HomeMy WebLinkAbout2013 ECSI Fire Alarm Inspection Report�ECSI- Fire Alarm Inspection and Testing Form
Sygatosrt Date 7/24/2013 [Completion Date 7/24/13 Doc: INSP -A
1. Property information:
Name of Property: city of Oak Park Heights
(Address: 14168 Oak Park Blvd. North P.O. Box 2007 Oak Pak Heights,MN 55082 I
IDescription of Property: office Building
Occupancy Type: office
Name of Property Representative: Gary Brunckhorst
Address:
Phone: 651 - 439 -4439 Fax: E -mail.
Authority having Jurisdiction over this Property: Oak Park Hts
Phone: i Fax: E -mail.
2. Installation, Service and Testing Contractor Information:
Electronic Communication Systems, LLC
2300 Territorial Road
St. Paul, MN, 55114 Inspection Frequency 1
Phone: (651)- 735 -7470 Fax: (651) 735 -7471
Inspector Name Mark Bierbrauer Qualification JT
An Inspection Contract is in effect as of Contract Expires
3. Type of System or Service: ❑X Fire ❑ EvACS ❑ MINIS ❑ Other
❑ UL X NFPA NFPA Edition: ❑ Cert. of Completion ❑ UL Initial Cert
Interval of this Inspection: ❑X Annual ❑ Quarterly 0 ❑ Semi Annual
Monitoring Data: Monitoring Type: ❑X NFPA ❑ UL
1A Monitoring Contract is in Effect as of
IMonitoring Contractor Name Diaaold ACT #4545
Receiver Ph. Line # 1- 800 - 643 - 9216/1- 330 - 498 -2163
Monitoring Contract Expiration
Date
Central Station # 1- 800 - 548 -4478
System Ph Line 1 651 - 430 -1767 System Ph Line 2 651 - 689 -0154
Dialer manufacturer Notifier Model #: NFS2 -100
Dialer Location L.L. systems Room Breaker Location Electrical Rm
Number of Zones SLCi (DACT gaff T sealed Lead Software Rev. Date 3.1
Type Acid
Prior To Testing Notifications: ❑X Central station ❑X Building ❑ AHJ
3. Type of System or Service (continued)
3.2 Control Unit 1 ❑X Standard ❑ Audio Evac
Manufacturer Notifier
Software Rev 3.1
Zones or Data Loops 1 SLC
Printer Interface Serial
Other na
3.3 Control Unit 2 ❑ Standard ❑ Audio Evac
Manufacturer na
Software Rev na
Zones or Data Loops na
[Printer Interface na
FOther na
3.4 System Documentation
❑ UL Cert. Posted ❑X Drawings on site
❑X System Up- loaded ❑X Manual on site
4. System Power
4.1 Controls
Model #
NFS2 100
Manufacture Date
Audible Circuits 4
Printer Type. na
Other na
IModel # na
Software Rev Date na
Audible Circuits na
Printer Type. na
Other na
❑ All Labels Placed
Control #1 LL Systems primary Pwr 120VAC Breaker Elec Rm
Location Room Loc
Control #2 na Primary Pwr na Boc ker na
Location
4.2 Engine Driven Generator
Manufacturer: na
Fuel Type: na
4.3 Uninterruptible Power Supply
Equipment powered by UPS: na
❑X This System does not have a generator
FLocation77a
Fuel Location: na
0 This System does not have a UPS
