Loading...
HomeMy WebLinkAbout2003-09-26 MN State Plan Review - Montanari Office Building r" r" 00HE Witi t_' 1 I. -; )‘',- : SO - Department of Administration September 6,2003 t 3LM ( O S -N Mr Jim Butler City of Oak Park Heights 14168 Oak Park Blvd, PO Box 2007 Oak Park Height, MN 55082 Re: Plan Review Report- Montanari Building Dear Mr. Butler Enclosed you will find a copy of the plan review report for the Montanari building Project in Oak Park Heights, MN This report was generated from your request and application for plan review Dated July 16, 2003. Please review each code comment carefully. The contents of this report should be incorporated into a revised plan review report and should incorporate any local requirements you wish to add. The final plan review report should than be printed on your city letterhead (with your signature) and delivered to the permit applicant as soon as possible. The required plan review responses should than be reviewed and approved by you before authorizing complete construction on this project. If you have any questions or comments regarding this review, feel free to contact me at (651) 205 -4802 Sincer ly , .- Mike Fricke Building Code Representative 1 Building Codes and Standards Division, 408 Metro Square Building, 121 7th Place East, St. Paul, MN 55101 -2181 Voice: 651.296.4639; Fax: 651.297.1973; TTY: 1.800.627.3529 and ask for 296.9929 Plan Review Report Project Title: Montanari Building Review Date: September 6, 2003 Location: City of Oak Park Heights/Bayport Address: 13481 60 Street N Plan Review No.: Municipal 2003 -016 Date Received: July 17, 2003 Plans Examiner Michael J Fricke, MSBC Code Representative Cert. # 1548 Phone Number: 651.205.4802 Fax Number: 651.297.1973 Const. Value: Const. Doc.'s Dated: 4/18/2003 - Architectural & 4/18/2003 - Structural Addendum No.(s): None Architect: Shelly Santine Firm Name: Cundy, Santine & Associates Address: 3434 Lexington Avenue N Shoreview, MN Phone: (651) 490 -5454 Fax Number: Except as noted herein, the construction documents for the above described project have been reviewed for substantial compliance with the requirements of the proposed 2003 Minnesota State Building Code. The following code commentary should be incorporated into the contract documents for this project prior to the start of construction. Said contract documents should be revised to meet code - as necessary - before construction is started. This plan review report is a "nonstructural" code analysis based on the proposed 2003 Minnesota State Building Code. Although every attempt has been made to identify "code issues" or "concerns" for proper and necessary change, the project designer(s), the building contractor(s) and the property owner(s) are ultimately responsible for providing complete code compliance and maintaining minimum construction standards for the safeguarding of life or limb, health, public welfare and property. Comments contained within this report shall not be construed to relieve from, lessen the responsibility, or grant authorization for work in violation of any laws or ordinances of the State of Minnesota of this jurisdiction. 2 Miscellaneous Code Commentary: Note: In accordance with state law, prior to excavation or grading on any site, utilities must be located. Call Gopher State One Call at 1- 800 - 252 -1166 (651- 454 -0002 local) as soon as possible to schedule utility locations for this site. [Minnesota Statute 216D.01 to 216D.07] Note: All plumbing plans (i.e., kitchen fixture and equipment plans, DWV and water piping supply plans, RWL plans, gas and process piping plans, plumbing fixture plans and details and all exterior site utilities, including on -site septic design plans) must also be submitted to the Minnesota Department of Health, Plumbing Codes Division for separate review and approval. Further information may be obtained by contacting the MDH at 651- 215 -0836. Submit required plumbing plans to the MDH Plumbing Codes Division ASAP. [MN Rule 4715] Note: Floor plans must be submitted to the Metropolitan Council, Environmental Services Division for proper and required SAC unit determination. Submit a copy of the floor plan(s) for this project the MCES as soon as possible as a building permit cannot be issued without proper SAC unit determination. Note: Site grading, landscaping, utility installations, erosion control measures, etc. must all be completed as approved by the City Engineering Department and Planning Commission without alteration. Deviations from previously approved plans must be checked and approved by the Engineering Department and/or the City Planning Commission prior to said change. In addition, required erosion control devices must be installed and maintained throughout the construction process as approved by the City Engineering Department. [Local Codes] Note: The main job -site entrance must be posted with the project address so that it is clearly visible from the street. Said job -site address sign must be installed prior to the start of excavation and grading for the project and must be maintained in place until final occupancy. . Permanent address numbers must be installed on the front of the building for final occupancy inspection. [IBC 501.2 and IFC 505.1] Note: As part of