Loading...
HomeMy WebLinkAbout2003-03-18 Fire Marshal CommentsBa Fire Lep artment I 1 .1111, 294 N. 3 rd Street Ba MN. 55003 (651) 439-6992 Fax (651) 351-7051 Proudl Servin the Communities of: ort Ba Oak Park Hetr g _Vts,. and West Lakeland March 18, 2003 RE: Andersen Office Complex Fire Review (The old St. Croix Mall) J ud y Holst Cit of Oak Park Hei 14168 N Oak Park Hei Oak Park Hei MN. 55082 I've been reviewin the old St. Croix Mall fire protection prints sense Andersen Corporation purchased the propert The fire protection class chan from a Group M Occupancies (Mercantile) to a Group B Occupancies (Businesses). The sprinkler densit is g reater in a Group M than the Group B. With Herber still on the East side of the mall there is a mixed g roup class. Herber is still in a Group M. There are no special fire separation re for an M to a B. This fire sprinkler s is desi in what we call a pipe schedule s This is a fire protection sprinkler s that is based off of the number of heads, distance to the main, water main pressure, and re sprinkler densit The new fire protection sprinkler s are based off of the same criteria but with a computer pro The pipe schedule s have a hi level of safet factor built into the calculations. The mall sprinkler s is still based off a Group M sprinkler densit and a pipe-schedule s which is well above the re densit f actor for the sprinklers if the Mall.was to be built toda as an off ice buildin a Group B. It is sprinkled above and below all the ceilin a re do to the open area between the suspended ceilin All the sprinkler risers are monitored for water flow and all air handlin units have smoke detection. The buildin is divided into 10 sprinkler zones and 5 fire department connections. There is a fire h within the re distance to each fire department location. The one open issue is the location of fire h on the propert and the water main pipe size. Andersen Corporation has reviewed with me the construction prints and pipe sizes on the print. B the prints there are 3 water mains comin into the buildin (2) 8" water mains comin from Os and (1) 8" water main comin from 60th street. There is g ood fire h spacin except for the North side of the buildin There is no h between the h on Omaha Ave. and the h in front of Herber on the North side. Based off the sprinkler s the buildin fire loadin the buildin usa as a Group B, and the locations of emer exits and li I don't see a life safet problem. Therefore I'm not re the Andersen Corporation to add an additional h at this time. Re Brad Carmichael Fire Code Official Ba Fire Department