"' CYCL j VOLTS — HEAD FT. PSI 131 c.% I COMMENTS: SO 1 011 ° 13 4 k 1 301 York Ave V Mt, St. Paul, Minnesota 55130 CO. (651) 558 -3300 • (800) 229 -6263 Setting The Standard... Fax: (651) 558 - 3310 SHEET 2 of 2 - Use separate sheet for each system inspected System No. or Description if multiple systems 'T }/ 7 - (hie Cu ll,l----- Inspection Report ( J, 1 T(--t i-. l No. -23001 11 Date dry-pipe valve trip tested (control valve partially open) (See Trip Test Table which follows) 12 Date dry-pipe valve trip tested (control valve fully open) A - y- f (See Trip Test Table which follows) 13 Date quick - opening device tested (See Trip Test Table which follows) DRY VALVE TRIP TEST TABLE Q.O.D. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. t-0 U.' 1 F 4 WOO Z'1A?iv V. •I&. 46 --7 i 2c.)(/Z. DRY PIPE Time to Trip Water Aix Trip Point Time Water Reached Alarm Operated OPERATING Thru Test Pipe Pressure Pressure Air Pressure Test Outlet Properly TEST MIN. SEC. PSI PSI PSI MIN. SEC. YES NO Without Q.O.D With , t Q.O.D C, t V 14 Date d e l u g e o r p r e a c t i o n v a l v e tested A - 5- I f (See Trip Test Table which follows) 7 • n514- TRIP TEST TABLE Operation ❑ PNEUMATIC w tECTRIC ❑ HYDRAULIC Piping Supervised ❑ YES a.NO Detecting Media Supervised BYES ❑ NO DELUGE & Does valve operate from the manual trip and /or remote control stations AYES ❑ NO PREACTION Is there an accessible facility in each circuit for testing DES ❑ NO (Method of Testing Circuits f — // /+q ) VALVES Does each circuit operate Does each circuit Maximum time to MAKE MODEL supervision loss alarm operate valve release operate release YES NO YES NO YES NO A /I A..1 i t IR` c a.-� ),` Y - I 15 See Control Valve Maintenance Table CONTROL VALVE MAINTENANCE TABLE Explain Abnormal Control Valves Number Type Open Secured Closed Signs Condition City Control Valves Bypass Valves Tank Control Valves Pump Control Valves Sectional Control Valves System Control Valves Other Control Valves Kitchen Control Valves 16 Water Flow Test at Sprinkler Riser Water Supply Source: City Tank Pump Residual Test Pipe Size of Static (Flow) 1 Date Location Test Pipe Pressure Pressure Last Water Flow Test This Water Flow Test 17 Explain any "No" answers and comments: j 18 Adjustments or corrections made during this inspection: 19 Although the comments are not the result of an engineering review, please see the attached Non - Inspection Related Deficiencies form for additional items fo d during the co of the inspection (only attached if applicable). Inspector's Signature: G ' Date: 6 - - f, • Inspection Form P2 1-24-11 - i 301 York Ave v, alma' St. Paul, Minnesota 55130 ANIOSIAlle SPRINKLER CO (651) 558 -3300 • (800) 229 -6263 Setting The Standard... Fax: (651) 558 - 3310 SHEET 2 of 2 - Use separate sheet for each system inspected System No. or Description if multiple systems UA I. v c tlocx Inspection Report To c, el S (-- l`I*G ere ' "K No. Zit /t 11 Date dry -pipe valve trip tested (control valve partially open) (See Trip Test Table which follows) 12 Date dry-pipe valve trip tested (control valve fully open) 6 - _ it (See Trip Test Table which follows) 13 Date quick - opening device tested ( ee Trip Test Table which follows) 2' ' DRY VALVE l 9 o TRIP TEST TABLE Q.O.D. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. NIA 4- S ! - DRY PIPE Time to Trip Water Air Trip Point Time Water Reached Alarm Operated OPERATING Thru Test Pipe Pressure Pressure Air Pressure Test Outlet Properly TEST MIN. SEC. PSI PSI PSI MIN. SEC. YES NO Without �,v .O. /00 9 Z 2 7_ II- Q.O.D 14 Date deluge or preaction valve tested (See Trip Test Table which follows) TRIP TEST TABLE ��_Operation ❑ PNEUMATIC ❑ ELECTRIC o HYDRAULIC ' Pippin 9n ised ❑ YES ❑ NO (Detecting Media Supervised a YES ❑ NO DELUGE & Does valve operate manual trip and /or remote control stations a YES ❑ NO PREACTION Is there an accessible facility in e�3Lfrd "t for testing ❑ YES ❑ NO (Method of Testing Circuits VALVES Does each circuit operate Does each circuit Maximum time to MAKE MODEL ' ion loss alarm operate valve release operate release YES YES f NO YES NO I 15 See Control Valve Maintenance Table CONTROL VALVE MAINTENANCE TABLE Explain Abnormal Control Valves Number Type Open Secured Closed Signs Condition City Control Valves Bypass Valves Tank Control Valves Pump Control Valves Sectional Control Valves % Ce y V /lh, System Control Valves 7 l 'V Cif Z- JLt) Other Control Valves Kitchen Control Valves 16 Water Flow Test at Sprinkler Riser Water Supply Source: City Tank Pump Residual I Test Pipe Size of Static (Flow) Date Location Test Pipe Pressure Pressure Last Water Flow Test This Water Flow Test 17 Explain any "No" answers and comments: 18 Adjustments or corrections made during this inspection: 19 Although the comments are not the result of an engineering review, please see the attached Non - Inspection Related Deficiencies form for additional items found during the course of the inspection (only attached if applicable). Inspector's Signature: Date: Inspection Form P2 1-24-11 it 301 York Ave v, Bt. N a St. Paul, Minnesota 55130 AUTOMOmC tlpHOOC flR CO. (651) 558 -3300 • (800) 229 -6263 Suing The Standard... Fax: (651) 558 - 3310 SHEET 2 of 2 - Use separate sheet for each system inspected System No. or Description if multiple systems YiA RI) - Sw,'-i (.