the construction process, for the purposes of life safety, it will be your responsibility to assure that readily accessible (operable /charged) fire extinguishers will be located within the construction zone area during construction operation. Construction personnel should be made aware of where extinguishers are located and how to operate said life safety equipment. Please note that this will be verified throughout the construction process during periodic inspection. [IBC 3309] Note: Construction materials and/or equipment used or stored on this project site must be stored and placed so as not to endanger the public, workers, or adjoining property for the duration of this construction project. This will be verified throughout the construction process during periodic inspection. [IBC 3301.2] 3 • General Comments: 1 Shop drawings for the manufactured truss system(s) must be submitted to this department for code review prior installation. Said drawings must be signed/certified by a Minnesota licensed structural engineer. Submit shop drawings as soon as possible. [MSBC 1300.0130, Subpart 1, MN Rule 1800 & 1805] 2 Fire sprinkler shop drawings and hydraulic calculations must be submitted to this office for separate review and approval prior to installation of any portion of the system. Municipal water capabilities /supply, including residual and static pressure & GPM flow rate(s) of the supply line(s) must also be included in the submittal for design verification purposes. Submit required fire sprinkler information as soon as possible for separate review. [IBC Chapter 9 and NFPA 13] 3 Mechanical/Electrical /Plumbing plans were not submitted as part of your building permit application. In accordance with MSBC 1300.0130, Subpart 2 and Minnesota Rules 1800 and 1805, submittal documents, including specifications, are to include plans for mechanical, plumbing and electrical designs. Said plans must also be signed and certified by the appropriate Minnesota licensed design professional(s). Submit required signed/certified M & E documents for review as soon as possible. [MSBC 1300.0130, Subpart 2] 4 Plans must designate a specific area to be used for recycling space. Designate a recycling space on the contract document set for code review pursuant to MSBC 1303.1500. [MSBC 1303.1500] 5 A geotechnical soils investigation report was not submitted as part of the contract document submittal. Submit a copy of the geotechnical soils investigation report for this project for code review. [MSBC 1300.0130 & IBC 1802] 6 A complete site survey (certificate of survey) must be submitted for code review. The contract documents that have been submitted do not include appropriate /accurate information for proper and required code verification for a number of conditions. Submit a complete site survey for this project for code review. (Some of the issues of concern include proper /required fire department access to all areas of the building, hydrant locations, open yard conditions for allowable area computations, accessible entrances /exits, accessible parking, accessible routes to the addition, etc.) [MSBC 1300.0130] 7 Provide verification that corridor finish carpeting meets the minimum critical radiant flux of not less than a Class II level pursuant to IBC section 804.5 for interior floor finishes. [IBC 804.5] 8 Shop drawings for structural pre -cast members must be submitted for code review and record purposes. If pre -cast members are required to be fire - resistive, the appropriate testing/listing information for each member type must also be included in the submittal. Said shop drawings must also signed and certified by a Minnesota licensed Structural Engineer in accordance with MN Rule 1800 & 1805. Submit signed plans /shop drawings for all structural pre -cast (i.e., floor plank, structural columns and structural beams) for code review. [MSBC 1300.0130] 4 9 In accordance with IBC Chapter 17, a Special Inspections Agreement must be completed, signed and submitted to this office prior to permit issuance. Required special inspections must be determined by the appropriate design professional and the required third party inspection agencies must be contracted for said work. Submit a copy of a completed and signed Special Inspections Agreement for review — ASAP. [IBC Chapter 17 and MN Rule 1300.0130] 10 Verify that all wood used in direct contact with concrete or masonry will be that of a pressure treated type designed for such conditions pursuant to IBC 2304.11. [IBC 2304.11] 11 Wood members located within 8- inches of the earth must be pressure treated wood (e.g., wall studs, bottom plates and exterior wall sheathing). If the exterior finish grade is not separated from wood installations by at least 8- inches, wood members must be changed to the prescribed pressure treated as required. Verify wood/earth separations as required, or provide details of the design for code verification. [IBC 2304.11.2.2] 12 Concealed spaced formed by construction of this building will be required to be fireblocked pursuant to IBC Section 716. With the many instances of soffit construction, draftstops must be installed at 10 -foot intervals to subdivide said concealed conditions. Verify that provisions have been made to accommodate for these instances. [IBC 716] 13 Combustible attic spaces must be draft stopped so the attic is divided into area of not more than 3000 square feet. Required draftstops must be spaced no more than 60 feet apart.