Location of UPS: na Calculated Capacity of UPS:na
Standby Mode (hrs): na Alarm Mode (min): na
4. System Power (continued)
4.4 Batteries (Control 1)
Location FACP Type ACalded Lead Voltage 2 /12VDC Amp /Hr 7.5
Calc. Capacity in Standby (hrs) 24 Calc. Capacity in Alarm Mode (min) 5
❑ Batteries are marked with Date of manufacture
4.5 Batteries (Control 2)
Location na Type na Voltage na Amp /Hr na
1Calc. Capacity in Standby (hrs) na Calc. Capacity in Alarm Mode (min) na
❑ Batteries are marked with Date of manufacture
4.6 Remote Power Supplies
Location 1
Location 2
Location 3
Location 4
Location 5
Location 6
Public Works
Building
na
na
na
na
na
Batt Amp /Hr
Batt Amp /Hr
Batt Amp /Hr
Batt Amp /Hr
Batt Amp /Hr
Batt Amp /Hr
7.5 AH
na
na
na
na
na
Location AC
Location AC
Location AC
Location AC
Location AC
Location AC
Electrical Rm
na
na
na
na
na
5. Annunciators
Location
Location
Location
Location
Main Entrance
na
na
na
❑ This System Does Not have annunciators
6. Notifications Made Prior to Testing
Central Station
Building management
Building Occupants
Authority having Jurisdiction
Other, If Required
Contact
Time
Other note
DiaBold
8:30:00 AM
Gary
8:30:00 AM
All
8:30:00 AM
na
na
7. Data Updates
❑ System Data on this Form did not require updating at the time of this inspection
0 System Data had changed and required updating ❑ Devices or Components Added
❑ Control Changes or Replaced ❑ Devices or Components Removed
❑ Device Changes ❑ See Separate Form for Changes
Reason For Changes
New Test
7.1 Device Counts:
Fire Alarm Initiating Devices and Circuit Style
Manual Pull Stat.
Ion Detectors
Photo Detectors
Duct Detectors
Heat Detectors
Beam Detectors
Supervisory Switches
Other:
Other:
Quantity Of
MFG
Model
Circuit Style
Other:
1
Notifier
NBG12LX -100
SLC -4
na
Notifier
FRM -1
SLC4
5
Notifier
Acclimate
SLC -4
23
Notifier
FSP -851R
SLC -4
Some Are Smoke Det
Programmed as Duct Det7
na
na
na
na
na
Alarm Indicating Devices:
Bell
Horns
Horn /Strobes
Strobes
Speakers
Speaker /Strobes
Chimes
Other:
Quantity Of
MFG
Model
Circuit Style
Other:
na
Notifier
FRM -1
SLC4
na
Notifier
FRM -1
SLC4
22
Wheelock
HSR
Y
12
Wheelock
STR
Y
na
na
na
Ina
Building Control Interface
Air Handlers
Dampers
Elevator Recall
Time Out Rooms
Quantity Of
MFG
Model
Circuit Style
Other:
1
Notifier
FRM -1
SLC4
22
Notifier
FRM -1
SLC4
2
Notifier
FRM -1
SLC4
na
na
na
na
na
Supervisory Devices and systems
=ire Pump Pwr
Fire Pump Running
Fire Pump Auto Pos
Fire Pump /Controller Trbl
Generator in Auto Pos
3enerator /Controller Trouble
Switch Transfer
Generator Transfer
Flow Switch
Tamper Switch
Post Indicator Valve
Pressure Switches
Quantity
MFG
Model
Circuit Style
Other:
na
na
na
na
na