(-, (i ( A/l Inspection Report T U. I No. 130/ c ri 11 Date dry -pipe valve trip tested (control valve partially open) (See Trip Test Table which follows) 12 Date dry-pipe valve trip tested (control valve fully open) 6 - i (See Trip Test Table which follows) 13 Date quick - opening device tested ( Trip Test Table which follows) LI " DRY VALVE 1115 TRIP TEST TABLE Q.O.D. L _ Z MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. DRY PIPE Time to Trip Water Air Trip Point Time Water Reached Alarm Operated OPERATING Thru Test Pipe Pressure Pressure Air Pressure Test Outlet Properly TEST MIN. SEC. PSI PSI PSI MIN. SEC. YES NO Without Q.O.D /3 /3 I C7 y I I d -1 6 1 With , Q.O.D I 14 Date deluge or preaction valve tested (See Trip Test Table which follows) TRIP TEST TABLE Operation ❑ PNEUMATIC ❑ ELECTRIC ❑ HYDRAULIC Piping Supervised ❑ YES ❑ NO (Detecting Media Supervised ❑ YES ❑ NO DELUGE & Does valve operate from the manual trip and /or remote control stations ❑ YES ❑ NO PREACTION Is there an accessible facility in each circuit for testing ❑ YES ❑ NO (Method of Testing Circuits VALVES Does each circuit operate Does each circuit Maximum time to MAKE MODEL supervision loss alarm operate valve release operate release YES NO YES NO YES NO 15 See Control Valve Maintenance Table CONTROL VALVE MAINTENANCE TABLE Explain Abnormal Control Valves Number Type Open Secured Closed Signs Condition City Control Valves Bypass Valves Tank Control Valves Pump Control Valves Sectional Control Valves I ` r Y System Control Valves t/ S Other Control Valves j N R. S ; S )uSC l°c.7j1. l: C TGt2 Kitchen Control Valves 16 Water Flow Test at Sprinkler Riser Water Supply Source: City Tank Pump Residual Test Pipe Size of Static (Flow) Date Location Test Pipe Pressure Pressure Last Water Flow Test This Water Flow Test 17 Explain any "No" answers and comments: 18 Adjustments or corrections made during this inspection: 19 Although the comments are not the result of an engineering review, please see the attached Non - Inspection Related Deficiencies form for additional items found during the urse of the inspection (only attached if applicable). Inspector's Signature: 0 , L Date: 6-4 1 Inspection Form F21 -24-11 301 York Ave v ito N co St. Paul, Minnesota 55130 AUTOMATIC SPwNICUMCO. (651) 558 -3300 • (800) 229 -6263 Setting The Standard... Fax: (651) 558 -3310 SHEET 2 of 2 - Use separate sheet for each system inspected System No. or Description if multiple systems Inspection Report No. zit)/ fn 11 Date dry-pipe valve trip tested (control valve partially open) (See Trip Test Table which follows) 12 Date dry-pipe valve trip tested (control valve fully open) G . I/ (See Trip Test Table which follows) 13 Date quick - opening device tested (See Trip Test Table which follows) y" DRY VALVE E�/(j TRIP TEST TABLE Q.O.D. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. 1Qrft�Mi. c 3'l I ESetsdsVl- ----- DRY PIPE Time to Trip Water Air Trip Point Time Water Reached Alarm Operated OPERATING Thru Test Pipe Pressure Pressure Air Pressure Test Outlet Properly TEST MIN. SEC. PSI PSI PSI MIN. SEC. YES NO Without ��//,� OC.� Q.O.D 0 Z2 ds S2 Zr) (Z) "et 1r 0 With Q .O.D ....... ..""' .. 14 Date deluge or preaction valve tested (See Trip Test Table which follows) TRIP TEST TABLE Operation ❑ PNEUMATIC ❑ ELECTRIC ❑ HYDRAULIC Piping Supervised ❑ YES ❑ NO (Detecting Media Supervised ❑ YES ❑ NO { i DELUGE & Does valve operate from the manual trip and /or remote control stations ❑ YES ❑ NO PREACTION Is there an accessible facility in each circuit for testing ❑ YES ❑ NO (Method of Testing Circuits VALVES Does each circuit operate Does each circuit Maximum time to MAKE MODEL supervision loss alarm operate valve release operate release YES I NO YES I NO YES I NO 15 See Control Valve Maintenance Table - CONTROL VALVE MAINTENANCE TABLE Explain Abnormal Control Valves Number Type Open Secured Closed Signs Condition City Control Valves Bypass Valves Tank Control Valves