[IBC 716.4]. Each attic spaced form by draftstops must be made accessible by an attic access complying with IBC 1202.2 14 Glazing installed within 60- inches of the floor and within 24- inches of the vertical plane of a door (measured in the closed position) must be "safety tempered" glass. (ALL glass within 60- inches of the floor.) Verify that glass set adjacent to doors will be "safety tempered" glazing per code. [IBC 2406.4] 15 Verify that a minimum of 1- layer of 15# asphalt building paper will be installed over wood exterior wall sheathing - behind all masonry veneer as required by code. Also provide additional information on the flashing types /conditions and details at exterior wall openings or at exterior finish material changes for code review and inspection purposes. [IBC 1405.5 and ACI 530] 16 Wall finishes within 24 inches of the front and sides of water closets and urinals must be finished with a smooth, hard, non - absorbent surface material to a height of 4 -feet above the finished floor. The finish material shall be a type that is not adversely affected by moisture. [IBC 1209.2] 17 Floor finishes in toilet must be finished with a smooth, hard nonabsorbent surface that extends upward onto the walls at least 5 inches. The finish material shall be a type that is not adversely affected by moisture. [IBC 1209.1] Mn rules 1305.1209.1 18 Unless the foundation for this building is constructed on/in a well drained gravel — sand/gravel soil condition, a foundation subsurface drainage system is required to be installed. The subsurface drainage system must be installed around the entire perimeter of the building 5 foundation system (enclosing interior space) in accordance with IBC section 1806.4.2 and must discharge in accordance with MSBC 1305.1806.4.3. Provide for the required foundation drainage system at the basement/below grade perimeter of this building and submit additional plans /details of said system for further code review. [IBC 1806.4.2] 19 Roof/attic ventilation must meet the minimum ventilation area per IBC section 1202.2. Please verify that the minimum roof/attic ventilation will be provided in each attic space area per code. Submit details of vent locations /types and vent/roof area computations for further code review and verification. [IBC 1202.2] 20 A draft curtain must be installed at each elevator shaft -way opening on each level of the building per MSBC 1307. Provide for the required draft curtain outside each elevator entrance per code. [MSBC 1307.0045, Subpart 3] Exiting Comments: 21 Required exterior lighting at/near exit door stoops must be interconnected with emergency power backup as part of the required exit discharge system. Revise the electrical power plans as required to assure that emergency back -up power is interconnected with exterior lighting at/near each exit door stoop /landing per code. [IBC 1003.2.11] 22 The means of egress, including the exit discharge, must be illuminated at all times the building is occupied. Plans do not provide for required means of egress illumination. Provide for required exit illumination along each means of egress system out to and including exterior exit discharge landings. Note that an emergency backup power supply shall be provided to automatically illuminate the means of egress in the event of a power failure. IBC 1003.2.11] Fire Resistive Comments: 23 Openings in the required 1 -hour fire - resistive exterior wall assembly - adjacent to the termination conditions of the fire -wall — must be rated as 45- minute assemblies. Revise the exterior wall openings in the 1 -hour exterior wall areas at either side of the fire -wall termination condition per code and resubmit plans for review. [IBC 705.5] 24 The elevator equipment room must be constructed with walls and/or a floor /ceiling assembly that is rated the same as the elevator shaft The elevator equipment room door assembly must also be revised to be rated at Revise the fire- resistive design rating of the elevator equipment room floor /ceiling assembly and the door assembly as required so that they are the same rating as the elevator shaft per code. [MSBC 1307] 25 Openings into the elevator hoistway must be protected with approved self - closing or automatic closing smoke and draft control assemblies that have been tested to meet UL 1784. Provide for the required smoke and daft control shaft opening protection at each elevator opening per code. Submit details of how this will be accomplished for further code review. [MSBC 1305.0707.7] 6 26 The wall schedule does not include assembly listings /testing identification for exterior bearing walls of one -hour fire- resistive wall assemblies. Provide details of the 1 -hour fire - resistive (testing/listing) wall assembly for code review. [IBC 703.2] 27 Membrane penetration openings on opposing sides of a common fire- resistive rated wall assembly must be offset by a solid stud or be spaced no less than 24- inches apart when installed back to back. Please note that unless steel outlet boxes are used (for