na
na
na
2
Notifier
FMM -1 (100)
SLC4
2
Notifier
FMM -1 (100)
SLC4
SLC4
na
na
na
Other
na
Other
na
Other
na
na
na
Code:
na
Code:
na
Code:
na
Bldg. Interfaces
Door mags
Door Holders
Fire Curtains
Kitchen Hoods
Pre - Action systems
Gas /CO Detection
Bldg. Temp
Freezer / Cooler
Boiler
Quantity
MFG
Model
Circuit Style
Other:
na
na
na
na
na
na
na
na
na
Agent Release System
1
Notifier
FMM - 1(100)
SLC4
na
8. Testing Results
8.1 Control Unit and Related Equipment
Description
Visual
Inspection
Functional
Test
pass
Fail
N/A
Comments
Control Unit
❑X
❑X
❑X
❑
na
Lamps, LED's, LCD's
❑X
❑X
❑X
❑
❑X
Fuses
X
X
X
❑
I ❑
Trouble Signals
❑X
❑X
❑X
❑
❑
Disconnect Switches
❑X
❑X
a
❑
❑
Ground Fault Monitor
X
X
FX1
❑
❑
Supervision
X
X
0
❑
❑
Local Annunciators
X
X
X
❑
❑
Remote Annunciators
X
X
X
❑
❑
Remote Pwr. Supplies
X
X
X
❑
❑
Isolation Modules
❑
❑
❑
❑
❑X
Other (Specify)
❑
❑
❑
❑
X
8.2 Control Unit Power Supplies
Description
Visual
Inspection
Functional
Test
pass
Fail
NSA
Comments
120 volt Power
❑X
❑X
❑X
❑
na
Generator or UPS
❑
❑
❑
❑
❑X
Battery Condition
X
X
X
❑
I ❑
Load Voltage
X
X
X
❑
❑
Discharge Test
X
X
X
❑
❑
Charger Test
X
X
X
❑
❑
Other (Specify)
❑
❑
❑
❑
❑
8.3 In Building Fire Emergency Voice Alarm Communication Equipment
Description
Visual
Inspection
Functional
Test
pass
Fail
N/A
Comments
Control Unit
❑
❑
❑
❑
na
Lamps, Leds, LCD's
❑
❑
❑
❑
❑X
Fuses
❑
❑
❑
❑
X
Primary Power Supply
❑
❑
❑
❑
❑X
Secondary Power Supply
❑
❑
❑
❑
X
Trouble Signals
❑
❑
❑
❑
X
Disconnect Switches
❑
❑
❑
❑
X
Ground Fault Monitor
❑
❑
❑
❑
❑X
Panel Supervision
❑
❑
❑
❑
x
8.3 Evac Continued
Sound Pressure Levels
Occupied
Ambient dBA
Alarm dBA
❑ Visual
❑ Yes
na
Ina
8.4 Notification Appliance Power Extender Panels
❑ Functional
❑ No
❑ Passed ❑ Failed
Description Visual Functional
Inspection Test
pass
Fail
NIA
Comments
Lamps, LCDs, LEDs ❑X ❑X
❑X
❑
❑
Fuses 0
F
❑
❑
Primary Power supply X
❑X
❑
❑
Secondary Power supply 0
0
❑
❑
Trouble Signals 0
X
❑
❑
Ground Fault Monitoring X
X
❑
❑
Panel Supervision X
X
❑
❑
Other (Specify) ❑ ❑
❑
❑
X
8.5 Mass Notification Equipment ❑X This Section Does Not Apply to this System or Facility.
Description Visual Functional
Inspection Test
pass
Fail
N/A
Comments
Functional Test ❑ ❑
❑
❑
❑X
Reset/Power down test ❑ ❑
❑
❑
X
Fuses [I El
❑
❑
Primary Power Supply ❑ ❑
❑
❑
❑X
UPS Power Test ❑ ❑
❑
❑
X
Trouble Signals ❑ ❑
❑
❑
X
Disconnect Switches ❑ ❑
❑
❑
0
Ground Fault Monitoring ❑ ❑
❑
❑
0
CCU Security Mechanism ❑ ❑
❑
❑
❑X
Prerecorded message content ❑ ❑
❑
❑
❑X
Recorded message activation ❑ ❑
❑
❑
❑X
Software backup Performed ❑ ❑
❑
❑
X
Test backup software ❑ ❑
❑
❑
IX
❑ ❑
❑
❑
❑X
❑ ❑
❑
❑
❑X
❑ ❑
❑
❑
0
❑ ❑
❑
❑
X
Other:
❑ ❑
❑
❑
X
8. 0 Testing Results (continued)