Pump Control Valves Sectional Control Valves System Control Valves Other Control Valves Kitchen Control Valves 16 Water Flow Test at Sprinkler Riser Water Supply Source: City Tank Pump Residual Test Pipe Size of Static (Flow) Date Location Test Pipe Pressure Pressure Last Water Flow Test This Water Flow Test 17 Explain any "No" answers and comments: 18 Adjustments or corrections made during this inspection: 19 Although the comments are not the result of an engineering review, please see the attached Non-Inspection Related Deficiencies form for additional items found during the of the inspection (only attached if applicable). Inspector's Signature: \ , / . Date: (7 '7 - j' 1 Inspection Form P21 -2411 301 York Ave v■ P t, N CS St. Paul, Minnesota 55130 AUTOMATIC tlM CO. (651) 558 -3300 • (800) 229 -6263 Setting The Standard... Fax: (651) 558 - 3310 SHEET 2 of 2 - Use separate sheet for each system inspected System No. or Description if multiple systems Inspection Report N c 0 S I No. 23(.491- 11 Date dry-pipe valve trip tested (control valve partially open) (See Trip Test Table which follows) 12 Date dry-pipe valve trip tested (control valve fully open) (See Trip Test Table which follows) 13 Date quick - opening device tested (See Trip Test Table which follows) DRY VALVE TRIP TEST TABLE Q.O.D. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. DRY PIPE Time to Trip Water Air Trip Point Time Water Reached Alarm Operated OPERATING Thru Test Pipe Pressure Pressure Air Pressure Test Outlet Properly TEST MIN. SEC. PSI PSI PSI MIN. SEC. YES NO Without Q.O.D With Q.O.D 14 Date deluge or ',reaction valve tested 4-q- I ( (See Trip Test Table which follows) Z V t? ( j "Z S iJ 00N-) TRIP TEST TABLE uJ !: 1 ra t: U '. Operation Aftwraunc ❑ ELECTRIC OHYDRAULIC Piping Supervised AXES ❑ NO 'Detecting Media Supervised DOES ❑ NO DELUGE & Does valve operate from the manual trip and /or remote control stations ❑ YES ❑ NO PREACTION Is there an accessible facility in each circuit for testing ❑ YES ❑ NO 'Method of Testing Circuits Lo s3 Ai," VALVES Does each circuit operate Does each circuit Maximum time to MAKE MODEL supervision Loss alarm operate valve release operate release Al C YES I NO YES I NO YES NO cv. P - x 01- u: k,.• I- - 3 ). k 'Sr . 15 See Control Valve Maintenance Table CONTROL VALVE MAINTENANCE TABLE Explain Abnormal Control Valves Number Type Open Secured Closed Signs Condition City Control Valves Bypass Valves Tank Control Valves Pump Control Valves Sectional Control Valves System Control Valves Other Control Valves . Kitchen Control Valves 16 Water Flow Test at Sprinkler Riser Water Supply Source: City Tank Pump Residual Test Pipe Size of Static (Flow) Date Location Test Pipe Pressure Pressure Last Water Flow Test This Water Flow Test 17 Explain any "No" answers and comments: 18 Adjustments or corrections made during this inspection: 19 Although the comments are not the result of gineering review, please see the attached Non- Inspection Related Deficiencies form for additional i fo the co of the inspection (only attached if applicable). Inspector's Signature: Date: 6 - - // Inspection Form P21 -24-11 301 York Ave v ,, N Q St. Paul, Minnesota 55130 AUTOMMIC Spp NICLO ! CO. (651) 558 -3300 • (800) 229 -6263 Setting The Standard... Fax: (651) 558 - 3310 SHEET 2 of 2 - Use separate sheet for each system inspected System No. or Description if multiple systems Inspection Report . r.-.4 • c, ,' if No. Z301 3' 11 Date dry -pipe valve trip tested (control valve partially open) (See Trip Test Table which follows) 12 Date dry-pipe valve trip tested (control valve fully open) (See Trip Test Table which follows) 13 Date quick - opening device tested (See Trip Test Table which follows) DRY VALVE TRIP TEST TABLE Q.O.D. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. DRY PIPE Time to Trip Water Air Trip Point Time Water Reached Alarm Operated OPERATING Thru Test Pipe Pressure Pressure Air Pressure Test Outlet Properly TEST MIN. SEC. PSI PSI PSI MIN. SEC. YES NO Without Q.O.D With Q.O.D 14 Date deluge or preaction valve tested 4 9 1 I (See Trip Test Table which follows) y 7 00 TRIP TEST TABLE - 1, 1 Operation porfIEUMATIC ❑ ELECTRIC ❑ HYDRAULIC �� 1( I 1 1 Piping Supervised profES ❑ NO !Detecting Media Supervised geig ❑ NO ,4 DELUGE & Does valve operate from the manual trip and /or remote control stations gXES ❑ NO PREACTION Is there an accessible facility in each circuit for testing pr4FS ❑ NO !Method of Testing Circuits L. b A - A 1 VALVES Does each circuit operate Does each circuit um time to P p • 0 MAKE MODEL supervision loss alarm operate valve release operate release c <� YES NO