every wall opening), a listed fire - resistive outlet box must be used at each opening location. properly address fire- resistive rated wall "outlet type" membrane penetrations per code. Submit details for further code review. [IBC 711.3.2] 28 This building will have 2 -hour, fire- resistive masonry units used for part of its construction. Please identify the type of masonry block used to assemble the required fire- resistive rated assemblies and submit additional information/detail for review. [IBC 703] 29 Recessed lights, exhaust fans, outlet boxes and/or other recessed assemblies set in a fire - resistive assembly (i.e. rated floor - ceiling or ceiling assemblies) shall be designed and installed as a membrane penetration pursuant to IBC section 710. As such, they must be properly.sealed and/or boxed to provide a proper /approved membrane penetration assembly. Provide details on the types of listed assemblies used to properly seal the typical recessed fixtures installed within this building for further review. [IBC 710.2] 30 Sheet Al 0 indicates concealed spaces created by the floor /ceiling assembly these areas spaces must be sprinklered per NFPA 13. In lieu protecting these spaces with sprinkler heads the code allow for concealed spaces to be filled with non - combustible materials. Verify that these spaces are to be sprinklered or fill solid with insulation. 31 Prior to installation of any of the fire - resistive "through" or "membrane" penetration fireblock systems and any fire - resistive "joint" systems, detailed testing and installation information on each of the specific listed assemblies intend for use must be submitted to Building Official for code review. The specific assemblies must also be listed for each intended use (i.e. proper penetration size and rating condition and for the type of construction material that it is being used in/on). Each trade person responsible for sealing said conditions must provide this information to the building inspector for review prior to installation of any assembly. [IBC 703, 711 and 712] 32 None of the "joint" details located within or at termination points or intersections of required fire- resistive assemblies are identified as tested/listed assemblies Provide additional information on the tested/listed "joint" assemblies that will be used at these types of fire- resistive conditions for further code review. [IBC 703 and 712] Mechanical Comments: 33 Copies of all mechanical equipment balancing reports, orsat test results for fuel burning equipment and start-up certifications must be supplied to the city inspections department as soon as possible upon completion of said work. [MSBC /IMC 1346.M309.2.3] 7 34 Note that MN Rules 1346 (International Mechanical Code /International Fuel Gas Code) requires all gas piping to be tested at a minimum of 25 PSI for no less than 1/2 hour. Please schedule this testing accordingly. New gas lines may not be placed into service until this testing is complete. [MSBC 1346.G406.4.1] 35 Gas meter locations may require pipe bollard protection devices if located such that they are subject to damage. Gas meters and/or regulator equipment adjacent to vehicle drives or parking areas must be protected as required by the code. Provide for the required protective devices as necessary. Please note that these devices must be installed before final inspection of the building. [MSBC /1MC 1346.M304.9] 36 Mechanical equipment that is subject to damage will require pipe bollard or other protective devises when located such that it is subject to damage. HVAC equipment installed adjacent to or within vehicle drives or parking garages /areas must be protected as required by the code. Provide for the required protective devices as necessary at HVAC equipment. Please provide additional information/details on said devices for review. (Note: These devices must be installed for final inspection of the building.) [MSBC /IMC 1346.M304.9] 37 Verify that at least 10 -feet of separation will be provided between any HVAC exhaust vent, and openings into the building and HVAC system fresh air supply /intake on the buildings' . [UMC 706(0] Fire Code Comments: 38 Fire sprinkler shop drawings and hydraulic calculations must be submitted to this office for separate review and approval prior to installation of any portion of the system. Municipal water capabilities /supply, including residual and static pressure & GPM flow rate(s) of the supply line(s) must also be included in the submittal for design verification purposes. Submit required fire sprinkler information as soon as possible for separate review. [IBC Chapter 9 and NFPA 13] 39 During construction, fire extinguishers must be located on site at each stairway on all floor levels of the building and in every storage and construction shed. A fire extinguisher must also be located where special hazards exist (such as flammable or combustible liquid storage areas). Installation/locations of required construction extinguishers must be verified with the field inspector during construction. Maintenance of required on -site construction extinguishers will be verified throughout the construction process during periodic inspection. Provide for the required construction extinguishers per