8.5 Mass Notification Equipment (continued) ❑X This Section Does Not Apply to this System or Facility.
Sound Pressure Levels ❑ Visual ❑ Functional
Occupied ❑ Yes ❑ No
Ambient dBA na
Alarm dBA na
System Intelligibility
❑ CSI ❑ STI
❑ Visual ❑ Functional
8.6 Two -Way Communication Equipment ❑ This Section Does Not Apply to this System or Facility.
Description Visual Functional
Inspection Test
pass
Fail
N/A
Comments
Phone Handsets ❑ ❑
❑
❑
❑x
❑
Phone Jacks ❑ ❑
❑
❑
0
❑
Off Hook Indicator ❑ ❑
❑
❑
0
❑ ❑
Call in Signal ❑ ❑
❑
❑
X
System Performance ❑ ❑
❑
❑
System Audibility ❑ ❑
❑
❑
0
System Intelligibility ❑ ❑
❑
❑
0
Radio Communications ❑ ❑
❑
❑
X
Area of Refuge comm. system ❑ ❑
❑
❑
0
Elev. Emergency Comm. System ❑ ❑
❑
❑
X
Other(specify) ❑ ❑
❑
❑
0
8.7 Combination Systems
❑X This Section Does Not Apply to this System or Facility.
Description Visual Functional
Inspection Test
Pass
Fail
N/A
Comments
Fire Extinguishing Monitoring El ❑
Devices /system
1:1
F-1
0
❑
Phone Jacks ❑ ❑
❑
❑
0
❑
Off Hook Indicator ❑ ❑
❑
❑
0
❑ ❑
Call in Signal ❑ ❑
❑
❑
❑X
8.0 Testing Results (continued)
8.8 Special Hazards
Description Visual Functiona pass I Fail I N/A Comments
na
❑ ❑
❑
❑
na
❑ ❑
❑
❑
na
❑ ❑
❑
❑
na
❑ ❑
❑
❑
8.9 Emergency Communication System
❑ Visual ❑ Simulated Operation
❑ Functional ❑ Ensure predischarge notification appliances of special hazard systems are
not overridden by the MNS.
R in Mnnitnrprl Svstpms
Description Visual Functional
Inspection Test
pass
Fail
NIA
Comments
Engine Driven Generator ❑ ❑
❑
❑
❑X
Fire Pump ❑ ❑
❑
❑
x
Special suppression systems ❑X ❑
❑
❑
❑
Tested By Others
Other
❑X
❑ ❑
❑
❑
❑
❑
Flow Sw:
Quant:2
❑X ❑X
❑X
❑
❑
❑X
Tamper:
Quant:2
❑X
❑X
❑
❑
Elevator Shunt Trip ❑ ❑
Test Type: Flow ❑ Electronic ❑X
❑
1 ❑
❑
MNS override of FA signals ❑ ❑
Srinkler Test by:
F
Date:
R 11 Aiiviliary Functons
Description Visual Functional
Inspection Test
pass
Fail
NIA
Comments
Door Releasing Devices ❑ ❑
❑
❑
❑X
Fan Shutdown 0 a
0
❑
❑
Smoke management control ❑ ❑
❑
❑
❑X
Smoke Damper Operation ❑X ❑X
❑X
❑
❑
Smoke Shutter Release ❑ ❑
❑
❑
19
Door Unlocking ❑ ❑
❑
❑
❑X
Elevator Recall 0 ❑
❑
❑
❑
No key for reset
Elevator Shunt Trip ❑ ❑
❑
❑
X
MNS override of FA signals ❑ ❑
❑
❑
a
Other
❑ ❑
❑
❑
❑X
Other
❑ ❑
❑
❑
❑X
Other
❑ ❑
❑
❑
0
Other
❑ ❑
❑
❑
❑X
8.12 Alarm Initiating Device
❑X Device test results sheets attached listing all devices counted, tested and results
8.13 Supervisory Alarm Initiating
Device ❑X Device test results sheet attached listing all devices counted, tested and results
8.14 Alarm notification Appliances
❑X Appliance test results sheet attached listing all appliances counted, tested and results
8.0 Testing Results (continued)
8.15 Supervisory Station Monitoring
Description Visual Functional Time Signal
Time Signal Comments
inspection iesl
Alarm Signal ❑X ❑X
aern
12: 08pm
12: 08pm
AHJ
Alarm Restoration a ❑X
2: 44pm
2: 44pm
All
Trouble Signal 0
12: 30pm
12: 30pm
4:30pm
Trouble Restoration 0
2: 47pm
2: 47pm
Supervisory Signal X
12: 36pm
12: 36pm
Supervisory Restoration
2: 44pm
2: 44pm
9.0 Notification that Testing is Complete
Name:
Time:
Monitoring Org.
