HomeMy WebLinkAbout2012-08-22 Pipe Dream Plumbing RPZ 5-Yr Rebuild Test Sheets Test Sheet
5590 noyvkriA PIL Ut
Client Boatwell Landing pipe Dream
Address 5.686Norwich Parkway
City Oak Park Heights
Plumbing MN MN Inc
Zip 55082
Owner /Contact Jim Armstrong/Presbyterian 61296418
Homes
Phone 651- 775 -5859
Fax
Municipality 'PEST #
Test Date: 08/22/2012
Location of Device: IL Garbage Room
Serves:
Make and Model Size Serial # Yr
Wilkins 975XL .75" 1298744 RBLD
Check Check Pres. Dif Across Pres. Dif Across Strainer
Valve #1 Valve #1 Check Relief Valve
#2
Test Before Leaked Leaked psi _ psi None ( )
Repair Closed- Closed Cleaned ( )
Describe Repair: 5 year rebuild
Final Test Leaked Leaked 8.6 psi 4.0 psi
Closed Closed'
Materials Used:
Certification:
I hereby certify the foregoing data to be correct and that the tested device is functioning
within the limits of the standards.
Firm Name: Pipe Dream Plumbing Inc. 3333 Emerson Ave S, Mpls., MN 55408
By: Thomas Sidla Backflow Tester Certification # 063692 -BF
Remarks:
Pipe Dream Plumbing, Inc 3333 Emerson Ave S, Mpls., MN 55408 Fax: 763 - 434 -4103
Test Sheet
5590 ncrc Lthich PIC.Luj
Client Boatwell Landing pipe Dream
Address ,se90 Norwich Parkway
City Oak Park Heights
MN MN plumbing Inc
Zip 55082
Owner /Contact Jim Armstrong 612 -396,4798
Phone 651- 775 -5859
Fax
Municipality TEST #
Test Date: 08/22/2012
Location of Device: IL Trash Room
Serves: Shoot
Make and Model Size Serial # Yr
Wilkins 975XL .75" 1298714 RBLD
Check Check Pres. Dif Across Pres. Dif Across Strainer
Valve #1 Valve #1 Check Relief Valve
#2
Test Before Leaked Leaked psi psi None ( )
Repair Closed- Closed Cleaned ( )
Describe Repair: year year rebuild
Final Test Leaked Leaked _10.1 psi _3.6 psi
Closed
Materials Used:
Certification:
I hereby certify the foregoing data to be correct and that the tested device is functioning
within the limits of the standards.
Firm Name: Pipe Dream Plumbing Inc. 3333 Emerson Ave S, Mpls., MN 55408
By: Thomas Sidla Backflow Tester Certification # 063692 -BF
Remarks:
Pipe Dream Plumbing, Inc 3333 Emerson Ave S, Mpls., MN 55408 Fax: 763 - 434 -4103
Test Sheet
Ss90 ilvuo
(IL
Client Boatwell Landing pipe Dream
Address . ,568INorwich Parkway
City Oak Park Heights
MN MN plumbing Inc
Zip 55082
Owner /Contact Jim Armstrong
612- 396198
Phone 651- 775 -5859
Fax
Municipality TEST #
Test Date: 08/22/2012
Location of Device: IL Boiler Room
Serves: Boiler Feed
Make and Model Size Serial # Yr
Wilkins 975XL .75" 1293783 RBLD
Check Check Pres. Dif Across Pres. Dif Across Strainer
Valve #1 Valve #1 Check Relief Valve
#2
Test Before Leaked Leaked psi psi None ( )
Repair Closed- Closed Cleaned ( )
Describe Repair: 5 year rebuild
Final Test Leaked Leaked _9.0 psi _3.7 psi
Closed ose
Materials Used:
Certification:
I hereby certify the foregoing data to be correct and that the tested device is functioning
within the limits of the standards.
Firm Name: Pipe Dream Plumbing Inc. 3333 Emerson Ave S, Mpls., MN 55408
By: Thomas Sidla Backflow Tester Certification # 063692 -BF
Remarks:
Pipe Dream Plumbing, Inc 3333 Emerson Ave S, Mpls., MN 55408 Fax: 763 - 434 -4103