code. [IBC 3309] 40 "No Parking — Fire Lane" signs must be installed as indicated on the approved plan. Verify exact location and number required with the City Fire Marshal. Said signage must be installed prior to the final occupancy inspection of this structure. [IFC 503.3] 41 The location, size and type of required fire extinguishers for this project must be verified with the City Fire Marshal. Required fire extinguishers must be installed prior to final 8 occupancy inspection of this structure. Verify fire extinguisher conditions /locations with the local Fire Marshal prior to installation. [IFC 901.4.3 & NFPA Standard 10] 42 This building must be provided with a fire department key (knox) box for access to master keys for the entire facility. The type of key box and the required installation location must be verified with the Fire Marshal. Contact the Fire Marshal for verification of the type and location of the required key (knox) box. Said key box must be installed for final inspection of this project. [IFC 506] 43 Each building/tenant space /suite must be signed at the front entrance with the appropriate building address and/or suite identification for final building inspection and issuance of the Certificate of Occupancy. Addressing/identification must be completed prior to the final building inspection. [IBC 501.2 and IFC 505 and 408.11.2] 44 Shop drawings for the fire alarm system must be submitted to the Fire Marshal for separate review and construction authorization. Submit required fire alarm system plans and specifications as soon as possible (prior to installation). [MSBC 1300.0130] 45 The fire - sprinkler fire- department connection (OS & Y) must be located on the main street side of the building near the building's main entrance (unless another location has been authorized by the Fire Marshal). Provide further information on the proposed location of the OS & Y connection for department verification per code. [IFC 912] Enemy Comments: Energy calculations which clearly evidence that the new building areas comply with either the prescriptive of performance provisions of the Energy Code (MSBC 7676) must be submitted for review. Submit necessary thermal energy envelope computations for code review and verification. [MSBC 7676.0700] Identify the "R" and /or "U" values of all required exterior envelope construction material and insulation on/within the building for code review conditions. All construction material/building insulation materials must be properly /clearly identified (on the plan sheets) with the proper thermal "R" and/or "U" value for energy code verification and inspection purposes. Provide required information for review. [MSBC 7676.0600] Verify that proposed fenestration products meet the minimum performance standards set out be MSBC 7674.0700, Subpart 3 for each new window or door installation. Provide manufacturer data to substantiate the requirement. [MSBC 7676.0700] Provide for required "wind- wash" insulation blocking at exterior wall line areas within the attic. A wind -wash barrier must be installed (to block out wind intrusion in the insulation at these attic areas) throughout the space. Verify that a vertical "sheathing" membrane will be installed at attic /exterior wall edge conditions to form the required wind -wash barrier per code. [MSBC 7676.0600] 9 An interior air barrier must be installed at all exterior wall and/or roof/ceiling membrane areas of the building. The required air barrier must also be installed so that it is continuously sealed at all penetrations, including electrical boxes, plumbing penetrations, framed wall components and at the floors, walls and ceiling intersections of exterior walls and roof/ceilings. The air barrier must also be sealed at intersections of all interior - exterior wall connections and interior - exterior wall and roof/ceiling interconnections. Revise the plans and/or specifications as necessary to incorporate the required air barrier at exterior /perimeter walls and ceiling areas of the building and provide details for code review. [MSBC 7674.0600] Accessibility Comments: 1. Verify that tactile signage (restrooms, directories, room identification, etc.) will be designed and installed per MSBC 1341.0405, Item P and 1341.0476. All required tactile signage must be installed for final inspection and issuance of the Certificate of Occupancy. [MSBC 1341.0405 & 1341.0476] 2. Equipment controls (or a portion thereof) such as electrical outlets, alarm pulls, switches, and elevator controls and similar equipment and devices will be installed per code and or revise details as necessary. [MSBC 1341.0470 and 1341.0420, Subpart 5 and 6 and 1341.0405, Item M] 3. Verify that a "lever" or "paddle" style hardware system (accessible) will be installed at each door that requires accessibility. [MSBC 1341.0442, Subpart 9] 4. Provide a minimum 18 inch landing on latch side of door number D206. Submit required plan review information, including revised plans, details, specifications, Addenda's, or Change Orders (as required herein) as soon as possible for completion of this review process. If I can be of any further assistance please feel free to contact me at (651) 205 -4802 Thank you, Michael Fricke Building Code Represntative 10