HomeMy WebLinkAboutFP 2012-00071 Fire Alarm Monitoring System Change Out CITY OF OAK PARK HEIGHTS PERMIT NO.: 2012 -00071
14168 OAK PARK BLVD. N. #2007
OAK PARK HEIGHTS, MN 55082 -2007 DATE ISSUED: 04/30/2012
(651) 351 -1661 FAX: (651) 439 -0574
ADDRESS : 5903 NEAL AVE N
PIN : 06- 029 -20 -11 -0012
LEGAL DESC : OAK PARK PONDS ADDITION
: LOT 6 BLOCK 1
PERMIT TYPE : FIRE " ROTECTION
PROPERTY TYPE : COMMERCIAL
CONSTRUCTION TYPE : FIRE PROTECTION
VALUATION : $ 4,473.35
NOTE: WORK SHALL COMPLY WITH ALL ADOPTED CODES, DEVICE SPECIFICATIONS, AND APPROVED PLAN. PERMIT ISSUED
FOR INSTALLATION OF FIRE ALARM SYSTEM TO MONITOR BLDG WATER FLOW & HVAC UNITS, WITH PULL STATIONS AND 8
SPRINKLER HEADS, IF RQD.
APPLICANT FIRE PROTECTION BASE FEE 111.25
FIRE PROTECTION PLAN REVIEW 72.31
ALWAYS SECURE ALARM PROTECTION INC. STATE SURCHARGE - BUILDING 2.24
670 PEHHAM BLVD.
STE. 201 TOTAL 185.80
ST. PAUL, MN 55114- PAID WITH CHECK # 10743
(612) 728 -0000
Minnesota State License #: TS000679
OWNER
NEW HORIZON ACADEMY
3405 ANNAPOLIS LN. N.
STE. 100
PLYMOUTH, MN 55313 -
AGREEMENT AND SWORN STATEMENT
The work for which this permit is issued shall be performed
according to: (1) the conditions of this permit; (2) the
approval plans and specifications; (3) the applicable city
approvals, Ordinances, and Codes; and, (4) the State Building
Code. This permit is for only the work described, and does
not grant permission for additional or related work which
requires separate permits. This permit will expire and become
null and void if work is not started within 180 days, or if work
is suspended or abandoned for a period of 180 days any time
after work has commenced. The applicant is responsible for
assuring all required inspections are requested in conformance
with the Minnesota State Building Code.
SEPARATE PERMITS REQUIRED FOR WORK OTHER THAN DESCRIBED ABOVE.
flat.
Bayplirt Fri D
284 N. 3rd Street • Bayport, MN. 55M13 • Hal MI 275-4401 • Fax MU
AYPOR
MINNESOTA
Fire Inspection Review
Date: 4/27/12
Job: New Horizon's - 5903 Neal Ave. N - Fire Alarm Plan Review
Page # Item Comments Corrective action
{ Crib Add smoke detector to this room as it is a
All area sleeping area. Add smoke detector
Discussed adding a pull station to the
kitchen near the rear door. Was advised
Kitchen by installer that the door has been comment
removed from the plan.
Discussed with installer that the kitchen Kitchen hood fire
Kitchen hood fire notification devices would be suppression to be tied
tied into the alarm panel and would set !
into building alarm.
off a building alarm.
Double action pull stations are being ! Local alarm covers to
Pull installed. Advised the installer that local be installed by building
stations alarm covers would be required and the tenants if the pulls
responsibility of the tenants if the pulls become a tamper
become a tamper issue. issue.
4-27-12