YES NO YES NO C U k,'-, F 1 ,( x 1 15 See Control Valve Maintenance Table CONTROL VALVE MAINTENANCE TABLE Explain Abnormal Control Valves Number Type Open Secured Closed Signs Condition City Control Valves Bypass Valves Tank Control Valves Pump Control Valves Sectional Control Valves System Control Valves Other Control Valves Kitchen Control Valves 16 Water Flow Test at Sprinkler Riser Water Supply Source: City Tank Pump Residual Test Pipe Size of Static (Flow) Date Location Test Pipe Pressure Pressure Last Water Flow Test This Water Flow Test 17 Explain any "No" answers and comments: 18 Adjustments or corrections made during this inspection: 19 Although the comments are not the result of an engineering review, please see the attached Non - Inspection Related Deficiencies form for additional items found during the course of the inspection (only attached if applicable). Inspector's Signature: Date: 6- e 1 1 Inspection Form P2 1 301 York Ave v■ .t, N`a St. Paul, Minnesota 55130 AUTOIL 1C alts CO. (651) 558 -3300 • (800) 229 -6263 Settlug The Standard... - Tax: (651) 558 - 3310 SHEET 2 of 2 - Use separate sheet for each system inspected System No. or Description if multiple ,,, systems j . N. S` t",,r► ue l T. 3 Inspection Report No. 7 30 0-) 11 Date dry -pipe valve trip tested (control valve partially open) (See Trip Test Table which follows) 12 Date dry-pipe valve trip tested (control valve fully open) 6,- !v . / 1 (See Trip Test Table which follows) 13 Date quick - opening device tested (See Trip Test Table which follows) ( 6 DRY VALVE TRIP TEST TABLE Q.O.D. 1 .) C MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. U, k.. f i t), - !3 - ? DRY PIPE Time to Trip Water Air Trip Point Time Water Reached Alarm Operated OPERATING Thru Test Pipe Pressure Pressure Air Pressure Test Outlet Properly TEST MIN. SEC. PSI PSI PSI MIN. SEC. YES NO Without �CL-. Nu7 Q.O.D F ' n S CL1A CC with 0 • • . Q.O.D ...... / 1 0 6 ii t) t 8' ----- 14 Date deluge or preaction valve tested : (--/(). i I (See Trip Test Table which follows) TRIP TEST TABLE Operation ❑ PNEUMATIC crEEECTRIC o HYDRAULIC Piping Supervised ❑ YES 40)10 (Detecting Media Supervised oolES o NO DELUGE & Does valve operate from the manual trip and /or remote control stations g• o.'l ES o NO PREACTION Is there an accessible facility in each circuit forating goVES ❑ NO (Method of Testing Circuits 1 - t..l ►A lD VALVES k Does each circuit operate Does each circuit Maximum time to MAKE MODEL supervision loss alarm operate valve release operate release YES NO YES NO YES • • NO Cr,. at it l A- L ): X I I 's 15 See Control Valve Maintenance Table CONTROL VALVE MAINTENANCE TABLE &Plain Abnormal Control Valves Number Type Open Secured Closed Signs Condition City Control Valves Bypass Valves Tank Control Valves Pump Control Valves Sectional Control Valves System Control Valves Other Control Valves Kitchen Control Valves 16 Water Flow Test at Sprinkler Riser Water Supply Source: City Tank Pump Residual Test Pipe Size of Static (Flow) Date Location Test Pipe Pressure Pressure Last Water Flow Test This Water Flow Test 17 Explain any "No" answers and comments: 18 Adjustments or corrections made during this inspection: 19 Although the comments are not the result of an engineering review, please see the attached Non- Inspection Related Deficiencies form for additional items found during the course of the inspection (only attached if applicable). Inspector's Signature: Date: Inspection Fomi,P2 - 24 - 11 a s' 301 York Ave y■ a t, N a St. Paul, Minnesota 55130 AUTOMATIC SPIIIIIKUIR CO. (651) 558 - 3300 • (800) 229 - 6263 Setting The Standard... Fax: (651) 558 - 3310 SHEET 2 of 2 - Use separate sheet for each systeut inspected System No. or Description if multiple systems to 3 Ji Inspection Report 1 . it 7 S. T‘.14.... ( No. Z7O j>fl- 11 Date dry-pipe valve trip tested (control valve partially open) (See Trip Test Table which follows) 12 Date dry-pipe valve trip tested (control valve fully open) 6 - q - f' (See Trip Test Table which follows) 13 Date quick - opening device tested (See Trip Test Table which follows) 9 ' DRY VALVE 1 1133 TRIP TEST TABLE Q.O.D. L J- L i V MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. r1,, - N4 d ,,` - 3 , 1 AScxS 6 3 DRY PIPE Time to Trip Water Air Trip Point Time Water Reached Alarm Operated OPERATING Thru Test Pipe Pressure Pressure Air Pressure Test Outlet Properly TEST MIN. SEC. PSI PSI PSI MIN. SEC. YES NO Without Q.O.D (b lib l v 3 '5" 1 g 360. by ‘1-- With Q.O.D 1 14 Date deluge or preaction valve tested b -9- 1 / (See Trip Test Table which follows) Z 'z ? t Xf SA) j Ply TRW TEST TABLE Operation ❑ PNEUMATIC ❑erLECTRIC ❑ HYDRAULIC Piping Supervised ❑ YES uoNO (Detecting Media Supervised W ❑ NO DELUGE dr Does valve operate from the manual trip and /or remote control stations erYES ❑ NO PREACTION Is there an accessible facility in each circuit for testing ❑ YES ❑ NO (Method of Testing Circuits / - /14 VALVES Does each circuit operate Does each circuit Maximum time to MAKE MODEL supervision loss alarm operate valve release operate release YES NO YES 't t . IN a I NO YES NO • 15 See Control Valve Maintenance Table CONTROL VALVE MAINTENANCE TABLE .1 Explain Abnormal Control Valves Number Type Open Secured Closed Signs Condition City Control Valves Bypass Valves Tank Control Valves Pump Control Valves Sectional Control Valves System Control Valves , Other Control Valves Kitchen Control Valves 16 Water Flow Test at Sprinkler Riser Water Supply Source: City / Tank Pump Residual Test Pipe Size of Static (Flow) Date Location Test Pipe Pressure Pressure Last Water Flow Test This Water Flow Test 17 Explain any "No" answers and comments: 18 Adjustments or corrections made during this inspection: L AS r\ CC . ,pan (40 19 Although the comments are not the result of an engineering review, please see the attached Non-,Inspection Related Deficiencies form for additional items fo d during the course f the inspection (only attached if applicable). � L \\„.Z Inspector's Signature: l� L/ � Inspection Fort P21 -24-11 301 York Ave 1 v, rt, N� St. Paul, Minnesota 55130 AUTOMAI1C SPw.tast CO. (651) 558 -3300 • (800) 229 -6263 Setting The Standard... Fax: (651) 558 - 3310 SHEET 2 of 2 - Use separate sheet for each system inspected System No. or Description if multiple 0 systems (ku hH( (Z To ( :(a 4L . Inspection Report V\ k No. 7J Jf f 11 Date dry -pipe valve trip tested (control valve partially open) (See Trip Test Table which follows) 12 Date dry -pipe valve trip tested (control valve fully open) A - c' i (See Trip Test Table which follows) 13 Date quick - opening device tested ( Trip Test Table which follows) 6 DRY VALVE 0,dikrrtizi e tCu C TRIP TEST TABLE Q.O.D. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. flat I . 1 . , I F 0 3(R 3 - ---• -- _ DRY PIPE Time to Trip Water Air Trip Point Time Water Reached Alarm Operated OPERATING Thru Test Pipe Pressure Pressure Air Pressure Test Outlet Properly TEST MIN. SEC. PSI PSI PSI MIN. SEC. YES NO Without l Z Z L - Q.O.D � / Z f With Q.O.D .. 14 Date deluge or preaction valve tested 6 - 9 - 1 r (See Trip Test Table which follows) 2 ' ft 7 (...)4)t St.) i g v 0 t TRIP TEST TABLE Operation ❑ PNEUMATIC neLECTRIC o HYDRAULIC Piping Supervised ❑ YES q•NO !Detecting Media Supervised a l'ES o NO DELUGE Sr Does valve operate from the manual trip and /or remote control stations ES ❑ NO PREACTION Is there an accessible facility in each circuit for testing o YES ❑ NO !Method of Testing Circuits l - H A Q VALVES Does each circuit operate Does each circuit Maximum time to MAKE MODEL supervision loss alarm operate valve release operate release YES NO YES NO YES NO M. r.014 ' X 15 See Control Valve Maintenance Table CONTROL VALVE MAINTENANCE TABLE '- Explain Abnormal Control Valves Number Type Open Secured Clued Signs Condition City Control Valves Bypass Valves Tank Control Valves Pump Control Valves Sectional Control Valves System Control Valves Other Control Valves Kitchen Control Valves 16 Water Flow Test at Sprinkler Riser Water Supply Source: City Tank Pump Residual Test Pipe Size of Static (Flow) Date Location Test Pipe Pressure Pressure Last Water Flow Test . This Water Flow Test 17 Explain any "No" answers and comments: 18 Adjustments or corrections made during this inspection: 19 Although the comments are not the result of an engineering review, please see the attached Non - Inspection Related Deficiencies form for additional items found during the course of the inspection (only attached if applicable). Inspector's Signature: Date: Inspection Form P2 1-24-11 301 York Ave . V ■ Bt, N a St. Paul, Minnesota 55130 AUTOMATIC ER CO. (651) 558 -3300 • (800) 229 -6263 Setting The Standard... Fax: (651) 558 - 3310 SHEET 2 of 2 - Use separate sheet for each system inspected System No. or Description if multiple systems Inspection Report No. /$) 11 Date dry -pipe valve trip tested (control valve partially open) (See Trip Test Table which follows) 12 Date dry-pipe valve trip tested (control valve fully open) (See Trip Test Table which follows) 13 Date quick - opening device tested (See Trip Test Table which follows) DRY VALVE TRIP TEST TABLE Q.O.D. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. DRY PIPE Time to Trip Water Air Trip Point Time Water Reached Alarm Operated OPERATING Thru Test Pipe Pressure Pressure Air Pressure Test Outlet Properly TEST MIN. SEC. PSI PSI PSI MIN. SEC. YES NO Without Q.O.D With Q.O.D 14 Date deluge or preaction valve tested 6-10-11 (See Trip Test Table which follows) TRIP TEST TABLE Operation ci IEUMATIC ❑ ELECTRIC ❑ HYDRAULIC AAA 9C Piping Supervised orf ES ❑ NO (Detecting Media Supervised poYESS ❑ NO DELUGE & Does valve operate from the manual trip and /or remote control stations p►YES ❑ NO PREACTION Is there an accessible facility in each circuit for testing UXES ❑ NO (Method of Testing Circuits L oss , 'r VALVES ‘ Does each circuit operate Does each circuit Maximum time to N ,' — Lir MAKE MODEL supervision loss alarm operate valve release operate release L 0 - -35 YES I NO YES I NO YES I NO 15 See Control Valve Maintenance Table CONTROL VALVE MAINTENANCE TABLE Explain Abnormal Control Valves Number Type Open Secured Closed Signs Condition City Control Valves Bypass Valves Tank Control Valves Pump Control Valves Sectional Control Valves System Control Valves Other Control Valves Kitchen Control Valves 16 Water Flow Test at Sprinkler Riser Water Supply Source: City Tank Pump Residual Test Pipe Size of Static (Flow) Date Location Test Pipe Pressure Pressure Last Water Flow Test This Water Flow Test 17 Explain any "No" answers and comments: 18 Adjustments or corrections made during this inspection: 19 Although the comments are not the result of an engineering review, please see the attached Non- Inspection Related Deficiencies form for additional items found during the aµroe of the inspection (only attached if applicable). r � I Inspector's Signature: , Date: G -/ c.) - / Inspection Form P21 -24-11 301 York Ave v■ 1411141131 St. Paul, Minnesota 55130 AUTOMATIC wee CO. (651) 558 -3300 • (800) 229 -6263 Setting The Standard... Fax: (651) 558 - 3310 SHEET 2 of 2 - Use separate sheet for each system inspected System No. or Description if multiple systems 7, if 2 Inspection Report is .., /• au Si-t t r2 - 4tA. T /"UL C C c/ No. 7,30 } 11 Date dry-pipe valve trip tested (control valve partially open) (See Trip Test Table which follows) 12 Date dry-pipe valve trip tested (control valve fully open) (, . 4- a (See Trip Test Table which follows) 13 Date quick - opening device tested (See Trip Test Table which follows) Z t'L DRY VALVE '°I C TRIP TEST TABLE Q.O.D. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. DRY PIPE Time to Trip Water Air Trip Point Time Water Reached Alarm Operated OPERATING Thru Test Pipe Pressure Pressure Air Pressure Test Outlet Properly TEST MIN. SEC. PSI PSI PSI MIN. SEC. YES NO Without t ().3 W 0 y I vS y Z -z_`r a 1 7 Q.O.D _ 14 Date deluge or preaction valve tested L - C - ) f (See Trip Test Table which follows) y 1 ` , & t i TRIP TEST TABLE Operation ❑ PNEUMATIC goLIECTRIC ❑ HYDRAULIC Piping Supervised ❑ YES cro14O (Detecting Media Supervised oefES ❑ NO DELUGE & Does valve operate from the manual trip and /or remote control stations geYES ❑ NO PREACTION Is there an accessible facility in each circuit for testing ❑ YES ❑ NO (Method of Testing Circuits ) - If ►4 p VALVES Does each circuit operate Does each circuit Maximum time to MAKE MODEL supervision loss alarm operate valve release operate release YES NO YES I NO YES NO 6.•,/ 'Pt li V.. Y Y 15 See Control Valve Maintenance Table CONTROL VALVE MAINTENANCE TABLE Explain Abnormal Control Valves Number Type Open Secured Closed Signs Condition City Control Valves Bypass Valves Tank Control Valves Pump Control Valves Sectional Control Valves System Control Valves Other Control Valves Kitchen Control Valves 16 Water Flow Test at Sprinkler Riser Water Supply Source: City Tank Pump , Residual Test Pipe Size of Static (Flow) Date Location Test Pipe Pressure Pressure Last Water Flow Test This Water Flow Test 17 Explain any "No" answers and comments: i 18 Adjustments or corrections made during this inspection: 19 Although the comments are not the result of an engineering review, please see the attached Non - Inspection Related Deficiencies form for additional items and during the urse of the inspection (only attached if applicable). Inspector's Signature: �� 1 Date: 69 - Inspection Form P2 1-24-11 301 York Ave ... st■ N c3 St. Paul, Minnesota 55130 AUTOMATIC SPtiOtLIR CO. (651) 558 -3300 • (800) 229-6263 Setting The Standard... - Fax: (651) 558 SHEET 2 of 2 - Use separate sheet for each system inspected System No. or Description if multiple systems A sN - t3y Inspection Report 0 R tr — 7 A■cid P At(-id T PC: Z3018 11 Date dry -pipe valve trip tested (control valve partially open) (See Trip Test Table which follows) 12 Date dry -pipe valve trip tested (control valve fully open) 6-I" (See Trip Test Table which follows) 13 Date quick - opening device tested (See Trip Test Table which follows) is DRY VALVE zau6 TRIP TEST TABLE Q.O.D. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. Ui t l DRY PIPE Time to Trip Water Air Trip Point Time Water Reached Alarm Operated OPERATING Thru Test Pipe Pressure Pressure Air Pressure Test Outlet Properly TEST MIN. SEC. PSI PSI PSI MIN. SEC. YES NO Without I° 5 3 6 I C.31.4.: G. U Q.O.D With Q.O.D 1 14 Date deluge or preaction valve tested (See Trip Test Table which follows) TRIP TEST TABLE Operation ❑ PNEUMATIC ❑ ELECTRIC ❑ HYDRAULIC Piping Supervised ❑ YES ❑ NO (Detecting Media Supervised ❑ YES ❑ NO DELUGE & Does valve operate from the manual trip and /or remote control stations ❑ YES ❑ NO PREACTION Is there an accessible facility in each circuit for testing ❑ YES ❑ NO Method of Testing Circuits VALVES Does each circuit operate Does each circuit Maximum time to MAKE MODEL supervision loss alarm operate valve release operate release YES NO YES I NO YES I NO 15 See Control Valve Maintenance Table CONTROL VALVE MAINTENANCE TABLE I Expo Abnormal Control Valves Number Type Open Secured Closed Signs Condition City Control Valves Bypass Valves Tank Control Valves Pump Control Valves Sectional Control Valves System Control Valves Other Control Valves , Kitchen Control Valves 16 Water Flow Test at Sprinkler Riser ` Water Supply Source: City Tank Pump Residual Test Pipe Size of Static (Flow) Date Location Test Pipe Pressure Pressure Last Water Flow Test 1 This Water Flow Test 17 Explain any "No" answers and comments: 18 Adjustments or corrections made during this inspection: 19 Although the comments are not the result of an engineering review, please see the attached Non - Inspection Related Deficiencies form for additional items found during the course of the inspection (only attached if applicable). Inspector's Signature: Date: Inspection Form P2 1-24-11 301 York Ave V■ et. NW St. Paul, Minnesota 55130 MUt N 11C SPRINKLER CM (651) 558 -3300 • (800) 229-6263 Setting The Standard... Fax: (651) 558 - 3310 SHEET 2 of 2 - Use separate sheet for each system inspected System No. or Description if multiple systems Inspection Report )C co I? -P4 4 No. Zit? /f' 11 Date dry -pipe valve trip tested (control valve partially open) (See Trip Test Table which follows) 12 Date dry-pipe valve trip tested (control valve fully open) (See Trip Test Table which follows) 13 Date quick -opening device tested (See Trip Test Table which follows) DRY VALVE TRW TEST TABLE Q.O.D. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. DRY PIPE Time to Trip Water Air Trip Point Time Water Reached Alarm Operated OPERATING Thru Test Pipe Pressure Pressure Air Pressure Test Outlet Properly TEST MIN. SEC. PSI PSI PSI MIN. SEC. YES NO Without Q.O.D With Q.O.D 14 Date deluge or Reaction valve tested (See Trip Test Table which follows) ri - 62- L 2 U() 6 TRIP TEST TABLE Operation t .Pi iEUMATIC o ELECTRIC ❑ HYDRAULIC L v - 31. Piping Supervised p/4ES o NO (Detecting Media Supervised ar'rES o NO DELUGE & Does valve operate from the manual trip and /or remote control stations d4ES o NO PREACTION Is there an accessible facility in each circuit for testing oorES ❑ NO (Method of Testing Circuits /..c, is A-- VALVES - Does each circuit operate Does each circuit Maximum time to S MAKE MODEL supervision loss alarm operate valve release operate release YES NO 'YES NO YES NO V, fc. t= t I I 15 See Control Valve Maintenance Table CONTROL VALVE MAINTENANCE TABLE Expo Abnormal Control Valves Number Type Open Secured Closed Signs Condition City Control Valves Bypass Valves Tank Control Valves Pump Control Valves Sectional Control Valves System Control Valves Other Control Valves Kitchen Control Valves 16 Water Flow Test at Sprinkler Riser Water Supply Source: City Tank Puau> Residual Test Pipe Size of Static (Flow) Date Location Test Pipe Pressure Pressure Last Water Flow Test This Water Flow Test 17 Explain any "No" answers and comments: 18 Adjustments or corrections made during this inspection: 19 Although the comments are not the result of an engineering review, please see the attached Non - Inspection Related Deficiencies form for additional items found during the course of the inspection (only attached if applicable). Inspector's Signature: Date: Inspection Foam P2 1-24-11 4* Addle 301 York Ave v. all N a St. Paul, Minnesota 55130 AUTOMATIC SPIVIOCUIR CO. (651) 558 -3300 • (800) 229 -6263 Setting The Standard... Fax: (651) 558 - 3310 SHEET 2 of 2 - Use separate sheet for each system inspected System No. or Description if multiple systems Inspection Report -'( ti (c /(Pc No. 7,3 11 Date dry-pipe valve trip tested (control valve partially open) (See Trip Test Table which follows) 12 Date dry-pipe valve trip tested (control valve fully open) (See Trip Test Table which follows) 13 Date quick - opening device tested (See Trip Test Table which follows) DRY VALVE TRIP TEST TABLE Q.O.D. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. DRY PIPE Time to Trip Water Air Trip Point Time Water Reached Alarm Operated OPERATING Thru Test Pipe Pressure Pressure Air Pressure Test Outlet Properly TEST MIN. SEC. PSI PSI PSI MIN. SEC. YES NO Without Q.O.D With Q.O.D 14 Date deluge or preaction valve tested 6 _ t o. / 1 (See Trip Test Table which follows) TRIP TEST TABLE Operation ❑ PNEUMATIC attfCTRIC ❑ HYDRAULIC Piping Supervised ❑ YES 'Detecting Media Supervised SXES ❑ NO DELUGE & Does valve operate from the manual trip and /or remote control stations p04/ES ❑ NO PREACTION Is there an accessible facility in each circuit for testing ❑ YES ❑ NO 'Method of Testing Circuits h - H !1 VALVES Does each circuit operate Does each circuit Maximum time to MAKE MODEL supervision loss alarm operate valve release operate release YES I NO YES NO YES NO is •, .• - 4 i u cloud, X Y ° 15 See Control Valve Maintenance Table CONTROL VALVE MAINTENANCE TABLE Expo Abnormal Control Valves Number Type Open Secured Closed Signs Condition City Control Valves Bypass Valves Tank Control Valves Pump Control Valves Sectional Control Valves System Control Valves Other Control Valves Kitchen Control Valves 16 Water Flow Test at Sprinkler Riser Water Supply Source: City Tank Ptnnp Residual Test Pipe Size of Static (Flow) Date Location Test Pipe Pressure Pressure Last Water Flow Test This Water Flow Test 17 Explain any "No" answers and comments: 18 Adjustments or correction made during this inspection: 5(429(—‘ Z IOC t 1/4.)6(1n. 19 Although the comments are not the result of an engineering review, please see the attached Non - Inspection Related Deficiencies form for additio items found uring th co of the inspection (only attached if applicable). Inspector's Signature: / Date: (j - / Inspection Pam P21 -24-11 301 York Ave v , 'times . St. Paul, Minnesota 55130 AUTOMATIC SPirNKIERCp, (651) 558 -3300 • (800) 229 -6263 re Setting Whe Standard... Fax: (651) 558 -3310 SHEET 2 of 2 - Use separate sheet for each system inspected System No. or Description if multiple systems )to v' Pt 1 c &r Inspection Report ( , No. 23018 4 , . 11 Date dry-pipe valve trip tested (control valve partially open) (See Trip Test Table which follows) 12 Date dry-pipe valve trip tested (control valve fully open) - i (See Trip Test Table which follows) 13 Date quick - opening device tested (See Trip Test Table which follows) DRY VALVE TRIP TEST TABLE Q.O.D. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. 1.);14•``) F. t U; k..'y 0 - I DRY PIPE Time to Trip Water Air Trip Point Time Water Reached Alarm Operated • OPERATING Thru Test Pipe Pressure Pressure Air Pressure Test Outlet Properly TEST MIN. SEC. PSI PSI PSI MIN. SEC. YES NO Without 1 Q.O.D With j � Q.O.D r I f S tg' Li 14 Date deluge or preaction valve tested L - / (j / 1 (See Trip Test Table which follows) LJ ' 118 S V TRIP TEST TABLE Operation ❑ PNEUMATIC ❑ ELECTRIC ❑ HYDRAULIC Piping Supervised ❑ YES ❑ NO (Detecting Media Supervised ❑ YES ❑ NO DELUGE & Does valve operate from the manual trip and /or remote control stations #, ❑ YES ❑ NO PREACTION Is there an accessible facility in each circuit for testing ❑ YES ❑ NO (Method of Testing Circuits VALVES N Does each circuit operate Does each circuit Maximum time to MAKE MODEL supervision loss alarm operate valve release operate release idlidlidlial , 11 15 See Control Valve Maintenance Table CONTROL VALVE MAINTENANCE TABLE Abnormal , Control Valves Number Type Open Secured Closed Signs Condiii City Control Valves Bypass Valves Tank Control Valves Pump Control Valves ' Sectional Control Valves S Control Valves s ''. Other Control Valves Kitchen Control Valves 16 Water Flow Test at Sprinkler Riser I, *°'t Water Supply Source: City Tank Pump .1 Residual Test Pipe Size of Static (Flow) Date Location Test Pipe Pressure Pressure Last Water Flow Test This Water Flow Test 17 Explain any "No" answers and comments: 18 Adjustments or corrections made during this inspection: 19 - Although the comments are not the result of an engineering review, please see the attached Non - Inspection Related Deficiencies form for additional iteq s found during the co • • e inspection (only attached if applicable). Inspector's Signature: , , , Date: 6 -/0-ii Inspection Form P2 1-24-11