Building Mngt.
Building Occupants
AHJ
Other
DieBold
Gary
All
4:30pm
4:30pm
4:30pm
10. System Restored to Normal Operation
Date 7/25/13
Time 4:30 PM
11. System Operational or Repair Deficiencies.
❑X No Deficiencies were noted at the time of this inspection
❑ Deficiencies were noted at the time of this inspection. ( See included deficiency report)
❑ Deficiencies noted were not corrected at the time of inspection
❑ Deficiencies noted were corrected at the time of Inspection
❑ Repairs Denied by customer
❑ ** SYSTEM RED TAGGED. (System out of Service) IMMEDIATE ACTION REQUIRED.
Repairs Corrected on:
12. Certification
12.1 Inspector Certification
Inspector Name Mark Bierbrauer
12.2 Owner or Rep. Acceptance
Date: 7/25/13
Signature Printed Name Organization Date
ECSI - Facility Fire Alarm Device Location And Test Log
Address
Location
_ Type
Visual
Funct.
Pass
Fail
Comments
CITY OF OAK PARK HTS
Test
1D001
—
EVIDENCE ROOM 19
-
Sup.L(DUCTP)
X
X
X
1D002
EVIDENCE ROOM 19
Sup.L(DUCTP)
X
-_
X
!X
-
1D003
LlDO04
L1D 005
EVIDENCE ROOM 19
EVIDENCE ROOM 19
L.LEVEL HALL /EVIDENCE
Sup.L(DUCTP)
Sup.L(DUCTP)
Sup.L(DUCTP)
IX
X
X
x
X
X
X
X
X
L1 D006
__-
L.LEVEL MENS ROOM
Sup.L(DUCTP)
_
X-
X
x—
L1 D007
VOTING STORAGE ROOM
Sup.L(DUCTP)
X
X
L1 D008
VOTING STORAGE ROOM
Su .L DUCTP
X
X
LlDO09
VOTING STORAGE ROOM
!Sup.L(DUCTP)
X
X
X
L1D010
L.LEVEL HALL ARCHIVE
Sup.L(DUCTP)
X
X
X
L1 D012
L.LEVEL HALL ARCHIVE
Sup.L(DUCTP)
__
X
X
X
L1D013
L.LEVEL MECH /ELEC
Sup.L(DUCTP)
X
X
X
L1 D014
EVIDENCE /BY GARAGE
Sup.L(DUCTP)
X
X -
X
LlDO151
EVIDENCE RM 19
Sup.L(DUCTP)
X
X
IX
L1 D016
AT FACP _
SMOKE(PHOTO)
X
X
X
L1 D018
I PUBLIC WORKS
PHO
SMOKE(PHOTO)
( )
X
X
X
Ll 5
-
N EL CHAMBERS
Su pOKE
TO .L DUCTP
X
X
X
L1D026
-
COUNCEL CHAMBERS
'Su .L DUCTP
()
X
X
X
L1 D027
L-1 D030
CONF.BY ROTUNDA
ELEV LOBBY L.LEVEL
Sup.L(DUCTP)
SMOKE(PHOTO)
X
X
X
X
X
X
L1D031
l D
L1 D032
ELEV LOBBY ST FL
- --
ELEV EQUIP ROOM
SMOKE(PHOTO)
SMOKE(PHOTO)
'X
X
X
X
X
X
_.
L1 D037
L.LEVEL MECH /ELEC
Sup.L(DUCTP)
X
X
X
_
LlD042
ABOVE FINANCE
Sup.L(DUCTP)
X
X_
X_
L1 DO-43
ABOVE FINANCE
Sup.L(DUCTP)
X
X
L1 D044
P.D.FILE ROOM —Sup.L(DUCTP)
_X
X
X
X
L1 D045
- --
P.D.FILE ROOM
Sup.L(DUCTP)
X
X
X
L1 D046
-- - --
ABOVE WORK ROOM
Sup.L(DUCTP) -
X --
X
X
- --
L1 M001
DAMPER EVIDENCE ROOM 19
RELAY
X
X
X
MONITORING ADD =160
L1M002
DAMPER EVIDENCE ROOM 19
RELAY
X
X
X
MONITORING ADD =161
L1M003
DAMPER EVIDENCE ROOM 19
RELAY
X
X
X
MONITORING ADD =162
L1M004
DAMPER EVIDENCE ROOM 19
RELAY
X
X
X
MONITORING ADD =163
L1M005
L.LEVEL HALL /EVIDENCE
RELAY
X
X
X
MONITORING ADD =164
L1 M006
L.LEVEL MENS ROOM
RELAY
X
X
X
MONITORING ADD =165
L1 M007
VOTING STORAGE ROOM
1 RELAY
X
x
X_
MONITORING ADD =166
L1 M008
VOTING STORAGE ROOM
-
CRELAY
X
X
X
MONITORING ADD =167
L1 M010
L.LEVEL HALL ARCHIVE
RELAY
X
X
X
MONITORING ADD =169
L1 M012
L.LEVEL HALL ARCHIVE
RELAY
X
X !X
MONITORING ADD =171
L1M013
L.LEVEL MECH /ELEC
RELAY
X
X
X
MONITORING ADD =172
L1 M014
UM-015
EVIDENCE BY GARAGE
RELAY
--X-----X---
X
X
X
MONITORING ADD =173
EVIDENCE BY ROOM 19
RELAY
X
X
MONITORING ADD =174
L1 MO 16
AT FACP L.LEVEL
PULL _STATION
X
X
X
MONITORING ADD =175
L11025
L1M026
LlM027
COUNCEL CHAMBERS
COUNCEL CHAMBERS -
CONF.BY ROTUNDA
RELAY
RELAY
RELAY
X
X
X
X
X
X
X
X
X
MONITORING ADD =184
MONITORING ADD =185
MONITORING ADD =186
L1M029
SERVER RM SUPPRESION(SYSTEM)
L1 M030
L1 M031
PRIMARY ELEV. RECALL
SECONDARY ELEV. RECALL
--
CONV SMOKE
RELAY
RELAY
X !X
X
X
iX
X
X
X
X
MONITORING ADD =188
MONITORING ADD =189
MONITORING ADD =190
L1 M032
MECH RM. SMOKE
-
RELAY
X
X
-�
X !
MONITORING ADD= 91
L1 M033
CITY HALL TAMPER
TRACK SUPE_RV
X
X
X
MONITORING ADD =192
L1 M034
CITY ALL H WATER FLOW
FLOW
X
X
X
MONITORING ADD =193
L1 M035
PUBLIC WPRKS TAMPER
TRACK SUPERV
X
X
X
MONITORING ADD =194
L1 M036
PUBLIC WORKS WATER FLOW
FLOW IX
!X
X
MONITORING ADD =195
L1 M037
L.LEVEL MECH /ELEC
RELAY X�X
'X_
MONITORING ADD =196
L11038
L.LEVEL MECH /ELEC
RELAY
X
X
X
MONITORING ADD =197
L1 M039
AHU 1 RETURN DUCT
Sup.L(DUCTP )
X
X ix
MONITORING ADD =198
ECSI - Facility Fire Alarm Device Location And Test Log
Address
Location
Type_
Visual
Funct.
Pass
Fail
Comments
CITY OF OAK PARK HTS
Test
L1 M040
AHU 1 SUPPLY DUCT
Sup.L(DUCT_ P)_
X
X
X
MONITORING ADD =199
L1 M041
L.LEVEL MECH /ELEC
RELAY
X
X
X
MONITORING ADD =200
LlM042
ABOVE FURNACE
RELAY
X
X
X
MONITORING ADD =201
L1 M043
ABOVE FURNACE
RELAY
X
X
X
MONITORING ADD =202
L1 M044
ABOVE POLICE RECEPTION
RELAY
X
X
X
MONITORING ADD =203
L1 M045
ABOVE POLICE RECEPTION _
-
RELAY
X
X
X
MONITORING ADD =204
L1 M046
ABOVE WORK ROOM
RELAY _tX
X
X
_
MONITORING ADD =205
-
- - -- -